Buffer
Relay Wired In Door
Holder Circuit?
Like a door stop, a door holder keeps a fire door open.
When smoke is detected, the door holder releases, allowing the door to shut.
The door holder looks simple and innocuous enough, but it presents a special problem on installation.
The door holder looks simple and innocuous enough, but it presents a special problem on installation.
Between the Control Relay and the Door Holder Magnet, a
Buffer Relay prevents the magnet's turn-off voltage spike from harming the
Control Relay.
|
The Door Holder is an Electromagnet
A door holder prevents the door from closing because it
hangs onto the door using magnetism; making the magnetic field, electrical
current passes through the coil of the door holder.
When the fire alarm system detects smoke, the current to the door holder turns off, allowing the door to close.
That much is obvious.
What's not obvious is electromagnets are hard on the relay contacts turning the magnet off.
When the fire alarm system detects smoke, the current to the door holder turns off, allowing the door to close.
That much is obvious.
What's not obvious is electromagnets are hard on the relay contacts turning the magnet off.
The door holders are switched
on and off by an auxiliary relay - one that can handle the voltage spikes
produced by the door holders when they are turned off. The auxiliary relay is
turned on and off by the Fire Alarm Control Relay.
Transient Voltage Spike
An electromagnet, using the
energy from the electrical current, builds a magnetic field, and saves this
energy in the magnetism.
Once the electricity stops, the collapsing magnetic field generates a transient voltage spike. This voltage spike travels along the wires, back to the relay contacts.
Fire Alarm Control Relays are small, and each time this spike comes back, the contacts burn a little.
Once the electricity stops, the collapsing magnetic field generates a transient voltage spike. This voltage spike travels along the wires, back to the relay contacts.
Fire Alarm Control Relays are small, and each time this spike comes back, the contacts burn a little.
Burning Out the Contacts
Burning the contacts just a
little every time the relay turns off the door holder is bad because the
burning is cumulative. The damage from this repeated voltage spike adds up and
eventually destroys the contacts of the relay.
Regular testing of the Fire Alarm System is especially hard on the contacts. When testing, each time the fire alarm system is put into alarm, the relay is exercised, and the door holders burn out the relay contacts even quicker.
To prevent this transient voltage spike from burning out the control relay contacts, an auxiliary relay with big contacts should be installed between the Fire Alarm Control Relay and the door holders. Then the auxiliary relay takes the voltage spike, and the Fire Alarm Control Relay only has to turn off the auxiliary relay.
Regular testing of the Fire Alarm System is especially hard on the contacts. When testing, each time the fire alarm system is put into alarm, the relay is exercised, and the door holders burn out the relay contacts even quicker.
To prevent this transient voltage spike from burning out the control relay contacts, an auxiliary relay with big contacts should be installed between the Fire Alarm Control Relay and the door holders. Then the auxiliary relay takes the voltage spike, and the Fire Alarm Control Relay only has to turn off the auxiliary relay.
The Fire Alarm Control Relay
is only used as a "pilot duty" switch to keep the Auxiliary Relay
normally turned on. With an alarm, the Fire Alarm Control Relay switches off
the Auxiliary Relay, which in turn switches off the door holders.
Compatibility
Compatibility, though, is an
issue; even auxiliary relays can create problems for the Fire Alarm Control
Relays.
From an internal capacitor, some off-the-shelf auxiliary relays, when they first turn on, have a huge surge current. This surge current will weld the contacts of the small Fire Alarm Control Relay. Once welded, the contacts of the control relay are stuck together, and the relay will never turn off.
Even though their published coil currents look like they're compatible with the Fire Alarm Control Relay, the fire alarm manufacturer does not accept these auxiliary relays as compatible. Call your fire alarm manufacturer's tech support to make sure the auxiliary relay is computable with the Fire Alarm Control Relay.
From an internal capacitor, some off-the-shelf auxiliary relays, when they first turn on, have a huge surge current. This surge current will weld the contacts of the small Fire Alarm Control Relay. Once welded, the contacts of the control relay are stuck together, and the relay will never turn off.
Even though their published coil currents look like they're compatible with the Fire Alarm Control Relay, the fire alarm manufacturer does not accept these auxiliary relays as compatible. Call your fire alarm manufacturer's tech support to make sure the auxiliary relay is computable with the Fire Alarm Control Relay.
Auxiliary Relay Coil Circuit
The auxiliary relay coil is
also an electromagnet. To protect the Fire Alarm Control Relay from the
auxiliary relay's coil, type accepted auxiliary relays have an internal Flyback Diode already installed.
Long Term Reliability
The most important thing to
remember in all of this is that a door holder cannot be connected directly to a
Fire Alarm Control Relay, an auxiliary relay is required.
Without this auxiliary relay, there is a good chance that sometime down the road the control relay will fail and the door will not stay open.
Without this auxiliary relay, there is a good chance that sometime down the road the control relay will fail and the door will not stay open.
Most modern fire alarm common
controls manufactured today utilize common "on board" relay contacts
that are rated at 24 volts DC. They are designed to interface with a fire alarm
communicator for offsite monitoring of trouble, alarm, and supervisory
conditions. In many instances, you must provide additional relay contacts to
handle things like fan shutdown, fire dampers, etc.
110VAC door holders - Must utilize a
24VDC relay contactor that is triggered by a relay on the fire alarm's common
control. Under no circumstances should you run the 110VAC for the door holder
into the common control cabinet (although there are a number of older systems
out there in which this was perfectly acceptable, electrical codes have
changed). You must install the relay contactor into a separate box and ensure
you maintain a physical separation between the high voltage and low voltage
terminals. IMPORTANT! The door holders must utilize a 110VAC source that is
separate from the fire alarm system.
24VAC door holders - Must utilize a
24VDC relay contactor that is triggered through the fire alarm's common alarm
relay as well. You can install a relay block into the common control cabinet,
but the door holders must be powered by a 24VAC source that is independent of
the fire alarm system. Ensure that the cable entry for the 24VAC into the fire
alarm common control enclosure complies with the manufacturer's instructions
for non-power limited wires.
Signal Circuit Relays - For retrofit
installations (where it may not be possible to run wires all the way back to
the common control), Edwards (GE Security) manufactures the only UL/ULC listed
signal (NAC) circuit relay module for use on any conventional supervised signal
(NAC) circuit. The unit is listed as a "6554 Series Fire Alarm
Relay". The relay contacts are rated at 120VAC or 30 VDC, 5 amps
inductive, 3 amps resistive. The unit mounts inside a standard two gang (4x4)
deep box and comes complete with a appropriately labelled stainless steel
cover. You must exercise caution when employing this relay to trip anything
other than a door holder. Most new signal appliances don't ring continuously,
but are set to pulse temporarily, and some are programmed to silence manually.
When either of these circumstances occur, the relay will "follow" the
operation of the NAC circuit (in which case things like fan shutdown, elevator
recall, fire dampers may not function in the manner required by code). There is
a "workaround" for this however. You can employ a latching relay
contactor on the circuit. This will require the operator to manually reset the
device once the fire alarm system has been restored.
NOTE: If you're going to
be employing a remotely mounted latching contactor, please ensure that
appropriate instructions for resetting the circuit are posted on the fire alarm
control (and/or remote annunciator) and that those instructions also include
the location of the modules used to perform the required function.
The relay contacts are rated at 120VAC or 30 VDC, 5 amps inductive, 3 amps resistive. The unit mounts inside a standard 4x4 deep box and comes complete with a appropriately labeled stainless steel cover. It's manufactured by GE Security/Edwards and it's listed as a "6554 Series Fire Alarm Relay".
The relay contacts are rated at 120VAC or 30 VDC, 5 amps inductive, 3 amps resistive. The unit mounts inside a standard 4x4 deep box and comes complete with a appropriately labeled stainless steel cover. It's manufactured by GE Security/Edwards and it's listed as a "6554 Series Fire Alarm Relay".
NOTE: You must
exercise caution when employing this relay to trip anything other than a door
holder. Most new signal appliances don't ring continuously, but are set
to pulse temporarily, and some are programmed to silence manually. When
either of these circumstances occur, the relay will "follow" the
operation of the NAC circuit (in which case things like fan shutdown, elevator
recall, fire dampers may not function in the manner required by code).
There is a "work-around" for this however. You can employ a latching
relay contactor on the circuit. This will require the operator to
manually reset the device once the fire alarm system has been restored. In
this scenario, appropriate instructions must be posted on the fire alarm
control (and/or remote annunciator).
It is an informative post.
ReplyDeleteI have no words to appreciate this post. It is just an outstanding source of knowledge on this topic with a technical writing essays. In the outline reveal all important points which explained in this post.
ReplyDeletefire and safety institute in chennai
ReplyDeletefire safety course
fire and safety course
fire & safety course in chennai
diploma in industrial safety course
safety training institute in chennai
industrial safety management course in chennai
safety officer course
Thank you for the above post. Very detailed explanation.
ReplyDeleteNebosh course in Chennai
Nebosh IGC course in Chennai
Nebosh
Nebosh HSW course in Chennai
IOSH course in Chennai
HABC course in Chennai
OHSAS 18001:2007 Lead Auditor course in Chennai
safety training institute
fire safety training in Chennai
I have no words to appreciate this post. It is just an outstanding source of knowledge on this blog
ReplyDeleteAmazing blog
ReplyDeleteI like the way you design it. But, I always recommend being precautioned as a Safety professional by learning all the fire safety skills from Fire safety courses in Chennai @Nationalsafetyschool.com. If you're interested in such kinda stuff, feel free to check out it. Thank you!
NEBOSH Course in Chennai
Fire and Safety Course in Chennai
IOSH Course in Chennai
UnikCCTV offer best Security and Surveillance system which are offer in market right now. These systems can range from wireless home security cameras to sophisticated alarm systems that notify law enforcement at the first sign of trouble. This will ensures safety of your good and services. Our online store packed with different kind of security systems like contactless door lock, intercom with inbuild video camera, microphone & screen, and many more.
ReplyDeleteThat make up return made my smirks teary since my amateur premonition the archetype singing, detrimental absolutely consequently it is too well written for the 6 grader, on the alternative fist similarly--assist flavorless strenuous importantly--so in the raining nexus everywhere a preteen plus an juvenile appropriate resonant considers. jual fire door
ReplyDeleteThis comment has been removed by the author.
ReplyDeleteUnikCCTV offer best Security and Surveillance system which are offer in market right now. These systems can range from wireless home security cameras to sophisticated alarm systems that notify law enforcement at the first sign of trouble. This will ensures safety of your good and services. Our online store packed with different kind of security systems like contactless door lock, intercom with inbuild video camera, microphone & screen, and many more.
ReplyDeleteNice blog!
ReplyDeleteAre you searching for a service center in Dubai for your Macbook?? Scorpionfix is here, one of the best Apple service center in Dubai.
Surface pro 8 repair in Sharjah
Surface pro service center Sharjah
Surface pro service center Dubai
Macbook repair in Sharjah
Macbook repair in Dubai.
Laptop repair in Dubai
Laptop repair in Sharjah
Surface pro 8 repair in Dubai
macbook service center abu dhabi
macbook repair abu dhabi
Laptop repair abu dhabi
Laptop service center abu dhabi
Apple service center Sharjah
A safety course equips individuals with crucial skills to identify and manage risks effectively, ensuring a safer environment. It includes training on safety protocols, emergency procedures, and hazard prevention strategies.
ReplyDeleteIndustrial Safety course in chennai
Fire and Industrial safety course in Chennai
Safety Courses in chennai
Fire and safety courses in Chennai
Lead auditor course in Chennai
IOSH Managing Safely course in Chennai
Our accredited fire door inspection service ensures that your fire doors are fully compliant, safe, and effective in protecting lives and property. Regular inspection of fire doors is essential to identify potential issues like misalignment, wear, or damage that could compromise their function in an emergency. Our experienced inspectors conduct a thorough assessment, checking for proper installation, certification, gaps, seals, hinges, and hardware to verify that each door meets the required safety standards. Following the inspection, we provide a detailed report with recommendations for repairs or replacements if necessary. With our expert guidance, you can maintain optimal fire safety and compliance for your premises. Explore our extensive range of fire door survey by clicking this link to access our catalog, where you'll find detailed descriptions, pricing information, and customer reviews.
ReplyDelete