Thursday, July 15, 2021

Cybersecurity for Fire Alarm Systems

 Cybersecurity for Fire Alarm Systems

Active fire protection typically requires some sort of input, such as a person triggering a fire alarm. Where it is automatic, such as with sprinklers or alarms which detect smoke and fire, these systems are usually localised, operating only within a certain vicinity. To turn them off, you usually have to access a valve or control panel and make the change manually.

From cell phones to refrigerators, we live in an interconnected world. The Internet of Things (IoT) is the network of physical objects — such as cars, thermostats and watches — that have the ability to exchange data and interoperate with existing network infrastructure. They transmit data to manufacturers, owners or other devices, and can be sensed and controlled remotely. It provides us with real-time control and information from IoT-enabled products and systems.

Networked fire Alarm systems have a number of advantages over these traditional ones. If an alarm goes off, for instance, a networked system can tell you exactly where it is and when it was activated, giving you more information that you can use to take action. It can also allow you to link different parts of a building or site without running cables between them, and can allow you to operate it remotely, either to turn it off or for testing.  Today’s IoT smart buildings include two types of connected technologies: information technology (IT) and operational technology (OT).

Fire alarm control units, intrusion detection systems, mass notification systems and access control systems reside on the OT side usually managed by facilities operations. Both systems have vulnerabilities that commonly include equipment tampering as well as inside and outside threats. Firewalls and other cyber protection processes and devices can help mitigate the potential for a widespread attack and protect the individual components of the IT or OT systems. 

Cyber vulnerabilities can have a dramatic consequence if these products and systems are not properly protected. Building sensors can provide early detection of unwanted events such as intrusion or fire. Cameras are used for monitoring and remote surveillance that may communicate with alarm control units that can in turn provide information to end users and monitoring stations. Historically these products were hardwired, but technology has enabled us to communicate either wirelessly or wired through an IT infrastructure that is also linked to the internet. Electronic life safety and physical security infrastructures include emergency communications systems, fire alarm systems, alarm receiving systems, automated teller machine systems, access control systems, surveillance cameras, DVRs, NVRs and the like.

There are a variety of codes, standards and best practice guidelines that can help guide creation of a cybersecurity program. Fire alarm control units may include two types of software: executive software and site-specific software. These applications are covered by UL 864, the Standard for Safety of Control Units and Accessories for Fire Alarm Systems, and NFPA 72. Under part of UL 864, third-party certifiers execute and test the equipment’s software for integrity of normal operation. UL 5500, the & Standard for Safety for Remote Software Updates, covers best practices for software patches and updates. UL 5500 offers guidance on technical attributes necessary for the remote connection to smart devices and safe functionalities and securely executing remote software downloads. Most smart systems rely on the ability to update software remotely or onsite. UL 5500 applies to these applications in conjunction with the product’s end standard. To evaluate through tests, the cybersecurity of critically connected life safety and electronic physical security systems, Underwriters Laboratories has published UL 2900-2-3, the Standard for Software Cybersecurity for Network-Connectable Products, Part 2-3: Particular Requirements for Security and Life Safety Signaling Systems. This newest addition to the UL 2900 series of cybersecurity Standards was developed as a bi-national (U.S. and Canada) consensus Standard and with industry input. It provides a foundational set of cybersecurity performance and evaluation requirements that manufacturers of network connectable products can use to establish a baseline of cyber protection against known vulnerabilities, weaknesses and malware. UL 2900-2-3 was developed specifically for security and life safety equipment and systems. It is a testable standard (not limited to audit-based investigations) applicable to IoT connected equipment such as fire alarm control units, mass notification systems, access control equipment and smoke alarms. For UL 2900-2-3, a three-tiered security approach was developed with an increasing level of security requirements for each tier.

The National Fire Protection Association (NPFA) Code 72 (National Fire Alarm and Signaling Code) describes reacceptance testing of equipment and systems when site-specific or executive software changes have been made and the equipment is commissioned and already in use. Site specific software update requires a 100% test of all functions known to be affected by the change. Currently, 10% of initiating devices that are not directly affected by the change (up to 50 devices) must be tested to verify correct system operation and a record of completion must be kept. These commonsense requirements help ensure full integrity of software changes. However, it would be challenging for any end user or code authority to directly verify that the software changes did not affect the integrity or operation of the system or equipment without additional testing or investigation. Third-party validation, reconfirmation and field testing is crucial. The work on the 2022 edition of NFPA 72, National Fire Alarm and Signaling Code is at the halfway point. The work on the first draft has been completed. In NFPA 72 2022 edition cybersecurity has been added. This is in addition to requirements to be added to 72 addressing cybersecurity that will be included in a new Chapter 11 and references the associated Annex J to address cybersecurity guidance. The Technical Committee on Fundamentals has been tasked with the development of the new chapter on cybersecurity. This chapter is still in development and will not be finalized until the second draft meeting to be held later this year. There is a task group made up of members from a number of the technical committees that are working on the requirements for cybersecurity.

At the time of the first draft this was still located in Chapter 10. At the close of the first draft, the following text was added:

Systems shall be designed and installed in accordance with one or more of the following cybersecurity standards:
(1) ANSI/ISA-62443 Series
(2) NIST Framework for Improving Critical Infrastructure Cybersecurity Version 1.1
(3) UL 2900 Series
(4) or other standards accepted by the authority having jurisdiction.

This is not the final version.

I recommend the use of the EST4, which is an industrial or commercial life safety system with a firewall solution from EDWARDS. The EST4 Life Safety System is a state-of-the-art system with a firewall built to add several layers of protection to your systems. The EST4 comes with a 4-FWAL firewall, which blocks all traffic not needed for EST4 operation. It also features impenetrable 256 bit AES encryption securing the traffic through the EST4, including emails and communication with fire operation centres.  At SSA Integrate are ready for migration from EST3 to EST4 without changes of field component, with minimising financial impact.

 

Conclusion 

In today’s connected world, the variety of available devices offers numerous points of entry for cyberattacks. Now is the time for software developers and manufacturers to understand a system's vulnerabilities and to harden their product against cyberattacks. Verifying that alarm systems meet appropriate standards can help ensure the performance and reliability of a product’s software to decrease downtime and mitigate cyber risks. A safety system with a firewall is the most viable solution for this problem. A firewall is a comprehensive cybersecurity solution able to protect a fire alarm system and its IT infrastructure from unauthorized access.

If your Fire Alarm connect with IoT devices / Internet, then only your FACP is get entry for cyberattacks. If your FACP use as standalone basis or not connected with Internet any more than your FACP is completely safe for cyberattacks. In India most of FACP not connect with Internet so it’s safe from cyberattacks. Lots of customer having Control remotely Like: Two EST3 panel are in Kolkata, One EST3x in Bangalore & one EST3 in Delhi, Customer control via FireWorks all panel from Kolkata, in this case you must consider cyber security part for your estimate organization. Responsible System Integrator or OEM can’t offer you cyber vulnerable product.


Thursday, July 1, 2021

Smoke Detector Testing

Smoke Detector Testing 

Requirements for testing of smoke detectors vary by country, the common need is for a functional test where smoke, or simulated smoke, is introduced through the vents of the detector to the sensor.

Functional testing is required by all national standards around the world, including BS: 5839, DIN 14675 and NFPA 72. BS:5839-1 which, at its last update, stated: “Multi-sensor fire detectors should be physically tested by a method that confirms that products of combustion in the vicinity of the detector can reach the sensors and that the appropriate response is confirmed at CIE.” (45.4(j).  It highlights that each sensor on which a fire detection decision depends (e.g. smoke, heat, CO) should be physically tested individually. This means that functional testing needs to be carried out on both the smoke and heat sensors, this ultimately requires spending more time under each detector and on a site where multi-sensors are the dominant device, this can add significant time to a site visit.  In this situation access to an all-in-one test solution adds real value, not only does it mean less time spent changing between testers but it also means less tools are required to be carried around site – reducing disruption and improving productivity.

A functional test should be carried out using an appropriate test tool which is designed for purpose and will cause no damage to the detector under test.

If you have standalone smoke detector, test the alarm monthly. Replace the batteries at least once every year. Replace the entire smoke alarm every 10 years. Press and hold the test button on the smoke detector. It can take a few seconds to begin, but a loud, ear-piercing siren should emanate from the smoke detector while the button is pressed. If the sound is weak or non-existent, replace your batteries. Most of Standalone detectors have either a blinking or a solid light that glows to let you know that the alarm is getting power. 

Before starting the testing job for 2wire / 4wire smoke detector, take the proper work permit and inform to all the respective departments / authority. Then do force the respective logics or interlocks if any (like fire suppression systems activation etc).

§  Prior to testing of Smoke detector see the LED status of the Smoke Detector it should be blinking red.

§  Check the voltage of the Smoke Detector, it should be + 30 Volts DC. This can be checked at the addressable base of the detector.

§  Now Smoke Detector is healthy and it is ready for testing.

§  Clean the Smoke Detector’s dust by cotton cloth and blower

§  Apply the aerosol spray to the Smoke Detector by solo Smoke detecting gun with the help of the Solo A10S/A5 aerosol bottle.

§  Keep applying aerosol spray for 10 seconds.

§  After 10 seconds LED status of the Smoke detector will change from the steady blinking red to steady red and after that alarm appears and hooter is activated on the fire alarm panel.

§  To silence the hooter press acknowledge key on the Fire Alarm Panel.

§  After alarm appears remove Smoke detecting test gun from Smoke Detector.

§  Note down the alarm tag and descriptions from the HMI or workstation. The alarm details must match with the smoke detector tag number and installed location.

§  Confirm the smoke detector activation status from the respective graphics page. You have to visually identify the colour change signals of the respective smoke detector on the graphics.

§  Reset the alarm of the Smoke detector from Fire Alarm Panel.

§  The LED status will change from steady red to blinking red.

§  Smoke Detector is now working normally.

§  Repeat the above procedure for all the remaining smoke detectors.

§  Normalize the forced interlocks or logics if any.

§  Close the work permit.

Note: The mentioned voltages or LED colors sequence may change as per the vendor or model of the smoke detectors. Solo Smoke Aerosols is approved all over the world, its Non-toxic & Silicone free. Solo smoke aerosols (used with the Solo 330/332 dispensers) deliver smoke particles to the detector under test replicating the conditions of smoke from a fire. Our range of smoke aerosols has recently increased to allow continued use of Solo 330/332 dispensers in full compliance with latest regulations.

BS:5839-1 as the example once again, the 2017 update to the standard covered this by stating: “For remotely situated or hard-to-access detection equipment, consideration needs to be given to the feasibility of testing and maintenance at the design stage.” (Clause 22.1).

Unique Formula Identifier (UFI), is a 16 character alphanumeric code which will soon be required to appear on the labelling of all products classified as hazardous by the ECHA. This new directive is designed to enable faster identification of product contents, with the UFI code used to detail the composition, product category and toxicological information of the product and enable faster reaction and treatment of potential harm.

UFI codes will become mandatory on relevant products across Europe from January 2021.

Do remember A10S is globally approved non-flammable UL listed product.

Tuesday, June 15, 2021

MCP Testing

MCP Testing

Manual Call Point is a device for the manual initiation of an alarm.

Manual fire alarm activation is typically achieved through the use of a pull station (term used in USA & Canada) or call point (term used in Europe, Australia, and Asia), which then sounds the evacuation alarm for the relevant building or zone. Manual fire alarm activation requires human intervention.

Manual Call Points (MCPs) are referred to or referenced by different names in various regions worldwide like Break Glass Units (BGs), Pull Stations, Push Buttons, Alarm Points, etc.

When should a Manual Call Point be used? In the event of a fire in a building; or if there is no automatic detection activated by the installed heat & smoke detection or any other detectors; or if you discover the fire personally and if there is an emergency condition – you need to activate the Manual Call Point to trigger the Fire Detection And Alarm System (FDAS) in the building so that the system initiates the necessary notification devices and sends signals to many other third party systems (Voice Evacuation, Emergency Lighting, Smoke Control, Lifts, etc.) in the building.

🔴 Manual Call Point (MCP)
✔ Commonly used term in the UK, Europe, Middle East, and UAE
✔ Typically incorporates a break-glass or resettable element
✔ Allows manual activation of the fire alarm during an emergency
✔ Governed by EN 54 and adopted in the UAE Fire & Life Safety Code

🔴 Manual Pull Station
✔ Common term used in NFPA / North American standards; typically UL-listed
✔ Operated by pulling a lever or handle
✔ Performs the same function as a Manual Call Point
✔ Covered under NFPA 72 and acceptable under the UAE Fire & Life Safety Code

🔴 Break Glass Unit
✔ Describes the activation mechanism, not the system function
✔ Can form part of a Manual Call Point
✔ Requires breaking a glass or frangible element to operate
✔ Modern systems often use resettable (non-breakable) elements

How to Activate a Manual Call Point? There are different types of manual call points.
1. Break Glass Unit – Break the glass, and then the signal will be sent to the system
2. Pull Station – Pull the lever, and then the signal will be sent to the system
3. Break Glass with Double Action cover – Lift the cover and break the Glass
4. Pull Station with double action cover – Lift the cover and pull the lever
5. Push Button type – Push the button, and the signal will be sent to the system

There are many different types; most often, when installed for FDAS, they are installed in red housing or casing for easy identification; however, in some jurisdictions, these can be other colours for architectural aesthetical purposes. It is always important to check with the authority having jurisdiction and to ensure the MCPs are readily recognisable, easily identified and signed as per the local guidelines and regulations.

Before starting the job, take the proper work permit and inform to all the respective departments. Also, do force the respective logics or interlocks if any (like fire suppression systems activation etc).

§  Remove all the screws and remove the glass cap from MCP.

§  After removing the glass cap from MCP,  the switch inside it activates so alarm appears on Fire alarm panel and the hooter is activated.

§  Acknowledge the alarm or silence the hooter on the fire alarm panel.

§  Note down the alarm tag and descriptions from the HMI or workstation. The alarm details must match with the MCP tag number and installed location.

§  Confirm the MCP activation status from the respective graphics page. You have to visually identify the color change signals of the respective MCP on the graphics.

§  Check the + 36 Volts DC Supply on Monitor Module between terminal 1 and 2. (This is the circuit module inside the MCP).

§  Check all the wire connections on Monitor Module, the push button contact if it found loose then tighten them fully.

§  Ensure resistor leads are completely tightened on to the terminals of the circuit in MCP.

§  Clean the MCP dust by brush and cotton cloth.

§  Fix the glass cap of MCP and fix all screws. It should be fully tightened. If it is loose alarm reappears.

§  Reset the alarm signal from the Fire Alarm Panel.

§  Now MCP is working now in Normal condition.

§  Repeat the above procedure for all the remaining MCP’s.

§  Normalize the forced interlocks or logics if any.

§  Close the work permit.

Note: The mentioned voltages, terminals, circuit module names may change as per the vendor or model of the Manual Call Point.

As per UAE Fire and Life Safety Code:-
🔥 The manual call points shall be used only for fire alarm initiation. In addition, all manual call points within an occupancy shall be of similar design.
🔥 Distribution of the manual call points should be such that the travel distance should not be more than 61m to reach the nearest manual call point.
🔥 These figures are to be reduced to 25m and 16m in limited mobility areas and where processes of the area result in a likelihood of rapid-fire development.
🔥 A Manual Call Point shall be installed within 1.5 m from the exit door opening.
🔥 The manual call points shall be installed generally at the height of 1.2 m, above floor level, and in plain, accessible, well-lit, and free-hindrances places.

👉 To allow occupants to manually initiate a fire alarm signal
Understanding correct terminology helps prevent miscommunication during design, approval, installation, and inspections, especially on international projects.

If you would like to discuss further with us on MCPs and FDAS, don’t hesitate to get in touch with one of our technical experts.

Tuesday, June 1, 2021

T-Tapping in Fire Loop Line

 T-Tapping in Fire Loop Line

A fire alarm “T-Tap” is merely a parallel tap into the loop. The reason T-Tap wiring is allowed is because communications are being supervised to the device level. T-Tapping the different legs of the SLC provide multiple communications paths of the field devices and control equipment.
The answer to the question of how many T-Taps is allowed --- is "It Depends". It depends on the manufacturer and it depends on how easy the installer wants to make the system for the technician when servicing the system for the coming years. On a conventional system “T-Tap” not working.

Style 4 wiring (somewhat similar to Class B wiring), which is the data-loop or signaling line circuit (SLC), allows an unlimited number of T-Taps, at least for most manufacturers. Signaling Line Circuit (SLC), carries signals in the form of data between the panel and the input and output devices. Canada calls "Class B Level 1" "Data Communications Link (DCL) Style B". Someone called Initiating Device Circuit (IDC), its carries signals from the input devices to the panel.

Field Devices Connected to an SLC/DCL/IDC.

Input

·        Smoke Detectors

·        Heat Detectors

·        Combination Smoke/Heat Detectors

·        Pull Stations

·        Alarm and Supervisory Input Modules

Output

·        Control Relays

·        NAC Riser Modules

o   24 VDC Audible

o   24 VDC Visible

o   24 VDC Combination Audible/Visible

o   Audio for Speakers (Direct Current (DC) blocking capacitor allows 70.7 VAC 200-20KHz through) independent of other audio.

o   Firefighter’s Phone

Every device on a Signaling Line Circuit is a T-Tap for the Panel.

 
Long Star-Taps

Most fire alarm systems that use Style 4 wiring for the SLC are electronically connecting every device directly to the terminals of the fire alarm panel. Being wire nutted at all junctions, electrically the wire loop is a single pair of copper conductors. 

For all practical purposes, all devices on the loop are connected directly to the panel, and the panel can't tell the difference between home runs to each device and a single daisy chain. 

Yes, the installed wiring may daisy chain to 75 devices in a straight line, but electrically, every last one of them is connected directly to the terminals of the fire alarm panel. 

For these types of systems, the wires can be thought of as having a long star-tap. 

Later Servicing the System

The real concern with the T-Taps is with the later servicing of the system. When trying to find a ground fault or bad device. A limited number of T-Taps makes it easy to divide up the system. 
Not enough T-Taps and the technician has to guess where the wires run through the building. Too many T-Taps and the technician has to pull a lot of T-Taps apart to get an idea of where to find the faulty device or wiring. 

Manufacturer's T-Tap Limit

The manufacturers that limit the number of T-Taps have an input side and an output side to each device on the SLC. Here the panel itself is creating a map of the SLC wiring system. If there are too many t-taps, or if the ins and outs of the devices are not wired according to the installation sheets, the panel's created maps become useless for later servicing. 

How Many T-Taps

When trying to determine how many T-Taps are allowed, consult the manufacturer' installation sheets, and then decide on how easy the servicing of the system should be in the coming years.

If you still aren't sure how you manage your building / establishment loop line, feel free to get in touch with one of our experts via ssaintegrate@gmail.com. Before selecting vendor / installer check and verify they are authorized or not to execute your Fire Detection & Alarm system work. Its mandatory Fire Detection & Alarm System (Edwards, ESSER, Notifier, Autronica, Cooper, BOSCH & GST etc) commissioned by certified professional.


Tuesday, May 11, 2021

Heat Detector Testing

 Heat Detector Testing

Heat detector can be defined as an element or device that detects changes in heat or fire. If any heat (change in heat that exceeds the limits of heat sensor ratings) is sensed by the heat sensor, the heat sensor generates a signal for alerting or activating a security or protection system to extinguish or avoid the fire accidents. There are different types of heat sensors, which are classified based on different criteria such as the amount of heat withstanding capacity, nature of heat sensing capacity, and so on. Furthermore, the heat sensors are classified into different types that include analog heat sensors and digital heat sensors.

Heat detector can sense the heat (change in heat according to the features of heat detector used). But, a circuit is to be designed for activating an alarm system to indicate fire or heat change and for alerting the security or protection system. Heat detector circuit can be designed using heat sensor.

These heat detectors are mainly classified into two types based on their operation and they are “rate of rise heat detectors” and “fixed temperature heat detectors”.

Before starting the job, take the proper work permit and inform to all the respective departments. Then do force the respective logics or interlocks if any (like fire suppression systems activation etc).

§  Prior to testing of Heat detector see the LED status of the Heat Detector it should be blinking red.

§  Check the voltage of the Heat Detector, it should be + 30 Volts DC. This can be checked by the addressable base of the detector. (Digital type detector).

§  Now Heat Detector is healthy and it is ready for testing.

§  Clean the Heat Detector’s dust by cotton cloth and blower

§  Apply the heat to the Heat Detector by solo heat-detecting gun.

§  Keep applying heat for 10 seconds.

§  After 10 seconds LED status of the Heat detector is changing from steady blinking red to steady red and after that alarm appears and the hooter is activated on the fire alarm panel.

§  To silence the hooter press the acknowledge key to the Fire Alarm Panel.

§  After the alarm appears remove the heat-detecting test gun from Heat Detector.

§  Note down the alarm tag and descriptions from the HMI or Graphic workstation. The alarm details must match with the heat detector tag number and installed location.

§  Confirm the heat detector activation status from the respective graphics page. You have to visually identify the colour change signals of the respective heat detector on the graphics.

§  Reset the alarm of the Heat detector from the Fire Alarm Panel.

§  The LED status is changing from steady red to blinking red.

§  Heat Detector is now working normally.

§  Repeat the above procedure for all the remaining Heat Detectors.

§  Normalize the forced interlocks or logics if any.

§  Close the work permit.

Note: The mentioned voltages, terminals, circuit module names may change as per the vendor or model of the Heat Detector. Available in both 110 / 120 and 220 / 240 volt versions the Solo 423 and 424 are the professionals’ choice where cables and leads are acceptable. Unconstrained by energy availability they provide the quickest of test times and are, perhaps, most suitable for the highest temperature detectors.