Smoke Detector Testing
§ Prior to testing of
Smoke detector see the LED status of the Smoke Detector it should be blinking
red.
§ Check the voltage of the
Smoke Detector, it should be + 30 Volts DC. This can be checked at the addressable base
of the detector.
§ Now Smoke Detector is
healthy and it is ready for testing.
§ Clean the Smoke
Detector’s dust by cotton cloth and blower
§ Apply the aerosol spray
to the Smoke Detector by solo Smoke detecting gun with the help of the Solo A10S/A5
aerosol bottle.
§ Keep applying aerosol
spray for 10 seconds.
§ After 10 seconds LED
status of the Smoke detector will change from the steady blinking red to steady
red and after that alarm appears and hooter is activated on the fire alarm
panel.
§ To silence the hooter press
acknowledge key on the Fire Alarm Panel.
§ After alarm appears
remove Smoke detecting test gun from Smoke Detector.
§
Note down the alarm tag and descriptions from the
HMI or workstation. The alarm details must match with the smoke detector tag number
and installed location.
§
Confirm the smoke detector activation status from
the respective graphics page. You have to visually identify the colour change
signals of the respective smoke detector on the graphics.
§ Reset the alarm of the
Smoke detector from Fire Alarm Panel.
§ The LED status will
change from steady red to blinking red.
§ Smoke Detector is now
working normally.
§
Repeat the above procedure for all the
remaining smoke detectors.
§
Normalize the forced interlocks or logics if any.
§ Close the work permit.
Note: The
mentioned voltages or LED colors sequence may change as per the vendor or model
of the smoke detectors. Solo Smoke Aerosols is approved all over the
world, its Non-toxic & Silicone free. Solo smoke aerosols (used with the
Solo 330/332 dispensers) deliver smoke particles to the detector under test
replicating the conditions of smoke from a fire. Our range of smoke aerosols
has recently increased to allow continued use of Solo 330/332 dispensers in
full compliance with latest regulations.
BS:5839-1 as the example once again,
the 2017 update to the standard covered this by stating: “For
remotely situated or hard-to-access detection equipment, consideration needs to
be given to the feasibility of testing and maintenance at the design stage.” (Clause 22.1).
Unique
Formula Identifier (UFI), is a 16 character alphanumeric code which will soon
be required to appear on the labelling of all products classified as hazardous
by the ECHA. This new directive is designed to enable faster identification of
product contents, with the UFI code used to detail the composition, product
category and toxicological information of the product and enable faster
reaction and treatment of potential harm.
UFI codes will become mandatory on relevant products across Europe from January 2021.
Do remember A10S is globally approved non-flammable UL listed product.