Showing posts with label IS 2189. Show all posts
Showing posts with label IS 2189. Show all posts

Thursday, July 1, 2021

Smoke Detector Testing

Smoke Detector Testing 

Requirements for testing of smoke detectors vary by country, the common need is for a functional test where smoke, or simulated smoke, is introduced through the vents of the detector to the sensor.

Functional testing is required by all national standards around the world, including BS: 5839, DIN 14675 and NFPA 72. BS:5839-1 which, at its last update, stated: “Multi-sensor fire detectors should be physically tested by a method that confirms that products of combustion in the vicinity of the detector can reach the sensors and that the appropriate response is confirmed at CIE.” (45.4(j).  It highlights that each sensor on which a fire detection decision depends (e.g. smoke, heat, CO) should be physically tested individually. This means that functional testing needs to be carried out on both the smoke and heat sensors, this ultimately requires spending more time under each detector and on a site where multi-sensors are the dominant device, this can add significant time to a site visit.  In this situation access to an all-in-one test solution adds real value, not only does it mean less time spent changing between testers but it also means less tools are required to be carried around site – reducing disruption and improving productivity.

A functional test should be carried out using an appropriate test tool which is designed for purpose and will cause no damage to the detector under test.

If you have standalone smoke detector, test the alarm monthly. Replace the batteries at least once every year. Replace the entire smoke alarm every 10 years. Press and hold the test button on the smoke detector. It can take a few seconds to begin, but a loud, ear-piercing siren should emanate from the smoke detector while the button is pressed. If the sound is weak or non-existent, replace your batteries. Most of Standalone detectors have either a blinking or a solid light that glows to let you know that the alarm is getting power. 

Before starting the testing job for 2wire / 4wire smoke detector, take the proper work permit and inform to all the respective departments / authority. Then do force the respective logics or interlocks if any (like fire suppression systems activation etc).

§  Prior to testing of Smoke detector see the LED status of the Smoke Detector it should be blinking red.

§  Check the voltage of the Smoke Detector, it should be + 30 Volts DC. This can be checked at the addressable base of the detector.

§  Now Smoke Detector is healthy and it is ready for testing.

§  Clean the Smoke Detector’s dust by cotton cloth and blower

§  Apply the aerosol spray to the Smoke Detector by solo Smoke detecting gun with the help of the Solo A10S/A5 aerosol bottle.

§  Keep applying aerosol spray for 10 seconds.

§  After 10 seconds LED status of the Smoke detector will change from the steady blinking red to steady red and after that alarm appears and hooter is activated on the fire alarm panel.

§  To silence the hooter press acknowledge key on the Fire Alarm Panel.

§  After alarm appears remove Smoke detecting test gun from Smoke Detector.

§  Note down the alarm tag and descriptions from the HMI or workstation. The alarm details must match with the smoke detector tag number and installed location.

§  Confirm the smoke detector activation status from the respective graphics page. You have to visually identify the colour change signals of the respective smoke detector on the graphics.

§  Reset the alarm of the Smoke detector from Fire Alarm Panel.

§  The LED status will change from steady red to blinking red.

§  Smoke Detector is now working normally.

§  Repeat the above procedure for all the remaining smoke detectors.

§  Normalize the forced interlocks or logics if any.

§  Close the work permit.

Note: The mentioned voltages or LED colors sequence may change as per the vendor or model of the smoke detectors. Solo Smoke Aerosols is approved all over the world, its Non-toxic & Silicone free. Solo smoke aerosols (used with the Solo 330/332 dispensers) deliver smoke particles to the detector under test replicating the conditions of smoke from a fire. Our range of smoke aerosols has recently increased to allow continued use of Solo 330/332 dispensers in full compliance with latest regulations.

BS:5839-1 as the example once again, the 2017 update to the standard covered this by stating: “For remotely situated or hard-to-access detection equipment, consideration needs to be given to the feasibility of testing and maintenance at the design stage.” (Clause 22.1).

Unique Formula Identifier (UFI), is a 16 character alphanumeric code which will soon be required to appear on the labelling of all products classified as hazardous by the ECHA. This new directive is designed to enable faster identification of product contents, with the UFI code used to detail the composition, product category and toxicological information of the product and enable faster reaction and treatment of potential harm.

UFI codes will become mandatory on relevant products across Europe from January 2021.

Do remember A10S is globally approved non-flammable UL listed product.

Tuesday, June 15, 2021

MCP Testing

MCP Testing

Manual Call Point is a device for the manual initiation of an alarm.

Manual fire alarm activation is typically achieved through the use of a pull station (term used in USA & Canada) or call point (term used in Europe, Australia, and Asia), which then sounds the evacuation alarm for the relevant building or zone. Manual fire alarm activation requires human intervention.

Manual Call Points (MCPs) are referred to or referenced by different names in various regions worldwide like Break Glass Units (BGs), Pull Stations, Push Buttons, Alarm Points, etc.

When should a Manual Call Point be used? In the event of a fire in a building; or if there is no automatic detection activated by the installed heat & smoke detection or any other detectors; or if you discover the fire personally and if there is an emergency condition – you need to activate the Manual Call Point to trigger the Fire Detection And Alarm System (FDAS) in the building so that the system initiates the necessary notification devices and sends signals to many other third party systems (Voice Evacuation, Emergency Lighting, Smoke Control, Lifts, etc.) in the building.

🔴 Manual Call Point (MCP)
✔ Commonly used term in the UK, Europe, Middle East, and UAE
✔ Typically incorporates a break-glass or resettable element
✔ Allows manual activation of the fire alarm during an emergency
✔ Governed by EN 54 and adopted in the UAE Fire & Life Safety Code

🔴 Manual Pull Station
✔ Common term used in NFPA / North American standards; typically UL-listed
✔ Operated by pulling a lever or handle
✔ Performs the same function as a Manual Call Point
✔ Covered under NFPA 72 and acceptable under the UAE Fire & Life Safety Code

🔴 Break Glass Unit
✔ Describes the activation mechanism, not the system function
✔ Can form part of a Manual Call Point
✔ Requires breaking a glass or frangible element to operate
✔ Modern systems often use resettable (non-breakable) elements

How to Activate a Manual Call Point? There are different types of manual call points.
1. Break Glass Unit – Break the glass, and then the signal will be sent to the system
2. Pull Station – Pull the lever, and then the signal will be sent to the system
3. Break Glass with Double Action cover – Lift the cover and break the Glass
4. Pull Station with double action cover – Lift the cover and pull the lever
5. Push Button type – Push the button, and the signal will be sent to the system

There are many different types; most often, when installed for FDAS, they are installed in red housing or casing for easy identification; however, in some jurisdictions, these can be other colours for architectural aesthetical purposes. It is always important to check with the authority having jurisdiction and to ensure the MCPs are readily recognisable, easily identified and signed as per the local guidelines and regulations.

Before starting the job, take the proper work permit and inform to all the respective departments. Also, do force the respective logics or interlocks if any (like fire suppression systems activation etc).

§  Remove all the screws and remove the glass cap from MCP.

§  After removing the glass cap from MCP,  the switch inside it activates so alarm appears on Fire alarm panel and the hooter is activated.

§  Acknowledge the alarm or silence the hooter on the fire alarm panel.

§  Note down the alarm tag and descriptions from the HMI or workstation. The alarm details must match with the MCP tag number and installed location.

§  Confirm the MCP activation status from the respective graphics page. You have to visually identify the color change signals of the respective MCP on the graphics.

§  Check the + 36 Volts DC Supply on Monitor Module between terminal 1 and 2. (This is the circuit module inside the MCP).

§  Check all the wire connections on Monitor Module, the push button contact if it found loose then tighten them fully.

§  Ensure resistor leads are completely tightened on to the terminals of the circuit in MCP.

§  Clean the MCP dust by brush and cotton cloth.

§  Fix the glass cap of MCP and fix all screws. It should be fully tightened. If it is loose alarm reappears.

§  Reset the alarm signal from the Fire Alarm Panel.

§  Now MCP is working now in Normal condition.

§  Repeat the above procedure for all the remaining MCP’s.

§  Normalize the forced interlocks or logics if any.

§  Close the work permit.

Note: The mentioned voltages, terminals, circuit module names may change as per the vendor or model of the Manual Call Point.

As per UAE Fire and Life Safety Code:-
🔥 The manual call points shall be used only for fire alarm initiation. In addition, all manual call points within an occupancy shall be of similar design.
🔥 Distribution of the manual call points should be such that the travel distance should not be more than 61m to reach the nearest manual call point.
🔥 These figures are to be reduced to 25m and 16m in limited mobility areas and where processes of the area result in a likelihood of rapid-fire development.
🔥 A Manual Call Point shall be installed within 1.5 m from the exit door opening.
🔥 The manual call points shall be installed generally at the height of 1.2 m, above floor level, and in plain, accessible, well-lit, and free-hindrances places.

👉 To allow occupants to manually initiate a fire alarm signal
Understanding correct terminology helps prevent miscommunication during design, approval, installation, and inspections, especially on international projects.

If you would like to discuss further with us on MCPs and FDAS, don’t hesitate to get in touch with one of our technical experts.

Tuesday, May 11, 2021

Heat Detector Testing

 Heat Detector Testing

Heat detector can be defined as an element or device that detects changes in heat or fire. If any heat (change in heat that exceeds the limits of heat sensor ratings) is sensed by the heat sensor, the heat sensor generates a signal for alerting or activating a security or protection system to extinguish or avoid the fire accidents. There are different types of heat sensors, which are classified based on different criteria such as the amount of heat withstanding capacity, nature of heat sensing capacity, and so on. Furthermore, the heat sensors are classified into different types that include analog heat sensors and digital heat sensors.

Heat detector can sense the heat (change in heat according to the features of heat detector used). But, a circuit is to be designed for activating an alarm system to indicate fire or heat change and for alerting the security or protection system. Heat detector circuit can be designed using heat sensor.

These heat detectors are mainly classified into two types based on their operation and they are “rate of rise heat detectors” and “fixed temperature heat detectors”.

Before starting the job, take the proper work permit and inform to all the respective departments. Then do force the respective logics or interlocks if any (like fire suppression systems activation etc).

§  Prior to testing of Heat detector see the LED status of the Heat Detector it should be blinking red.

§  Check the voltage of the Heat Detector, it should be + 30 Volts DC. This can be checked by the addressable base of the detector. (Digital type detector).

§  Now Heat Detector is healthy and it is ready for testing.

§  Clean the Heat Detector’s dust by cotton cloth and blower

§  Apply the heat to the Heat Detector by solo heat-detecting gun.

§  Keep applying heat for 10 seconds.

§  After 10 seconds LED status of the Heat detector is changing from steady blinking red to steady red and after that alarm appears and the hooter is activated on the fire alarm panel.

§  To silence the hooter press the acknowledge key to the Fire Alarm Panel.

§  After the alarm appears remove the heat-detecting test gun from Heat Detector.

§  Note down the alarm tag and descriptions from the HMI or Graphic workstation. The alarm details must match with the heat detector tag number and installed location.

§  Confirm the heat detector activation status from the respective graphics page. You have to visually identify the colour change signals of the respective heat detector on the graphics.

§  Reset the alarm of the Heat detector from the Fire Alarm Panel.

§  The LED status is changing from steady red to blinking red.

§  Heat Detector is now working normally.

§  Repeat the above procedure for all the remaining Heat Detectors.

§  Normalize the forced interlocks or logics if any.

§  Close the work permit.

Note: The mentioned voltages, terminals, circuit module names may change as per the vendor or model of the Heat Detector. Available in both 110 / 120 and 220 / 240 volt versions the Solo 423 and 424 are the professionals’ choice where cables and leads are acceptable. Unconstrained by energy availability they provide the quickest of test times and are, perhaps, most suitable for the highest temperature detectors.


Monday, June 1, 2020

Guidelines for building when reopen post COVID-19 lockdown fire & life safety aspect

Guidelines for building when reopen post COVID-19 lockdown fire & life safety aspect

To prevent the spread of the coronavirus (Covid-19) disease among building workers and office staff when commercial activities resume in various states of India, the states, district administration and the labour department already issued a detailed advisory for business units reopening while the lockdown is still in place. The labour department said that since the city has a unique mix of industrial and office workforce, owing to closeness with other national Capital region cities, it has been decided to apply more stringent measures in a few domains to prevent the spread of this disease.
Additional labour commissioner of NCR, Haryana. “All organisations are expected to align their operations to these guidelines to ensure safe working conditions. In case the companies don’t comply with the standard operating procedures (SOP), their permissions will be withdrawn and criminal proceedings would be initiated against them,” he said.

What is COVID-19
COVID-19 is a disease caused by a new strain of coronavirus. ‘CO’ stands for corona, ‘VI’ for virus, and ‘D’ for disease. Formerly, this disease was referred to as ‘2019 novel coronavirus’ or ‘2019-nCoV. The COVID-19 virus is a new virus linked to the same family of viruses as Severe Acute Respiratory Syndrome (SARS) and some types of common cold.

What are the symptoms of COVID-19?
Symptoms can include fever, cough and shortness of breath. In more severe cases, infection can cause pneumonia or breathing difficulties. More rarely, the disease can be fatal. These symptoms are similar to the flu (influenza) or the common cold, which are a lot more common than COVID-19. This is why testing is required to confirm if someone has COVID-19.

How does COVID-19 spread?
The virus is transmitted through direct contact with respiratory droplets of an infected person (generated through coughing and sneezing). Individuals can also be infected from and touching surfaces contaminated with the virus and touching their face (e.g., eyes, nose, mouth). The COVID-19 virus may survive on surfaces for several hours, but simple disinfectants can kill it.
The outbreak of coronavirus disease (COVID-19) has been declared a Public Health Emergency of International Concern (PHEIC) and the virus has now spread to many countries and territories.

The Ministry of Home Affairs has issued new guidelines for the restarting of building operation post coronavirus lockdown. As per the new guidelines, the production units have been asked to consider first week after the lockdown ends as a trial period. The new guidelines address the issues from accommodation to sanitization needs. It also asks the companies to not target high production in the first week of operations. "When Lockout/Tagout procedures are not in place, many energy sources can prove to be hazardous to operators/supervisors who are servicing or maintaining electrical, mechanical or chemical equipment. When heavy machinery and equipment are not maintained periodically, they can become dangerous for the operators/engineers," NDMA said in a statement. 

Building owners and facility managers will be getting ready to reintroduce occupants to structures that may have been relatively vacant for an extended period. During this unique time, maintenance of all fire protection and life safety systems in commercial and multi-occupancy residential build­ings. However, it is possible that many of the ongoing inspection, testing, and maintenance (ITM) activities required by locally enforced codes and standards may not have been completed for a variety of reasons. Regardless of the level of ITM performed during this time, it is imperative that building owners and facility managers verify the performance of all building fire protection and life safety systems prior to reoccupation. Now we learn below factors that should be confirmed by a qualified person before re-open­ing a building to ensure safety of all its occupants.

Based on the assumption that the building was in compliance prior to being closed, the checklist below provides some initial steps to help ensure that the occupancy is safe enough to reopen until a qualified professional can complete the regularly scheduled ITM of all fire protection and life safety systems.
Fire and life safety checklist
Confirm all the following checkpoints for each of the building systems. While this is not a complete list, it does contain many of the items that can be addressed and confirmed by a building owner or facility manager during their initial work to reopen a building. We get help from IS, NBC 2016 & NFPA standard.

General
1.    All inspection, testing, and maintenance is up to date on the following systems or building elements:
Water-based fire protection system (NFPA 25)
Fire pumps (NFPA 25 & IS 12469)
Fire alarm system (NFPA 72 & IS 2189)
Commercial cooking equipment ventilation and fire protection (NFPA 96)
Portable fire extinguishers (NFPA 10)
Fire/smoke dampers (NFPA 80 and NFPA 105)
All fire doors (NFPA 80 and IS 3614)
Emergency lighting equipment (NFPA 101 & IS 10322)
Exit signs (NFPA 101 & IS 12349)
2.    Appropriate fire department access is unobstructed. (NFPA 1)
3.    For wildfire-prone areas, routine maintenance of combusti­ble vegetation has been completed. (NFPA 1)
4.    Hand sanitizers or alcohol-based hand rubs are stored and managed safely (NFPA 101), and if needed, learn more at https://youtu.be/1P3GjIBKwI8.
5.    Whether an undertaking from LPG piping installation agency and client stating that proposed gas bank, supply lines and other fitting associated with it is as per NBC of India -2016, Part-IV.
6.    Check with the local authority having jurisdiction (AHJ) to find out if they require any special provisions prior to reoc­cupying the building.

Fire Extinguishers (NFPA 10 & IS 2171)
Fire extinguishers are accessible and not physically damaged.
Fire extinguishers are Correctly located in the designated place. Operating instructions are clean, legible, and facing outwards.
Pressure gauge reading or indicator is in the operable range or position on all fire extinguishers.
Check weigh the extinguisher against the gross weight stamped on cylinder (this is the weight full, without hose, horn or carriage). If underweight by more than 10% of contents, the extinguisher should be removed from service and recharged.

Water-Based Systems (NFPA 25, IS 3844 and IS 13039)
All control valves are open.
Gauges are operable and not physically damaged.
Water filled piping is maintained above 40 F (4 C).
Sprinklers are not physically damaged. If any leakage will be repaired.
There are no leaks from the piping or sprinklers.
A Diesel fire pump should be required and provide diesel exhaust pipe from the diesel engine and terminate to atmosphere in a location acceptable to the local Authority.
Fire department connections are accessible and not physically damaged.
Hose connections (if provided) are accessible and not physically damaged.
An additional static water storage tank to be provided at roof / terrace level with capacity specified by the local fire authority with arrangements of replenishment by main or alternate source of supply, which can be used in the eventuality of failure of other system under gravity flow.
Visual inspection for all valves must be open, accessible and unobstructed. All the fire pumps to have direct access from the ground level.

Fire Alarm Systems (NFPA 72 & IS 2189)
There are no trouble, supervisory, or alarm signals.
Batteries and their connections should be examined and tested to ensure that they are in good serviceable condition under FACP.
Notification appliances are not blocked or physically damaged.
Fire Control panel functions should be checked and tested with all fault indicators and Loop circuits should be tested and checked.
Initiating devices (smoke detectors, heat detectors, etc.,) are not physically damaged.
Manual pull stations are accessible and not physically damaged.
A test & inspection of all integration (Like: PA, Access Control, EXIT signage, AHU) and graphic software.
A visual inspection with Cleaning should be made to check 60% Smoke Detector, MCP, Heat Detector under fire alarm system.

Electrical (NFPA 70B and NFPA 110)
Confirm that routine maintenance and operational testing is completed for the following:
Electrical equipment per the building’s Electrical Preventative Maintenance Program.
Emergency and standby power systems.

Means of Egress (NFPA 101 & NBC 2016)
All means of egress paths are unobstructed.
All doors in the means of egress are working properly and not physically damaged.
All doors are operable from egress side.
All doors are not physically blocked.
All fire doors are working properly and not physically damaged.
All fire doors latch.
All required lighting in the means of egress is functioning properly.
Means of egress is illuminated when occupied.
Emergency lighting is not blocked or physically damaged.
Exit signs are not blocked or physically damaged.
Exit signs are properly illuminated.


Ref:
https://www.who.int/medicines/areas/quality_safety/quality_assurance/supplement_4.pdf?ua=1