Saturday, January 1, 2022

How Fire Panel Know my Detectors are OK?

How Fire Panel Know my Detectors are OK?

Wishing you a very Happy New Year 2022.

The exact design of a commercial fire alarm system is determined by the commercial space’s occupancy classification and the local codes mandated by the Authority Having Jurisdiction (AHJ) for that specific occupancy classification. But regardless of the system design, all commercial fire alarm systems must have a Fire Alarm Control Panel (FACP).

An FACP is the “brain” of the fire alarm system to which all other devices are connected. When an initiating device (such as a smoke detector or a manual pull station) transmits an alarm signal to the FACP, it activates the notification devices to alert the occupants via audible and visual alarm devices.

An FACP also has a digital display that provides the current status of the fire alarm system. In modern “addressable” fire alarm systems, every device connected to the FACP has a unique address (for example: “57 - smoke detector basement electrical room”) which allows the FACP to display the specific device that initiated the signal. This level of detail allows the authorized personnel to quickly locate the source of the alarm. The building’s authorized personnel also use the FACP’s functional switches to acknowledge signals, silence alarms and reset the system once the alarm condition has been cleared by fire department personnel.

It's assumed that fire alarm systems have to work all the time because fires happen anytime... but, then again, this is the real world. Problems with the fire alarm system do occur, and that's when it may not go into alarm. To know when it needs to be fixed, the whole fire alarm system needs to be supervised. 

Smoke detectors look for the presence of smoke. The most common type used today are photoelectric smoke detectors. A photoelectric smoke detector operates by projecting a small beam of light across an internal chamber. If that beam of light becomes obscured beyond a preset threshold (a percentage of light obscuration) by smoke, dirt or other small particles, the detector will transmit an alarm signal to the

If there's trouble inside the fire alarm panel, the panel does its self-diagnostics and indicates trouble. However, when there's a problem in the wiring or devices outside the panel, that's another story. 

Addressable Supervision is the Fire Alarm Control Panel polling or asking a device "Are You OK?", and the device answers "I'm OK!"

Polling is an I'm OK Check

Conventional Class A and Class B wiring directly supervises only the wires; it does not really supervise the devices. The Signaling Line Circuit (SLC), on the other hand, is different; it supervises the devices. 

Unlike the conventional methods, the SLC is a kind of two way street. To supervise, the SLC uses Polling of the Devices. Polling is similar to an I'm OK survey of the entire fire alarm system outside the panel. 

To Poll the devices, the panel uses a signal to say 'device 27 report', and device 27 reports back with a signal that says essentially, 'I'm OK.' If device 27 doesn't report back, or if it does report back but says it isn't working correctly, the message on the fire alarm panel indicates trouble on device 27. 

Failure of the device to report back could be trouble with the device, or trouble with the wiring. However, because the panel specifies the device in trouble, the troubleshooting process of the fire alarm system is sped up. 

Supervising the Wire

With conventional Class A or Class B wiring methods, in order to directly supervise the wire, a current is passed through the entire wire loop. 

The devices connected to the loop aren't supervised; the panel never checks the devices to see if they work. Unless a detector in the field opens the loop, or a horn or strobe shorts (almost never happens), the fire alarm panel won't indicate trouble. 

On the other hand, with the exception of Styles 6 and 7 (equivalent to the conventional Class A), the wires in an addressable loop aren't directly supervised. 

Instead of passing a current through the wire, the SLC wiring is indirectly supervised. If, during the polling process, the returning I'm OK signal is received at the panel, the panel assumes that the wiring is complete. That's the indirect supervision of the wire in the loop. 

Alarm Signals -- Input and Output Device

For input devices, of course, if smoke detector 27 goes into alarm, the panel gets the signal from device 27, and using words on the display, identifies smoke detector 27 as the source of the alarm.

Then again, to turn on the horns or strobes is a specific area, the panel can also send signals along the same SLC to the specific output modules it needs to turn on. 

Addressable I'm OK Supervision -- It's All About Confidence

Using the "I'm OK" signals of the polling process, the addressable fire alarm system directly supervises the devices on the SLC. With this direct supervision of the devices, the fire alarm system has confidence the building wiring is intact.

According to NFPA 72, fire alarm initiating devices are defined as devices used to manually or automatically signal a fire alarm system to initiate responses from equipment and people. These devices connect to the alarm system’s control panel and are under the control panel’s surveillance. When triggered, the control panel identifies the location and then goes into the alarm stage, sounding alerts throughout the building and sending commands to emergency responders.

SSA Integrate offers NFPA inspection programs to our customers. Regular fire equipment inspections will ensure the ongoing reliability and safety of your fire protection systems. As part of the fire protection inspection process, detailed reports will be provided identifying any system deficiencies and recommended action to bring the system back up to applicable fire codes.
We provide a comprehensive selection of fire protection inspection services through our Preventive Maintenance Agreement (PMA). Your company can save valuable time and money by having your fire safety needs addressed with one PMA.


Friday, October 15, 2021

ISOLATOR INSTALLATION, INSPECTION, AND SERVICE!

ISOLATOR INSTALLATION, INSPECTION AND SERVICE

Isolator module is used on the intelligent fire alarm control panels to protect the system against wire-to-wire short circuits on the analogue addressable loop wiring. Fire Projects designer know how and where to use this isolators to get optimum performance. Some of OEM told short-circuit isolator module which is designed to electrically separate and protect vulnerable parts of the bus.

SOME DO’s AND DON’T’s

In the last twenty (or so) years, I’ve been privileged to have been able to watch the tremendous advances in technology that continues to inspire several manufacturers around the world to explore new developments in electronic life safety systems.   Unfortunately, each new advance exposes some vulnerability that must also be addressed. 

In this article, we’re going to discuss “isolators” and more specifically, the correct wiring methods for the various types of circuits you’re going to encounter, as well as the testing that must be performed, both at the system’s commissioning/Verification and on an annual basis.  We’re going to focus on the changes currently adopted by the Canadian Standard for Installation of Fire Alarm Systems (CAN/ULC-S524) as well as what’s “in the pipe” in the way of amendments.

ISOLATOR TYPES AND TERMINOLOGY

What is an isolator, and how does it work?  Let’s begin by actually answering these two questions.  An isolator is a device that is designed to limit the extent a circuit is compromised by a single “short” fault.  In North America, there are four distinct “families” of short circuit isolators.  They are:

  • Data Communication Loop (DCL) Isolators – some manufacturers call them Signal Line Circuit (SLC) Isolators
  • Power Buss Isolators
  • Audio Buss Isolators
  • Suite Signal Isolators

Most isolators are “dumb” devices comprising a simple relay in a short sensing circuit on their “out” terminals.  As long as there is resistance on the circuit, they’re “happy”.  When the resistance drops to nothing (a short), they activate to preserve the loop integrity on their “in” side.  Some manufacturers have chosen to make their isolators “smart” by employing their panel’s protocols to “communicate” with each isolator.  This has the advantage of being able to “group bypass” an entire floor area from the common control if work is being performed there, without affecting the operational status of the rest of the system.  You’ll usually find these isolators employed by companies that are engaged in providing large scale networked type fire alarm systems (for the obvious reason that it also makes testing easier).

APPLICABLE CODES AND STANDARDS

NBC 2015, VBBL 2019

The only time isolators are actually mentioned in any Canadian Building Code is in conjunction with in-suite signalling means.  This is articulated in BCBC 2018 (as adopted from NBC 2015) in Section 3.2.4.19 called Audibility of Alarm Signals and reads in sentence (8):

“Audible signal devices within a dwelling unit or a suite of residential or care occupancy shall be connected to the fire alarm system:

a) in a manner such that a single open circuit at one device will not impair the operation of other audible signal devices on that same circuit that serve the other dwelling units or suites of residential or care occupancy, or

b) on separate signal circuits that are not connected to the devices in any other dwelling unit, public corridor or suite of residential or care occupancy. (See Appendix A.)”

CAN/ULC-S524-14

The Canadian Standard for Fire Alarm Installation is where we will find reference to the installation of Data Communication Link (DCL), network data, audio buss, and power buss fault isolators.  We will be using the abbreviations “DCL” “ND”, “AB” and “PB” for the purposes of this article.  It also deals with some specific installation requirements governing the use of insuite signalling isolators.

We’ve provided links to diagrams at the bottom of this page which detail both Class “A” interconnected field devices and a Class “A” Riser interconnected to field devices in a Class “B” configuration as part of this article.  This is one area where the manufacturer’s installation instructions also fall short and may even reference practices only acceptable outside of Canada (i.e. NFPA requirements).  The essential difference between the drawings you’ll see in the official amendment to the Standard and ours centres around one additional isolator which we’re suggesting be added to the “return” side of the loop to protect this part of the riser if you are employing uni-directional isolators.  In this instance, I’m of the opinion that this qualifies as an improvement on the actual requirements of the Standard (something that’s referred to as “good engineering practice”).

There are currently two versions of CAN/ULC-S524-14.  One includes the Amendments published in January of 2016 as a separate insert while the other will not have an amendment.  Please ensure your Standard includes the statement:  “Including Amendment 1” on the cover.

So, let’s begin with Clause 5.7.3:

“Where a data communication link utilizing active field devices or supporting field devices serves more than one National Building Code of Canada required fire alarm zone, a fault within one National Building Code of Canada Required fire alarm zone shall not prevent the normal operation of other input or output field devices in another National Building Code of Canada required fire alarm zone, except as noted in Clause 5.7.3.4.

Note:  See also Clause 4.3.1.8 and 4.3.1.9.”

5.7.3.4 states:

“Active field devices or supporting field devices serving water flow devices, supervisory devices on sprinkler systems, or duct type smoke detectors on HVAC systems that are located within a National Building Code of Canada required fire alarm zone but serve other National Building Code of Canada required fire alarm zones, need not be separately fault isolated from each other or the National Buiilding Code of Canada required fire alarm zone.”

5.7.3.5 states:

“A control unit or transponder or its associated data communication link that serves more than one floor area, shall be subject to the constraints of Clause 5.7.3.1.”

5.7.3.6 states:

“Data communication link style A with fault isolation modules, or data communication link style C with fault isolation modules, or an equivalent method shall be utilized to meet the requirements of Clauses 5.7.3.1, 5.7.3.4, and 5.7.3.5.  (Refer to Figure 5).”

Inbuild Isolator Brand Like: ESSER, COOPER... etc

Base Isolator Brand Like: GST, Edwards... etc

Isolator as a Separate product Brand Like: Edwards, Notifier, Morley, GST, Apollo, Ravel... etc

Section 4.3 is entitled “ELECTRICAL SUPERVISION”.

4.3.1.8 states:

“Except as permitted by Clause 4.3.1.10 or Clause 4.3.1.11, where a power buss circuit serves more than one National Building Code of Canada required fire alarm zone, a single fault (open circuit fault, short circuit fault or ground fault) shall not prevent the normal operation of input or output field devices in more than one National Building Code of Canada required fire alarm zone.

NOTE:  Refer to Appendix A (Informative) Explanatory Materials, Clause A4.3.1.8.”

4.3.1.9 states:

“Except as permitted in Clause 4.3.1.10, where an audio buss serves more than one National Building Code of Canada required fire alarm zone, a single fault (open circuit fault, short circuit fault, or ground fault) shall not prevent teh normal operation of input or output field devices in more than one National Building Code of Canada required fire alarm zone.”

4.3.1.11 states:

“Where a power buss serves supporting field devices which are located within a common National Building Code of Canada required fire alarm zone but serve other National Building Code of Canada required fire alarm zones, the power buss segment serving these supporting devices is not required to comply with Clause 4.3.1.8.”

4.3.1.12 states:

“Class A circuit with fault isolators installed in accordance with Subsection 10.2, Fault Isolators, or an equivalent method, shall be utilized to meet the requirements of Clauses 4.3.1.9 and 4.3.1.10.

NOTE:  For Data Communication Links, refer to Subsection 5.7.3, Field Device Data Communication Link.”

Section 10.2 is entitled “FAULT ISOLATORS”

10.2.1.1 states:

“This Subsection applies to the installation of fault isolation modules as required by Subsection 5.7.3, Field Device Data Communication Link, for data communication links between field devices.  (Refer to Figures 33.1, 33.2, 33.3, and 33.4.)

Note:  Where available, data fault isolators should be located in a fire separated electrical room.”

10.2.1.2 states:

“Data fault isolators shall be utilized when entering and leaving each National Building Code of Canada required fire alarm zone.   See also Appendix A (Informative) Explanatory Materials, Clause A4.3.1.8.”

10.2.1.3 states:

“Data fault isolators required by Clause 10.2.1.2 are not required between field devices located within the same floor area that are monitoring mechanical equipment serving other floor areas.

NOTE:  For example, water flow devices on sprinkler systems or duct type smoke detectors on HVAC systems serving other floor areas are considered part of the same area specified in Clause 10.2.1.2 and need not be separately fault isolated from other devices within that area.”

10.2.1.4 states:

“Except as noted in Clause 10j.2.1.5, data fault isolators, shall be located in a separate enclosure and installed so as to be visible and accessible at all times.”

10.2.1.5 states:

“Data fault isolators that are integral to a field device shall be mounted in accordance with the requirements of that field device.”

Note:  Field devices incorporating fault isolation modules complying with Clause 10.2.1.2 do not require additional dedicated data fault isolators.”

10.2.1.6 states:

“Where a fire separation is provided, data fault isolators required by Clause 10.2.1.2 shall be installed on each side of that fire separation.”

10.2.1.7 states:

“Data fault isolators installed on opposite sides of the same fire separation shall be offset horizontally to a minimum of 400 mm, and not located within the same stud space.”

10.2.1.8 states:

“Where no fire separation is provided between each National Building Code of Canada required fire alarm zone, a single fault isolation module shall be utilized when isolating zones within the same floor area.

Note:  This Clause would be applicable to large horizontal buildings, e.g., warehouses, shopping malls, factories, etc.”

10.2.1.9 states:

“Data fault isolators serving a single field device in an exit or vertical service space shall be installed on the floor area side.

Note:  Fault isolation modules are not required on the exit or vertical service space side.  See Figure 2.4”

10.2.1.10 states:

“Data fault isolators shall have an identifying mark or label on the cover plate or field device.  The identifier shall be visible after installation.  Where field devices incorporating fault isolation modules are used to comply with Clause 10.2.1.2, the first field device entering and the last field device leaving each National Building Code of Canada required fire alarm zone shall be marked.”

 

Tuesday, June 1, 2021

T-Tapping in Fire Loop Line

 T-Tapping in Fire Loop Line

A fire alarm “T-Tap” is merely a parallel tap into the loop. The reason T-Tap wiring is allowed is because communications are being supervised to the device level. T-Tapping the different legs of the SLC provide multiple communications paths of the field devices and control equipment.
The answer to the question of how many T-Taps is allowed --- is "It Depends". It depends on the manufacturer and it depends on how easy the installer wants to make the system for the technician when servicing the system for the coming years. On a conventional system “T-Tap” not working.

Style 4 wiring (somewhat similar to Class B wiring), which is the data-loop or signaling line circuit (SLC), allows an unlimited number of T-Taps, at least for most manufacturers. Signaling Line Circuit (SLC), carries signals in the form of data between the panel and the input and output devices. Canada calls "Class B Level 1" "Data Communications Link (DCL) Style B". Someone called Initiating Device Circuit (IDC), its carries signals from the input devices to the panel.

Field Devices Connected to an SLC/DCL/IDC.

Input

·        Smoke Detectors

·        Heat Detectors

·        Combination Smoke/Heat Detectors

·        Pull Stations

·        Alarm and Supervisory Input Modules

Output

·        Control Relays

·        NAC Riser Modules

o   24 VDC Audible

o   24 VDC Visible

o   24 VDC Combination Audible/Visible

o   Audio for Speakers (Direct Current (DC) blocking capacitor allows 70.7 VAC 200-20KHz through) independent of other audio.

o   Firefighter’s Phone

Every device on a Signaling Line Circuit is a T-Tap for the Panel.

 
Long Star-Taps

Most fire alarm systems that use Style 4 wiring for the SLC are electronically connecting every device directly to the terminals of the fire alarm panel. Being wire nutted at all junctions, electrically the wire loop is a single pair of copper conductors. 

For all practical purposes, all devices on the loop are connected directly to the panel, and the panel can't tell the difference between home runs to each device and a single daisy chain. 

Yes, the installed wiring may daisy chain to 75 devices in a straight line, but electrically, every last one of them is connected directly to the terminals of the fire alarm panel. 

For these types of systems, the wires can be thought of as having a long star-tap. 

Later Servicing the System

The real concern with the T-Taps is with the later servicing of the system. When trying to find a ground fault or bad device. A limited number of T-Taps makes it easy to divide up the system. 
Not enough T-Taps and the technician has to guess where the wires run through the building. Too many T-Taps and the technician has to pull a lot of T-Taps apart to get an idea of where to find the faulty device or wiring. 

Manufacturer's T-Tap Limit

The manufacturers that limit the number of T-Taps have an input side and an output side to each device on the SLC. Here the panel itself is creating a map of the SLC wiring system. If there are too many t-taps, or if the ins and outs of the devices are not wired according to the installation sheets, the panel's created maps become useless for later servicing. 

How Many T-Taps

When trying to determine how many T-Taps are allowed, consult the manufacturer' installation sheets, and then decide on how easy the servicing of the system should be in the coming years.

If you still aren't sure how you manage your building / establishment loop line, feel free to get in touch with one of our experts via ssaintegrate@gmail.com. Before selecting vendor / installer check and verify they are authorized or not to execute your Fire Detection & Alarm system work. Its mandatory Fire Detection & Alarm System (Edwards, ESSER, Notifier, Autronica, Cooper, BOSCH & GST etc) commissioned by certified professional.


Monday, February 1, 2021

Circuits and Pathways in NFPA 72

 Circuits and Pathways in NFPA 72

In Greece, over 2500 years ago, near the small town of Marathon, there was a battle. After the battle, one of the winning Athenians ran all the way from Marathon to Athens carrying the news.

He ran along a path.

Nowadays, the message could be carried by a person running along a narrow mountain road, a verbal telephone call, a news story over the microwave towers, a data signal carried over fiber optics, Etc.; so may choices.
The NFPA would consider all of these to be communication paths. The paths are no longer just copper wires, but wireless radio waves are also used, Ethernet data cables are also used, and fiber optic cables are also used in fire alarm systems.

Because of all the different types of communication paths for fire alarm systems being used nowadays, the NFPA is addressing them all differently than they did in the past.

Beginning with the 2010 edition of NFPA 72, National Fire Alarm and Signalling Code, all of the “styles” of circuits were deleted, and four “classes” were added. A new chapter, Circuits and Pathways, was added during the reorganization of this code. In the past, the styles only described the operation during an alarm or fault condition for initiating device circuits, notification appliance circuits and signalling line circuits. NFPA 72, National Fire Alarm and Signalling Code, defines the performance of fire alarm circuit and pathways in Chapter 12. While the terms “circuit” and “pathway” are often used interchangeably, they are different. The styles of initiating device circuits (IDC), notification appliance circuits (NAC) and signalling line circuits (SLC) were eliminated, and four new classes were added. The intent was to add information about all circuits and pathways, not just IDCs, NACs and SLCs. A circuit is defined in Chapter 3 as “either means of providing power or a connection path between locations”, while a pathway is “any circuit, conductor, optic fiber, radio carrier or other means connecting two or more location.” Basically, a circuit is copper, while a pathway can be copper or any other type of connection.

There are three things considered by the NFPA with the carrying of the signals on the fire alarm system paths:

1.    Supervision - The method of self-checking for faults - the end-of-line resistor continuity check and handshaking using data signals are two common methods

2.    Redundancy - the continued operation of the whole fire alarm system, or a second path to carry signals around a problem is redundancy - an open wire or wire-to-wire short are some of the problems addressed with redundancy

3.    Protection from damage - conduit is one common method used to protect the path

Pathway performance is defined in Section 12.3, using Class A, B, C, D, E, N, or X based on the circuit performance. NFPA 72 does not determine what class is used on a particular pathway, but rather defines the performance of the pathway. The specification, designer, AHJ determine what class of pathway is used. NFPA 72, Chapter 24, “Emergency Communications Systems,” Section 24.3.14 is the only place I have found any requirements for survivability. Survivability for fire alarm pathways is typically only required for systems employing partial evacuation or relocation. Since building and fire codes require systems to be installed in accordance with NFPA 72, they do not have specific provisions for survivability. The Chapter 24 technical committee is proposing important changes to the 2022 edition of the code.

A pathway classification describes more than that. When describing a Class, the NFPA is concerned with is Reliability, Fixability, and Survivability.

Reliability - The NFPA wants to make sure the fire alarm system continues to work in the long run.

Fixability - The NFPA wants to make sure any problems that do occur are found and fixed on a timely basis.

Survivability - The NFPA wants to make sure the fire alarm system will continue to work when fixing it on a timely basis isn't good enough.

In a fire alarm system, there are (at the moment) seven Classes of communication and power infrastructure (paths):

  • Class A
  • Class B
  • Class C
  • Class D
  • Class E
  • Class N
  • Class X

The letters after the word Class are not shown in the order of reliability or importance; the letters after the word Class are only the name of the particular classification.

Chapter 12 describes each class. Here are some examples of each you may find useful.

 

Class A

1.    This will include a redundant signal path - If the path is interrupted, the system feeds both ends of the paths so there are now two paths; the original outgoing path which is now cut shorter, and the return path which is now being used as an outgoing path

2.    If wires are used, a wire-to-wire short may shut down the whole path

3.    Both conventional and addressable systems fit into this

4.    Both the IDC (Initiating Device Circuit) and the NAC (Notification Appliance Circuit) fit into this

5.    The panel shows a trouble signal when there is a problem

Class B

1.    There is no redundant path

2.    Any device beyond a break won't work

3.    If wires are used, a wire-to-wire short may shut down the whole path

4.    Both conventional addressable systems fit into this

5.    Both IDC and NAC fit into this

6.    The panel shows a trouble signal when there is a problem

Class C

1.    Uses Handshaking (equivalent to an I'm OK signal) to supervise the path

2.    Can have more than one pathway

3.    The panel shows a trouble signal when there is a problem 

 Examples:

1.    Signals from the fire panel to the monitoring company

2.    The use of IP (Internet Protocol), whether it's local communications or over the Internet

3.    The communicators over the telephone lines that are still in use

 

Class D

1.    Fail-Safe operation - If there is a failure, the device that is controlled by the fire alarm system goes into fire mode

2.    No trouble shows on the panel

Prior to the 2010 edition of NFPA 72, Class D pathways simply referred to as “fail-safe.” A typical application for a Class D pathway is a powered relay used for door release or fan control. Since the relay is powered in normal condition, operation of the relay is accomplished by removing power by control panel operation, or by a failure of the circuit.

 Example of a device going into fire mode when a wire breaks or a signal is lost:

1.    The fire door closes

2.    Emergency door locks release

3.    The damper closes

4.    The fans shut down

 

Class E

Class E pathways are not monitored for integrity and are used in applications where supervision is not required. Section 12.6 of NFPA 72 defines applications where monitoring for integrity is not required. Some examples include interconnection between equipment in an enclosure, interconnection between control equipment within 20 feet of each other where conductors are protected by conduit, and interconnection wiring of a stationary computer to its keyboard, monitor, or mouse where the wiring does not exceed 8 feet.

Class N

This is basically local Ethernet, Token Ring, or other network or IP infrastructure.

1.    Unless a single device is connected, or the path is short (less than 20 feet) and really protected in something like conduit, two pathways are used

2.    These pathways are verified through end to end communication, like data handshaking

3.    Loss of communication between end points on any path show a trouble signal on the panel

4.    Problems with one pathway won't affect the other pathway

Class X

1.    This will include a redundant signal path. Like Class A, if the path is interrupted, the system feeds both ends of the circuit so there are two circuits, the original outgoing path which is now cut shorter, and the return path which is now being used as an outgoing path

2.    Devices on both sides of an open will continue to communicate with the panel

3.    If wires are used, devices on both sides of a wire-to-wire short will continue to communicate with the panel (basically the short has to be isolated on both sides of the short)

4.    The panel shows a trouble signal when there is a problem

In order to be proper classified as Class A or Class X, the outgoing and return path routes for both Class A and Class X have to be separated by a certain distance; the two paths cannot be inside the same conduit, for instance.

Many designers and contractors do not include survivable cable or fire-rated enclosures in their designs for in-building fire emergency voice/alarm communications systems (EVACS) wiring as required in the code—or at least not until the authority having jurisdiction enforces the requirement because a designer missed it the first time around. This may be due in part to some confusion over where survivability is required in the first place. Pathway survivability is not required for all EVACS; it is only required where occupants will remain in the building during an emergency (i.e., relocation or partial evacuation). The intent is to ensure that we can still get subsequent instructions to those occupants if the situation worsens. For those systems where pathway survivability is required, it does not necessarily need to be applied throughout the entire system; it must be applied only where the circuit runs through multiple notification zones, so that a fire in one notification zone doesn’t impair the ability to communicate with occupants in another. Additionally, the current edition of NFPA 72 permits the installer to use Level 1, Level 2, or Level 3, meaning that a sprinklered building (i.e., Level 1 pathway survivability) does not require the use of fire-resistant cabling or an enclosure. No wonder a contractor or installer might not include fire-resistive cable in an initial design.


The reason behind survivability requirements is to maintain the operational reliability of the EVACS during a fire. Pathway survivability for emergency communications systems (including EVACS) is covered in 24.3.14; Section 12.4.5 includes the definition of Level 4 pathway survivability.
The previous requirements for survivability said only that the cable had to be two-hour-rated or installed in a two-hour-rated enclosure. The technical committee changed the requirement so that it is now related to the fire resistance rating of the building construction. This relationship is important because the listing of two-hour fire-rated cable is required to be attached to a concrete wall or floor assembly, constructed with a minimum of two-hour rating or as otherwise identified by the UL FHIT systems assembly.

Additionally, as stated in the Annex A of the code, “installing a pathway survivability Level 2 or Level 3 in a building that is constructed with less than two-hour construction would not be installed within the listing of the product.”

For building construction with a fire-resistance rating of one hour, but less than two hours, the technical committee has proposed a new Level 4 pathway survivability.

With the more common use of timber construction for larger buildings, the expectation is these buildings would be classified as one-hour fire rated. Two-hour cable, as it is presently listed, would not be allowed when using the proposed Level 4 wiring or with wiring that meets the proposed separation requirements. That prohibition is due to the concern that a fire causing an open, ground-fault, or short-circuit fault on the communication and control circuits between rooms or enclosures could affect the operation of the in-building fire emergency voice/alarm control equipment within these rooms or enclosures.

It is well known that the insulation on fire alarm cabling can melt when exposed to heat and flames, causing the conductors to short circuit. When this condition occurs, it is possible for an entire signaling line circuit to fail, seriously impacting communication and control circuits. To help guard against these kinds of catastrophic failures, the proposed code would require the use of fault circuit isolators to ensure that the entire circuit is not disabled during a fire.
These proposed changes to the 2022 code would provide guidance in Annex A to assist designers, contractors, and AHJs in the proper separation of circuits as well as the location of fault circuit isolators to ensure both compliance with the code and a high degree of operational reliability. It is important to remember that for fire alarm systems designed for relocation and partial evacuation, communication must remain operational on all floors other than the fire floor during a fire. The primary fire protection goal is reliable communication during the fire.