Showing posts with label Pull Station. Show all posts
Showing posts with label Pull Station. Show all posts

Saturday, October 1, 2022

Pull Stations is a First Line of Defence

 Pull Stations is a First Line of Defence

Today, at least one fire alarm pull station is required for all public buildings, including, schools, hospitals, prison, daycares, hotels, businesses, and apartments regardless of the automated fire alarm systems and detection devices used. At JMAC, you can find all sorts of single and dual pull stations, including addressable pull stations. Quality pull switches usually have some sort of approval or listing, and feature a corrosion-resistant material along with a handle that can only be reset by an authorized person. A fire alarm pull station is normally the first line of defense to an alarm security system and will do a fantastic job of alerting authorities and bystanders regarding danger within your premises.

A working fire alarm pull station supports prompt evacuation and swift action from first responders

When somebody “pulls the fire alarm,” they’re usually talking about fire alarm pull stations. For more than 50 years, some form of these typically red boxes have been found on the walls of most large buildings in the United States.

In this article, we’ll cover how pull stations work, why they’re important, and what to look for when purchasing one.

How does a fire alarm pull station work?

Sometimes referred to as “pull switches,” fire alarm pull stations—often featuring a T-bar handle, as shown below—activate fire alarm systems.

Pull stations with a T-bar handle are easily recognized and activate with a single downward motion.

These systems can also be activated by other initiating devices, such as automatic heat and smoke detectors, but what follows is the same: indicating appliances, such as horns or strobe lights, direct occupants to leave the area. Pull stations send a signal to the control panel, and if the fire alarm is monitored, the control panel then usually sends a message to a company’s monitoring service, which transmits that message to first responders. In some cases, a signal is transmitted directly to a fire department.

The status of pull switches and other essential components are displayed on fire alarm control panels like this one.

It’s a less commonly-known fact that most pull stations don’t cause fire sprinklers to spray water. Many fire alarm systems may monitor fire sprinkler systems – and sound the alarm when sprinklers discharge – but their purpose is to alert bystanders and authorities to danger.

Pull stations are redundant—and that’s (part of) the point

The National Fire Protection Association (NFPA) authors guidelines used by state and local governments to write fire code. At the core of NFPA’s philosophy is redundancy – the effort to guarantee that when one life safety system fails, another takes its place.

From the 2018 edition of NFPA 101

4.5.1 Multiple Safeguards. The design of every building or structure intended for human occupancy shall be such that reliance for safety to life does not depend solely on any single safeguard. An additional safeguard(s) shall be provided for life safety in case any single safeguard is rendered ineffective.

Attacking the problem of fire safety from multiple angles makes buildings much safer. Safety features – from fire extinguishers to fire escapes – are redundant in the best possible sense of the word.

Working, fail-safe fire prevention systems have become more widespread as the frequency of fires has declined. But today’s fires, while drastically fewer in number, remain just as deadly and devastating when they occur, making these fail-safes as critical as ever.

Thomas Peele, a journalist with The Mercury News, reported on a 2018 fire in San Jose, California that injured 15 people and displaced more than 100. Peele learned that an untested and uncertified fire alarm system failed to activate when fire broke out in a second-story unit at Summerwind Apartments. Fire inspector Andrew Whyte uncovered several additional fire safety violations, including problems with exit signs, emergency lights, and other fire prevention equipment. An inspection in 2011 had found “that the alarm at Summerwind was not certified as working,” but the issue was never remedied.

Pull stations, required in nearly every building, must be nearby

Every fire alarm system can be activated in one of several ways, but according to NFPA guidelines, manual fire alarm initiation is a requirement common to almost every building requiring a fire alarm system. Automatic detection can be used in place of manual activation only when explicitly allowed.

As a general rule, all kinds of public buildings – theaters, schools, daycares, hospitals, prisons, apartments, hotels, and businesses – need at least one alarm pull switch, even when automatic detection devices are connected to the alarm system. NFPA 101: Life Safety Code, available for free at NFPA.org, spells out these requirements.

From the 2018 edition of NFPA 101

9.6.2.6* For fire alarm systems using automatic fire detection or waterflow detection devices to initiate the fire alarm system in accordance with Chapters 11 through 43, not less than one manual fire alarm box, located as required by the authority having jurisdiction, shall be provided to initiate a fire alarm signal.

When boxes are required, they must be placed near exits and along walls at a prescribed distance.

From the 2018 edition of NFPA 101

9.6.2.3 A manual fire alarm box shall be provided as follows, unless modified by another section of this Code:

(1) For new alarm system installations, the manual fire alarm box shall be located within 60 in. (1525 mm) of exit doorways.

(2) For existing alarm system installations, the manual fire alarm box either shall be provided in the natural exit access path near each required exit or within 60 in. (1525 mm) of exit doorways.

9.6.2.5* Additional manual fire alarm boxes shall be located so that, on any given floor in any part of the building, no horizontal distance on that floor exceeding 200 ft (61 m) shall need to be traversed to reach a manual fire alarm box.

9.6.2.7* Manual fire alarm boxes shall be accessible, unobstructed, and visible.

Where multiple doors are clustered together, an alarm box is required on each side.

From the 2018 edition of NFPA 101

9.6.2.4 Manual fire alarm boxes shall be mounted on both sides of grouped openings over 40 ft (12.2 m) in width, and within 60 in. (1525 mm) of each side of the opening.

NFPA provides straightforward installation guidelines

NFPA 72: National Fire Alarm and Signalling Code establishes installation criteria for “initiating devices,” a term that covers everything from waterflow detectors to manual fire alarm boxes. First and foremost, only qualified installers should make changes to fire alarm systems.

From the 2016 edition of NFPA 72

10.5.2.1 Fire alarm systems and emergency communications systems installation personnel shall be qualified or shall be supervised by persons who are qualified in the installation, inspection, and testing of the systems.

10.5.2.2 State or local licensure regulations shall be followed to determine qualified personnel.

10.5.2.3 Personnel shall provide documentation of their qualification by one or more of the following:

(1) Registration, licensing, or certification by a state or local authority

(2) Certification by an organization acceptable to the authority having jurisdiction

(3) Manufacturer’s certification for the specific type and brand of system provided

Further guidelines ensure the visibility, accessibility, and proper function of alarm activation devices.

From the 2016 edition of NFPA 72

17.14 Manually Actuated Alarm-Initiating Devices.

17.14.1 Manually actuated alarm-initiating devices for initiating signals other than for fire alarm shall be permitted if the devices are differentiated from manual fire alarm boxes by a color other than red and labeling.

17.14.2 Combination manual fire alarm boxes and guard’s signaling stations shall be permitted.

17.14.3 Manually actuated alarm-initiating devices shall be securely mounted. 17.14.4 Manually actuated alarm-initiating devices shall be mounted on a background of contrasting color.

17.14.5 The operable part of a manually actuated alarm initiating device shall be not less than 42 in. (1.07 m) and not more than 48 in. (1.22 m) from the finished floor.

Two terms are introduced later in this section:

  • Single-action boxes require only one action to operate (i.e., a single pull on a lever)
  • Double or dual-action boxes require two actions – lift and pull.

The 2016 edition of NFPA 72 continues…………………

17.14.6 Manually actuated alarm-initiating devices shall be permitted to be single action or double action.

17.14.7* Listed protective covers shall be permitted to be installed over single- or double-action manually actuated alarm initiating devices.

17.14.8 Manual fire alarm boxes shall comply with 17.14.8.1 through 17.14.8.6.

17.14.8.1 Manual fire alarm boxes shall be used only for fire alarm initiating purposes.

17.14.8.2 Manual fire alarm boxes shall be installed so that they are conspicuous, unobstructed, and accessible.

17.14.8.3* Unless installed in an environment that precludes the use of red paint or red plastic, manual fire alarm boxes shall be red in color.

What features should I look for?

Listings are an indicator of a fire alarm pull station’s quality. A listing or approval from experts in product testing, such as UL, ensures that manufacturers have taken certain precautions against damage. A pull station meeting UL 38, the company’s Standard for Manual Signaling Boxes for Fire Alarm Systems, has been examined, tested, and confirmed to resist problems caused by impact, use, corrosion, weather, and other factors.

If the box features a metal body, it should be treated or coated with corrosion-resistant material. In most cases, a single-action pull station works, but a dual-action pull model – those that require two gestures to activate – may be best in areas where the alarm may be unintentionally activated by impact (or by a prankster). All boxes should feature a handle that cannot be reset, except by authorized personnel, when pulled.

Single-action pull stations basically made with corrosion-resistant cast-iron bodies that mount to a standard single gangbox – boxes sized for a single light switch or a pair of electrical sockets. These stations include a terminal block, allowing for wires to connect to alarms with no splicing required.

Fire is one hazard that can happen anywhere, anytime. Whether it is your home or office, effective safety equipment , is therefore, a must in all buildings, which is backed up by legislation. An attack from fire can create irreplaceable damage and loss of life. It is therefore crucial that you have systems in place to protect your assets from fire. So preparing yourself with quality safety equipment is a must. For consulting you can contact us.

Tuesday, June 1, 2021

T-Tapping in Fire Loop Line

 T-Tapping in Fire Loop Line

A fire alarm “T-Tap” is merely a parallel tap into the loop. The reason T-Tap wiring is allowed is because communications are being supervised to the device level. T-Tapping the different legs of the SLC provide multiple communications paths of the field devices and control equipment.
The answer to the question of how many T-Taps is allowed --- is "It Depends". It depends on the manufacturer and it depends on how easy the installer wants to make the system for the technician when servicing the system for the coming years. On a conventional system “T-Tap” not working.

Style 4 wiring (somewhat similar to Class B wiring), which is the data-loop or signaling line circuit (SLC), allows an unlimited number of T-Taps, at least for most manufacturers. Signaling Line Circuit (SLC), carries signals in the form of data between the panel and the input and output devices. Canada calls "Class B Level 1" "Data Communications Link (DCL) Style B". Someone called Initiating Device Circuit (IDC), its carries signals from the input devices to the panel.

Field Devices Connected to an SLC/DCL/IDC.

Input

·        Smoke Detectors

·        Heat Detectors

·        Combination Smoke/Heat Detectors

·        Pull Stations

·        Alarm and Supervisory Input Modules

Output

·        Control Relays

·        NAC Riser Modules

o   24 VDC Audible

o   24 VDC Visible

o   24 VDC Combination Audible/Visible

o   Audio for Speakers (Direct Current (DC) blocking capacitor allows 70.7 VAC 200-20KHz through) independent of other audio.

o   Firefighter’s Phone

Every device on a Signaling Line Circuit is a T-Tap for the Panel.

 
Long Star-Taps

Most fire alarm systems that use Style 4 wiring for the SLC are electronically connecting every device directly to the terminals of the fire alarm panel. Being wire nutted at all junctions, electrically the wire loop is a single pair of copper conductors. 

For all practical purposes, all devices on the loop are connected directly to the panel, and the panel can't tell the difference between home runs to each device and a single daisy chain. 

Yes, the installed wiring may daisy chain to 75 devices in a straight line, but electrically, every last one of them is connected directly to the terminals of the fire alarm panel. 

For these types of systems, the wires can be thought of as having a long star-tap. 

Later Servicing the System

The real concern with the T-Taps is with the later servicing of the system. When trying to find a ground fault or bad device. A limited number of T-Taps makes it easy to divide up the system. 
Not enough T-Taps and the technician has to guess where the wires run through the building. Too many T-Taps and the technician has to pull a lot of T-Taps apart to get an idea of where to find the faulty device or wiring. 

Manufacturer's T-Tap Limit

The manufacturers that limit the number of T-Taps have an input side and an output side to each device on the SLC. Here the panel itself is creating a map of the SLC wiring system. If there are too many t-taps, or if the ins and outs of the devices are not wired according to the installation sheets, the panel's created maps become useless for later servicing. 

How Many T-Taps

When trying to determine how many T-Taps are allowed, consult the manufacturer' installation sheets, and then decide on how easy the servicing of the system should be in the coming years.

If you still aren't sure how you manage your building / establishment loop line, feel free to get in touch with one of our experts via ssaintegrate@gmail.com. Before selecting vendor / installer check and verify they are authorized or not to execute your Fire Detection & Alarm system work. Its mandatory Fire Detection & Alarm System (Edwards, ESSER, Notifier, Autronica, Cooper, BOSCH & GST etc) commissioned by certified professional.