Wednesday, December 1, 2021

All about Internal Fire Hydrant System

All about Internal Fire Hydrant System 

We all dread unmanageable fire as it can cause destruction that is at times beyond repair. More awareness about the need to safeguarding our homes and valuable properties against any fire outbreak has encouraged people now to have fire alarm systems and other firefighting equipments at their homes or offices.

One of the necessary firefighting equipment is the fire hydrant. While it may not be seen as widely as an extinguisher, it is highly effective in dousing a full developed fire. Unfortunately, outdoor fire hydrants are fast disappearing from the Indian landscape as many civic authorities have failed to maintain and repair them on time.

So, should you invest in a fire hydrant? Yes, absolutely. In fact, you are legally obliged to do so. We are not talking about the vibrant red fire hydrants that is our usual image, but internal fire hydrants that are strictly required under the National Building Code. So, here is a short primer on fire hydrant systems India to help you along.

Nowadays, Indian manufacturers are offering such equipments of extremely good shelf life and affordable pricing. So, if you are on a hunt for firefighting equipments, then go for fire fighting equipments in India. Today, shops, educational institutions, banks, hospitals also have at least adequate number of fire extinguishers if not other comprehensive fire fighting equipments.

Need For Fire Hydrants

Fire hydrants act as a critical source of water when dealing with a developed fire. The location could be out of reach of sprinklers or it could be too developed for sprinklers or extinguishers to cope with. This is when firefighters step in. While firefighters have their own water tank, this can run dry very quickly. At such an eventuality, we need fire hydrants to boost the water supply.

Civic fire hydrants, run and managed by civic bodies, are found in public places. These are connected to the municipal water supply. Fire hydrants could be placed underground or overground. In India, the overground system is more common. Internal fire hydrants are different, placed in a building and often in-built in its construction. These hydrants are connected to the building dry and wet risers.

This is why fire hydrants are specifically mentioned in the National Building Code, which also specifies its supply mechanism, including water tanks and riser systems. High-rise buildings must, therefore, have an in-built fire hydrant system.

Parts Of Fire Hydrant Systems India

Water tanks: The fire hydrant system must have access to a water tank for a ready supply. The capacity of the tank is decided by the area and the number of risers. There are different type of tanks found on a property. These are:

1.   Static water tank: These are underground or on the surface and are built for water storage.

2.   Terrace tank: These tanks are made of plastic, concrete or cement. These are also meant for water storage.

3.   Priming tank: Unlike the other two tanks, the priming tank’s function is not water storage. This is a small tank, located above the firefighting pump. Its function is to ensure that the pumpcasing and suction is permanently flooded.

Pumps: The fire hydrants system cannot work without its pumps, which supply and regulate the water flow in the hydrant system. The various pumps here are:

1.   Fire pump: This is installed in the static tank to supply water to the wet-risers.

2.   Terrace pump: This is connected to the terrace tank. It has valves to regulate water supply from both ends. There should also be a pump panel attached to control its functioning.

3.   Jockey Pump: This pump is installed to regulate the water pressure. This is an automatic pump, which is triggered whenever there is a drop in the static pressure.

4.   Stand-by pump: As the name suggests, this is kept as an alternative in case of emergency. It has the same capacity as the fire pump.

Riser-system: These are pipes that run vertically through the building to carry the water required for the fire hydrant systems. The risers have a landing valve on each floor and at their ends to regulate the water supply. There are three types here:

1.   Wet riser: These are connected to the static water tank.

2.   Down comer: These are connected to the overhead tank.

3.   Wet-Riser-cum-Down-Comer: A combination of both types, connected to water tanks on both ends.

Hose reel: This is the tube attached to a pressurised water supply. It is the hose that ensures the water supply can be taken across a floor.

Air vessel: This is a small cylindrical vessel that is attached to the wet riser at the top and the bottom to nullify the water hammer effect.

Air release valve: This valve opens up the water supply to release the trapped air inside the riser as it is being charged.

Pressure switch: This is to regulate the functioning of the fire pump or the jockey pump as per the pressure in the system.

These are the essential parts of a fire hydrant systems. Check each part and ensure that these meet the required ISO standards before installing.

A comprehensive inspection and preventative maintenance program designed and conducted by an experienced fire protection company proactively locates fire and life safety issues and repairs these failures prior to an emergency event, ensuring all systems are operating at peak performance.

While each inspection and preventative maintenance program is different to accommodate a business’s or building’s unique needs, here is a general overview of the process:

1.   A physical inspection is conducted on each fire protection system in the facility.

2.   A detailed report is written outlining system deficiencies and recommended actions to ensure functionality and compliance.

3.   Maintenance and repairs are conducted on any fire and life safety systems that are broken or show signs of corrosion.

In terms of our fire protection inspection process, we provide building managers and business owners simple and easy-to-read inspection reports generated by intelligent Inspect Point software. Fire protection reports come with built-in NFPA forms to ensure compliance with the latest NFPA inspection requirements. Our fire and life safety inspection reports are optimized for NFPA inspection requirements including but not limited to:

·        NFPA 10

·        NFPA 13

·        NFPA 20

·        NFPA 25

·        NFPA 72

·        NFPA 80


Monday, June 1, 2020

Guidelines for building when reopen post COVID-19 lockdown fire & life safety aspect

Guidelines for building when reopen post COVID-19 lockdown fire & life safety aspect

To prevent the spread of the coronavirus (Covid-19) disease among building workers and office staff when commercial activities resume in various states of India, the states, district administration and the labour department already issued a detailed advisory for business units reopening while the lockdown is still in place. The labour department said that since the city has a unique mix of industrial and office workforce, owing to closeness with other national Capital region cities, it has been decided to apply more stringent measures in a few domains to prevent the spread of this disease.
Additional labour commissioner of NCR, Haryana. “All organisations are expected to align their operations to these guidelines to ensure safe working conditions. In case the companies don’t comply with the standard operating procedures (SOP), their permissions will be withdrawn and criminal proceedings would be initiated against them,” he said.

What is COVID-19
COVID-19 is a disease caused by a new strain of coronavirus. ‘CO’ stands for corona, ‘VI’ for virus, and ‘D’ for disease. Formerly, this disease was referred to as ‘2019 novel coronavirus’ or ‘2019-nCoV. The COVID-19 virus is a new virus linked to the same family of viruses as Severe Acute Respiratory Syndrome (SARS) and some types of common cold.

What are the symptoms of COVID-19?
Symptoms can include fever, cough and shortness of breath. In more severe cases, infection can cause pneumonia or breathing difficulties. More rarely, the disease can be fatal. These symptoms are similar to the flu (influenza) or the common cold, which are a lot more common than COVID-19. This is why testing is required to confirm if someone has COVID-19.

How does COVID-19 spread?
The virus is transmitted through direct contact with respiratory droplets of an infected person (generated through coughing and sneezing). Individuals can also be infected from and touching surfaces contaminated with the virus and touching their face (e.g., eyes, nose, mouth). The COVID-19 virus may survive on surfaces for several hours, but simple disinfectants can kill it.
The outbreak of coronavirus disease (COVID-19) has been declared a Public Health Emergency of International Concern (PHEIC) and the virus has now spread to many countries and territories.

The Ministry of Home Affairs has issued new guidelines for the restarting of building operation post coronavirus lockdown. As per the new guidelines, the production units have been asked to consider first week after the lockdown ends as a trial period. The new guidelines address the issues from accommodation to sanitization needs. It also asks the companies to not target high production in the first week of operations. "When Lockout/Tagout procedures are not in place, many energy sources can prove to be hazardous to operators/supervisors who are servicing or maintaining electrical, mechanical or chemical equipment. When heavy machinery and equipment are not maintained periodically, they can become dangerous for the operators/engineers," NDMA said in a statement. 

Building owners and facility managers will be getting ready to reintroduce occupants to structures that may have been relatively vacant for an extended period. During this unique time, maintenance of all fire protection and life safety systems in commercial and multi-occupancy residential build­ings. However, it is possible that many of the ongoing inspection, testing, and maintenance (ITM) activities required by locally enforced codes and standards may not have been completed for a variety of reasons. Regardless of the level of ITM performed during this time, it is imperative that building owners and facility managers verify the performance of all building fire protection and life safety systems prior to reoccupation. Now we learn below factors that should be confirmed by a qualified person before re-open­ing a building to ensure safety of all its occupants.

Based on the assumption that the building was in compliance prior to being closed, the checklist below provides some initial steps to help ensure that the occupancy is safe enough to reopen until a qualified professional can complete the regularly scheduled ITM of all fire protection and life safety systems.
Fire and life safety checklist
Confirm all the following checkpoints for each of the building systems. While this is not a complete list, it does contain many of the items that can be addressed and confirmed by a building owner or facility manager during their initial work to reopen a building. We get help from IS, NBC 2016 & NFPA standard.

General
1.    All inspection, testing, and maintenance is up to date on the following systems or building elements:
❑ Water-based fire protection system (NFPA 25)
❑ Fire pumps (NFPA 25 & IS 12469)
❑ Fire alarm system (NFPA 72 & IS 2189)
❑ Commercial cooking equipment ventilation and fire protection (NFPA 96)
❑ Portable fire extinguishers (NFPA 10)
❑ Fire/smoke dampers (NFPA 80 and NFPA 105)
❑ All fire doors (NFPA 80 and IS 3614)
❑ Emergency lighting equipment (NFPA 101 & IS 10322)
❑ Exit signs (NFPA 101 & IS 12349)
2.    Appropriate fire department access is unobstructed. (NFPA 1)
3.    For wildfire-prone areas, routine maintenance of combusti­ble vegetation has been completed. (NFPA 1)
4.    Hand sanitizers or alcohol-based hand rubs are stored and managed safely (NFPA 101), and if needed, learn more at https://youtu.be/1P3GjIBKwI8.
5.    Whether an undertaking from LPG piping installation agency and client stating that proposed gas bank, supply lines and other fitting associated with it is as per NBC of India -2016, Part-IV.
6.    Check with the local authority having jurisdiction (AHJ) to find out if they require any special provisions prior to reoc­cupying the building.

Fire Extinguishers (NFPA 10 & IS 2171)
❑ Fire extinguishers are accessible and not physically damaged.
❑ Fire extinguishers are Correctly located in the designated place. Operating instructions are clean, legible, and facing outwards.
❑ Pressure gauge reading or indicator is in the operable range or position on all fire extinguishers.
❑ Check weigh the extinguisher against the gross weight stamped on cylinder (this is the weight full, without hose, horn or carriage). If underweight by more than 10% of contents, the extinguisher should be removed from service and recharged.

Water-Based Systems (NFPA 25, IS 3844 and IS 13039)
❑ All control valves are open.
❑ Gauges are operable and not physically damaged.
❑ Water filled piping is maintained above 40 F (4 C).
❑ Sprinklers are not physically damaged. If any leakage will be repaired.
❑ There are no leaks from the piping or sprinklers.
❑ A Diesel fire pump should be required and provide diesel exhaust pipe from the diesel engine and terminate to atmosphere in a location acceptable to the local Authority.
❑ Fire department connections are accessible and not physically damaged.
❑ Hose connections (if provided) are accessible and not physically damaged.
❑ An additional static water storage tank to be provided at roof / terrace level with capacity specified by the local fire authority with arrangements of replenishment by main or alternate source of supply, which can be used in the eventuality of failure of other system under gravity flow.
❑ Visual inspection for all valves must be open, accessible and unobstructed. All the fire pumps to have direct access from the ground level.

Fire Alarm Systems (NFPA 72 & IS 2189)
❑ There are no trouble, supervisory, or alarm signals.
❑ Batteries and their connections should be examined and tested to ensure that they are in good serviceable condition under FACP.
❑ Notification appliances are not blocked or physically damaged.
❑ Fire Control panel functions should be checked and tested with all fault indicators and Loop circuits should be tested and checked.
❑ Initiating devices (smoke detectors, heat detectors, etc.,) are not physically damaged.
❑ Manual pull stations are accessible and not physically damaged.
❑ A test & inspection of all integration (Like: PA, Access Control, EXIT signage, AHU) and graphic software.
❑ A visual inspection with Cleaning should be made to check 60% Smoke Detector, MCP, Heat Detector under fire alarm system.

Electrical (NFPA 70B and NFPA 110)
❑ Confirm that routine maintenance and operational testing is completed for the following:
❑ Electrical equipment per the building’s Electrical Preventative Maintenance Program.
❑ Emergency and standby power systems.

Means of Egress (NFPA 101 & NBC 2016)
❑ All means of egress paths are unobstructed.
❑ All doors in the means of egress are working properly and not physically damaged.
❑ All doors are operable from egress side.
❑ All doors are not physically blocked.
❑ All fire doors are working properly and not physically damaged.
❑ All fire doors latch.
❑ All required lighting in the means of egress is functioning properly.
❑ Means of egress is illuminated when occupied.
❑ Emergency lighting is not blocked or physically damaged.
❑ Exit signs are not blocked or physically damaged.
❑ Exit signs are properly illuminated.