Install End of Line Resistance

Install End of Line Resistance
End of line resistors (EOLR) are resistors of a specified value that are used to terminate protective loops or zones.

The purpose of EOLR's is to allow the control panel to supervise the field wiring for open or short circuit conditions. How the alarm responds to each depends on the panel as well as system zone programming, but generally speaking, an alarm views an open circuit as a fault or alarm condition, and a short circuit as a trouble or alarm condition (if armed). The purpose of EOLR's is to allow the panel to differentiate between the two conditions by looking for a known resistance.

EOLR's should be installed at the last device on the loop, electrically speaking, and not inside the control, unless special conditions are met. The benefits of EOLR's on protective zones with all concealed wiring is commonly argued by professional installers, as well as EOLR's installed inside the control unit, negating their effectiveness, as well as disabling the EOLR feature and using NC (normally closed) loops for zone definitions. The use of EOLR's is recommended and is particularly important when the field wiring is subject to damage or compromise.
A fire EOLR should always be installed at the last device and never inside the control or across the zone defined as fire, as this is an inherent safety issue.

Some equipment supports Double End of Line Resistors (DEOLR) to further differentiate between conditions that may exist on the loop.

Saturday, January 7, 2012

Two Wire Fire Alarm Systems

Two Wire Fire Alarm Systems
Traditionally fire alarm systems have been know as conventional / non-addressable and analogue addressable type fire alarm systems.  However in recent years a new type of fire alarm system has been introduced into the market.  These systems are known as two wire systems.
What are Two Wire Fire Alarm Systems?
Two Wire Fire Alarm Systems are zoned similarly to a conventional fire alarm system in that the panels are sized by the amount of zones they can accomodate.  Typically two wire fire alarm system panels are available in 2 zone, 4 zone and 8 zones, again similar to modern conventional fire alarm systems.  A traditional conventional fire alarm system will have separate detection zone radial circuits which accommodate the detectors and call points on the system and separate sounder and beacons radial circuits.  The difference with a two-wire fire alarm system is that they can accomodate detectors, call points, sounder and beacons all on the zone radial circuit.

The benifits of Two Wire Fire Alarm Systems
The main benefit of two wire fire alarm systems is the reduced installation costs.  With the detectors, call points, sounders and beacons all being on the same radial circuit there is now no need to wire seperate sounder radial circuits.  This can reduce the installation costs dramatically and also reduce the installation time. 

Another benefit of Two Wire Fire Alarm Systems is that many of the manufacturers have detectors with integral sounders.  This again means that the system can offer detection and sounders in a single installation point on the same radial zone circuit, again reducing installation costs.