Saturday, May 18, 2013

Fire Damper vs Fire Smoke Damper

Fire Damper vs Fire Smoke Damper

Do you know the difference between fire dampers and fire smoke dampers?
This is a questions that seems to come up a lot in the fire alarm install and design world.  The definition of a damper is "A person or thing that damps or depresses".  In other words it is a plate that is placed within the duct work of an HVAC system to regulate or in some cases stop air flow.

Now in the fire alarm industry we are more concerned with the terms "Fire Damper", "Smoke Damper" or "Combination Smoke Fire Damper".  Whats is the difference?  Well it is actually quite simple as we explain below.
·                  A "Fire Damper" as defined in the CMC (California Mechanical Code) 2010 Edition Section 206.0 - "An automatic-closing metal assembly of one or more louvers, blades, slats or vanes that close upon detection of heat so as to restrict the passage of flame and is listed to the applicable recognized standard."  The automatic means can be accomplished one of two ways: 1) by a fusible link that will melt upon heat thus releasing the louvers into the closed position.  2)  by motorized actuators that will close upon loss or gain of power.  These are typically controlled by and addressable relay module.
·                  A "Smoke Damper" as defined in the CMC (California Mechanical Code) 2010 Edition Section 206.0 - "A damper arranged to seal off airflow automatically through a part of an air duct system so as to restrict the passage of smoke and is listed to the applicable recognized standard."

·                  A "Combination Fire Smoke Damper" is exactly that, a combination of a "Fire Damper" and a "Smoke Damper".
When are they required and how do I know when to use what type?

Keep in mind that the fire alarm contractor will not be providing or installing these.  However, it is nice to know what to look for on a bid set of plans or during a job walk.  First up is the "Fire Damper".  A fire damper is installed in HVAC duct work at the intersection of a rated barrier such as walls or partitions.  The damper is in place to secure the integrity of the rated barrier in the event of heat or flames around 165 degrees F.  Like we stated above, the fusible link will melt thus releasing the louvers on the damper.  Once the louvers are closed or shut, the fire barrier is now secured from allowing flames to penetrate prior to the rating level of the barrier itself.
Smoke dampers are similar however, they close in the presence of smoke.  Now since the smoke damper cannot obviously sense smoke, we need to install a smoke detector. The smoke detector can either be a system smoke (tied to a building fire alarm system) or a stand alone smoke solely in place to activate the smoke damper.  Smoke Dampers are required to be installed on walls that separate smoke barriers.  

What's a smoke barrier you ask......  A smoke barrier is a continuous surface such as a wall, floor, or ceiling constructed to restrict the movement of smoke.  A smoke barrier can be either vertical or horizontal. 

Now a "combination smoke fire damper" is located in a situation where both fire rating and smoke barriers come into play.  A combination fire smoke damper also needs a smoke detector just like the smoke damper.  The smoke detector can either be a duct smoke detector (System Sensor D4120 or DNR) or a pendant mounted detector within the duct work itself.  Once the detector senses smoke particles it will either through programming or local relay base close the damper louvers.

18 comments:

  1. There are a large number of methods to modulate fire and smoke dampers and apply fire and smoke safety controls. In containment applications, the damper is closed when either high temperatures or smoke is observed. In smoke control systems a number of ways exist to either open or close the damper to purge or pressurize spaces to prevent smoke from spreading.

    Great Blog, awesome knowledge thank you very much.

    ReplyDelete
  2. Ensuring the safety of human life and property in buildings is one of the toughest demands that planners, builders, owners and operators are called upon to face. Smoke related injuries and deaths outnumber fire related injuries and deaths four to one. This is a rising concern for the safety of people and fire fighters who need to travel through building emergency exit routes as quickly as possible.

    Tactical methods for smoke control are: fans, smoke vents, and closed doors in combination with dampers. Strategy varies with each situation.

    Warehouses employ smoke vents to release smoke to the outside. NFPA 204M allows fans in the roof with louvers and dampers in the side walls to control the smoke.
    Stairwell pressurization systems combine fans and dampers to prevent smoke from entering the stairwell from a burning floor.
    Building HVAC ducting systems use motorized fire and smoke dampers to seal off individual zones. Dampers which are actuated electrically can be controlled from a central point and be integrated into safety control systems allowing a relatively smoke free exit for occupants and entrance of fire fighters.
    Fire and smoke dampers are an integral part of distribution systems and are critical links in the life safety systems associated with most buildings. They offer extra protection against the dangerous amounts of low temperature smoke often produced before a fire actually breaks out. Restricting fires to the area of origin not only helps stop fire spread but has been proven to allow sprinklers to operate efficiently, and helps to ensure safety of human life.

    ReplyDelete
  3. Hi Mr Bhadra, It was nice blog, i hope below info can help you more:
    NFPA 80 and NFPA 105

    NFPA 80 regulates fire dampers and fire doors. NFPA 105 regulates smoke dampers & smoke doors.
    Both standards state defective dampers must be repaired immediately.
    List of inspection points that should be performed to ensure dampers are in working order.
    Both standards require that a record of repairs is kept on the premises.
    Testing intervals are established at initial commissioning, one year, and then every 4 years except in hospitals which must test each device every 6 years. Local codes vary and overide national standards. Consult your local Fire Marshal or Building Official.

    NFPA 80 and 105 are adopted by reference in the International Building Code and most state or local codes. Sections 703.1.2 and 703.1.3 of the International Fire Code also reference NFPA 80 and NFPA 105.

    ReplyDelete
  4. Thanks for one marvelous posting! I enjoyed reading it; you are a great author. I will make sure to bookmark your blog and may come back someday. I want to encourage that you continue your great posts, have a nice weekend!
    nebosh course in chennai

    ReplyDelete
  5. The great service in this blog and the nice technology is visible in this blog. I am really very happy for the nice approach is visible in this blog and thank you very much for using the nice technology in this blog
    safety course in chennai

    ReplyDelete
  6. Thanks for sharing this quality information with us. Very well defined the topic. I really enjoyed reading.,,,,

    ReplyDelete
  7. Your blog provided us with valuable information to your post. Thanks a lot for sharing
    Bosch Rexroth Cytrobox

    ReplyDelete
  8. Hi,

    Thanks for sharing your blog. It was very nice. If you want fire dampers services then you can consider Coral Air we are one of the leading Fire Damper Installation & certification service providers. We have a dedicated team that can be deployed to professionally review and audit any building in the greater Sydney and Wollongong areas.

    ReplyDelete
  9. I just want to thank you for sharing your information and your site or blog this is simple but nice Information I’ve ever seen i like it i learn something today. Fire Damper Inspection

    ReplyDelete
  10. This blog is very informative thanks for sharing and keep on posting .#ISO 45001 LEAD AUDITOR

    ReplyDelete
  11. Thank you for sharing this blog !!!

    Find the best suppliers of fire dampers in Saudi Arabia.

    ReplyDelete
  12. Very nice blog you have posted. Thanks for sharing with us. Keep doing. If you are looking to hire expert for smoke alarm installation sydney ? So I would recommend you DRS Electrical. They offer smoke alarm installation, repair and maintenance with an affordable price. At DRS Electrical Services their expert electricians are always ready to assist you.

    ReplyDelete