ISOLATOR INSTALLATION, INSPECTION, AND SERVICE!

ISOLATOR INSTALLATION, INSPECTION AND SERVICE

Isolator module is used on the intelligent fire alarm control panels to protect the system against wire-to-wire short circuits on the analogue addressable loop wiring. Fire Projects designer know how and where to use this isolators to get optimum performance. Some of OEM told short-circuit isolator module which is designed to electrically separate and protect vulnerable parts of the bus.

SOME DO’s AND DON’T’s

In the last twenty (or so) years, I’ve been privileged to have been able to watch the tremendous advances in technology that continues to inspire several manufacturers around the world to explore new developments in electronic life safety systems.   Unfortunately, each new advance exposes some vulnerability that must also be addressed. 

In this article, we’re going to discuss “isolators” and more specifically, the correct wiring methods for the various types of circuits you’re going to encounter, as well as the testing that must be performed, both at the system’s commissioning/Verification and on an annual basis.  We’re going to focus on the changes currently adopted by the Canadian Standard for Installation of Fire Alarm Systems (CAN/ULC-S524) as well as what’s “in the pipe” in the way of amendments.

ISOLATOR TYPES AND TERMINOLOGY

What is an isolator, and how does it work?  Let’s begin by actually answering these two questions.  An isolator is a device that is designed to limit the extent a circuit is compromised by a single “short” fault.  In North America, there are four distinct “families” of short circuit isolators.  They are:

  • Data Communication Loop (DCL) Isolators – some manufacturers call them Signal Line Circuit (SLC) Isolators
  • Power Buss Isolators
  • Audio Buss Isolators
  • Suite Signal Isolators

Most isolators are “dumb” devices comprising a simple relay in a short sensing circuit on their “out” terminals.  As long as there is resistance on the circuit, they’re “happy”.  When the resistance drops to nothing (a short), they activate to preserve the loop integrity on their “in” side.  Some manufacturers have chosen to make their isolators “smart” by employing their panel’s protocols to “communicate” with each isolator.  This has the advantage of being able to “group bypass” an entire floor area from the common control if work is being performed there, without affecting the operational status of the rest of the system.  You’ll usually find these isolators employed by companies that are engaged in providing large scale networked type fire alarm systems (for the obvious reason that it also makes testing easier).

APPLICABLE CODES AND STANDARDS

NBC 2015, VBBL 2019

The only time isolators are actually mentioned in any Canadian Building Code is in conjunction with in-suite signalling means.  This is articulated in BCBC 2018 (as adopted from NBC 2015) in Section 3.2.4.19 called Audibility of Alarm Signals and reads in sentence (8):

“Audible signal devices within a dwelling unit or a suite of residential or care occupancy shall be connected to the fire alarm system:

a) in a manner such that a single open circuit at one device will not impair the operation of other audible signal devices on that same circuit that serve the other dwelling units or suites of residential or care occupancy, or

b) on separate signal circuits that are not connected to the devices in any other dwelling unit, public corridor or suite of residential or care occupancy. (See Appendix A.)”

CAN/ULC-S524-14

The Canadian Standard for Fire Alarm Installation is where we will find reference to the installation of Data Communication Link (DCL), network data, audio buss, and power buss fault isolators.  We will be using the abbreviations “DCL” “ND”, “AB” and “PB” for the purposes of this article.  It also deals with some specific installation requirements governing the use of insuite signalling isolators.

We’ve provided links to diagrams at the bottom of this page which detail both Class “A” interconnected field devices and a Class “A” Riser interconnected to field devices in a Class “B” configuration as part of this article.  This is one area where the manufacturer’s installation instructions also fall short and may even reference practices only acceptable outside of Canada (i.e. NFPA requirements).  The essential difference between the drawings you’ll see in the official amendment to the Standard and ours centres around one additional isolator which we’re suggesting be added to the “return” side of the loop to protect this part of the riser if you are employing uni-directional isolators.  In this instance, I’m of the opinion that this qualifies as an improvement on the actual requirements of the Standard (something that’s referred to as “good engineering practice”).

There are currently two versions of CAN/ULC-S524-14.  One includes the Amendments published in January of 2016 as a separate insert while the other will not have an amendment.  Please ensure your Standard includes the statement:  “Including Amendment 1” on the cover.

So, let’s begin with Clause 5.7.3:

“Where a data communication link utilizing active field devices or supporting field devices serves more than one National Building Code of Canada required fire alarm zone, a fault within one National Building Code of Canada Required fire alarm zone shall not prevent the normal operation of other input or output field devices in another National Building Code of Canada required fire alarm zone, except as noted in Clause 5.7.3.4.

Note:  See also Clause 4.3.1.8 and 4.3.1.9.”

5.7.3.4 states:

“Active field devices or supporting field devices serving water flow devices, supervisory devices on sprinkler systems, or duct type smoke detectors on HVAC systems that are located within a National Building Code of Canada required fire alarm zone but serve other National Building Code of Canada required fire alarm zones, need not be separately fault isolated from each other or the National Buiilding Code of Canada required fire alarm zone.”

5.7.3.5 states:

“A control unit or transponder or its associated data communication link that serves more than one floor area, shall be subject to the constraints of Clause 5.7.3.1.”

5.7.3.6 states:

“Data communication link style A with fault isolation modules, or data communication link style C with fault isolation modules, or an equivalent method shall be utilized to meet the requirements of Clauses 5.7.3.1, 5.7.3.4, and 5.7.3.5.  (Refer to Figure 5).”

Inbuild Isolator Brand Like: ESSER, COOPER... etc

Base Isolator Brand Like: GST, Edwards... etc

Isolator as a Separate product Brand Like: Edwards, Notifier, Morley, GST, Apollo, Ravel... etc

Section 4.3 is entitled “ELECTRICAL SUPERVISION”.

4.3.1.8 states:

“Except as permitted by Clause 4.3.1.10 or Clause 4.3.1.11, where a power buss circuit serves more than one National Building Code of Canada required fire alarm zone, a single fault (open circuit fault, short circuit fault or ground fault) shall not prevent the normal operation of input or output field devices in more than one National Building Code of Canada required fire alarm zone.

NOTE:  Refer to Appendix A (Informative) Explanatory Materials, Clause A4.3.1.8.”

4.3.1.9 states:

“Except as permitted in Clause 4.3.1.10, where an audio buss serves more than one National Building Code of Canada required fire alarm zone, a single fault (open circuit fault, short circuit fault, or ground fault) shall not prevent teh normal operation of input or output field devices in more than one National Building Code of Canada required fire alarm zone.”

4.3.1.11 states:

“Where a power buss serves supporting field devices which are located within a common National Building Code of Canada required fire alarm zone but serve other National Building Code of Canada required fire alarm zones, the power buss segment serving these supporting devices is not required to comply with Clause 4.3.1.8.”

4.3.1.12 states:

“Class A circuit with fault isolators installed in accordance with Subsection 10.2, Fault Isolators, or an equivalent method, shall be utilized to meet the requirements of Clauses 4.3.1.9 and 4.3.1.10.

NOTE:  For Data Communication Links, refer to Subsection 5.7.3, Field Device Data Communication Link.”

Section 10.2 is entitled “FAULT ISOLATORS”

10.2.1.1 states:

“This Subsection applies to the installation of fault isolation modules as required by Subsection 5.7.3, Field Device Data Communication Link, for data communication links between field devices.  (Refer to Figures 33.1, 33.2, 33.3, and 33.4.)

Note:  Where available, data fault isolators should be located in a fire separated electrical room.”

10.2.1.2 states:

“Data fault isolators shall be utilized when entering and leaving each National Building Code of Canada required fire alarm zone.   See also Appendix A (Informative) Explanatory Materials, Clause A4.3.1.8.”

10.2.1.3 states:

“Data fault isolators required by Clause 10.2.1.2 are not required between field devices located within the same floor area that are monitoring mechanical equipment serving other floor areas.

NOTE:  For example, water flow devices on sprinkler systems or duct type smoke detectors on HVAC systems serving other floor areas are considered part of the same area specified in Clause 10.2.1.2 and need not be separately fault isolated from other devices within that area.”

10.2.1.4 states:

“Except as noted in Clause 10j.2.1.5, data fault isolators, shall be located in a separate enclosure and installed so as to be visible and accessible at all times.”

10.2.1.5 states:

“Data fault isolators that are integral to a field device shall be mounted in accordance with the requirements of that field device.”

Note:  Field devices incorporating fault isolation modules complying with Clause 10.2.1.2 do not require additional dedicated data fault isolators.”

10.2.1.6 states:

“Where a fire separation is provided, data fault isolators required by Clause 10.2.1.2 shall be installed on each side of that fire separation.”

10.2.1.7 states:

“Data fault isolators installed on opposite sides of the same fire separation shall be offset horizontally to a minimum of 400 mm, and not located within the same stud space.”

10.2.1.8 states:

“Where no fire separation is provided between each National Building Code of Canada required fire alarm zone, a single fault isolation module shall be utilized when isolating zones within the same floor area.

Note:  This Clause would be applicable to large horizontal buildings, e.g., warehouses, shopping malls, factories, etc.”

10.2.1.9 states:

“Data fault isolators serving a single field device in an exit or vertical service space shall be installed on the floor area side.

Note:  Fault isolation modules are not required on the exit or vertical service space side.  See Figure 2.4”

10.2.1.10 states:

“Data fault isolators shall have an identifying mark or label on the cover plate or field device.  The identifier shall be visible after installation.  Where field devices incorporating fault isolation modules are used to comply with Clause 10.2.1.2, the first field device entering and the last field device leaving each National Building Code of Canada required fire alarm zone shall be marked.”

 

Friday, October 1, 2021

Maintenance of Smoke & Heat Detector

 Maintenance of Smoke & Heat Detector

Maintenance of Smoke Detector

Requirements for Maintenance of smoke detectors vary by country & OEM, the common need is for a functional maintenance and test where smoke, or simulated smoke, is introduced through the vents of the detector to the sensor.

If you have standalone smoke detector, test the alarm monthly. Replace the batteries at least once every year. Replace the entire smoke alarm every 10 years. Press and hold the test button on the smoke detector. It can take a few seconds to begin, but a loud, ear-piercing siren should emanate from the smoke detector while the button is pressed. If the sound is weak or non-existent, replace your batteries. Most of Standalone detectors have either a blinking or a solid light that glows to let you know that the alarm is getting power.

Before starting the Maintenance job for 2wire / 4wire smoke detector, take the proper work permit and inform to all the respective departments / local authority. Then do force the respective logics or interlocks if any (like fire suppression systems activation etc).

§  Prior to maintenance of Smoke detector see the LED status of the Smoke Detector it should be blinking green or red. Now open Detector from Base.

§  Check the voltage of the Smoke Detector, it should be within +30 Volts DC. This can be checked at the addressable base of the detector. This step applicable if detector not responding or gives false alarm.

§  Clean the Smoke Detectors outside dust by brush and vacuum cleaner. Without open the detector from base you may do it.

§  Open Smoke Detector as per manufacturer’s published instructions and clean internal chamber through slowly brush and put air blower diagonally. Do not use any chemical or liquid for cleaning. This step applicable if detector not responding or gives false alarm.

§  Fixed smoke detector in same base. Do not alter smoke detector with another one.

§  Now Smoke Detector is healthy and it is ready for testing.

§  Apply the aerosol spray to the Smoke Detector by solo Smoke detecting gun with the help of the Solo A10/A5 aerosol bottle. Do not use any incense sticks (Agarbatti) and pray to energised smoke detector. Some of manufacturer’s allow use of Magnet to activate / energised smoke detector.

§  Keep applying aerosol spray for 10 seconds.

§  After 10 seconds LED status of the Smoke detector will change from the steady blinking red to steady red and after that alarm appears and hooter is activated on the fire alarm panel.

§  To silence the hooter press silence / acknowledge key on the Fire Alarm Panel. As per manufacturer’s published instructions.

§  After alarm appears remove Smoke detecting test gun from Smoke Detector.

§  Note down the alarm tag and descriptions from the HMI or workstation. The alarm details must match with the smoke detector tag number and installed location.

§  Confirm the smoke detector activation status from the respective graphics page. You have to visually identify the colour change signals of the respective smoke detector on the graphics.

§  Reset the alarm of the Smoke detector from Fire Alarm Panel.

§  The Detector LED status will change from steady red to blinking red.

§  Smoke Detector is now working normally.

§  Repeat the above procedure for all the remaining smoke detectors.

§  Normalize the forced interlocks or logics if any.

§  Close the work permit.

Note: The mentioned voltages or LED colors sequence may change as per the vendor or model of the smoke detectors. Solo Smoke Aerosols is approved all over the world, its Non-toxic & Silicone free. Solo smoke aerosols (used with the Solo 330/332 dispensers) deliver smoke particles to the detector under test replicating the conditions of smoke from a fire. Our range of smoke aerosols has recently increased to allow continued use of our Solo 330/332 dispensers in full compliance with latest regulations.

Unique Formula Identifier (UFI), is a 16 character alphanumeric code which will soon be required to appear on the labelling of all products classified as hazardous by the ECHA. UFI codes will become mandatory on relevant products across Europe from January 2021.

Maintenance is required to be performed in accordance with the manufacturer’s published instructions, with an emphasis on cleaning. Cleaning should be in strict accordance with the manufacturer’s instructions and as frequently as the ambient conditions of the placement area demand. For example, the manufacturer of a smoke detector could recommend annual cleaning, but ambient conditions might dictate cleaning be conducted at 3-month intervals. Areas subject to accumulations of dust and dirt that require more frequent cleaning include elevator hoistways and machine rooms, HVAC ducts, and boiler rooms. Recommended at list 10% of total Smoke detector test as per above procedure if your Fire Detection System age is 1 – 5years. After 5 year recommended at list 25% of total Smoke detector test as per above procedure. In above snap we observe some Service person open Edwards SIGA PS detector and clean in front of washbasin. This is not recommended by Edwards. Actual process describe in second snap. SSA Integrate are doing lots of Edwards Product Maintenance and confirm you that SIGA-PS, SIGA-PHS detectors are upgraded to SIGA-PD and SIGA-PHD respectively and can be used along with our former model in the same loop as well.

One of the main concerns regarding NFPA 72 is testing frequency for sensitivity, or rather, is smoke detector sensitivity testing required? The simplest answer is that testing must be performed annually. However, frequency also depends on the dates and results of the latest test. Further, sensitivity testing will be required unless it’s monitored on a continuous basis on the fire panel and an alert goes out when sensitivity is not within the required range.

Also, the frequency will depend on the type of detectors and the capabilities of the fire alarm control panel.

It may even be possible to avoid costly sensitivity tests on each detector. To quote NFPA 72-2016 14.4.3.2-17 (h) (4), “Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit when its sensitivity is outside its listed sensitivity range” is accepted as a means of ensuring that each smoke detector is working properly.

If you have a newer panel, it likely has this capability, but you can confirm this with the alarm contractor, and also determine its capabilities. Some newer systems may also be able to save sensitivity readings from fire panel software after the annual testing. That way, you have a record of the sensitivity at any particular time.

Required frequency will depend on the time and the results of two consecutive tests. Thus, smoke detector sensitivity should be inspected within a year after it is installed, then inspected each alternate year after that. After a second test that shows the device is within the appropriate sensitivity range, then the length of time between tests may be extended to a maximum of five years.

Maintenance of Heat Detector

Heat detector can be defined as an element or device that detects changes in heat or fire. If any heat (change in heat that exceeds the limits of heat sensor ratings) is sensed by the heat sensor, the heat sensor generates a signal for alerting or activating a security or protection system to extinguish or avoid the fire accidents. There are different types of heat sensors, which are classified based on different criteria such as the amount of heat withstanding capacity, nature of heat sensing capacity, and so on. Furthermore, the heat sensors are classified into different types that include analog heat sensors and digital heat sensors.


Heat detector can sense the heat (change in heat according to the features of heat detector used). But, a circuit is to be designed for activating an alarm system to indicate fire or heat change and for alerting the security or protection system. Heat detector circuit can be designed using heat sensor.

These heat detectors are mainly classified into two types based on their operation and they are “rate of rise heat detectors” and “fixed temperature heat detectors”. Above snap of Heat Detector from AUTRONICA. The most important point is “SelfVerify” function ensures the highest grade of reliability. All Autronica units comprising this function are automatically tested with a calibrated test once every 24 hours.

Before starting the job, take the proper work permit and inform to all the respective departments. Then do force the respective logics or interlocks if any (like fire suppression systems activation etc)

§  Prior to testing of Heat detector see the LED status of the Heat Detector it should be blinking green or red.

§  Open heat detector from Base. This step applicable if detector not responding or gives false alarm.

§  Check the voltage of the Heat Detector, it is within +30 Volts DC. This can be checked by the addressable base of the detector. This step applicable if detector not responding or gives false alarm.

§  Clean Heat detector body and thermistor stick through cotton cloth. Do not put pressure on thermistor stick or heat element stick. This step applicable if detector not responding or gives false alarm.

§  Fixed Heat detector in same base. Do not alter with another one.

§  Now Heat Detector is healthy and it is ready for testing.

§  Clean the Heat Detector’s outside dust by cotton cloth and air blower.

§  Apply the heat to the Heat Detector by solo heat-detecting gun.

§  Keep applying heat for 10 seconds.

§  After 10 seconds LED status of the Heat detector is changing from steady blinking red to steady red and after that alarm appears and the hooter is activated on the fire alarm panel.

§  To silence the hooter press the acknowledge key to the Fire Alarm Panel.

§  After the alarm appears remove the heat-detecting test gun from Heat Detector.

§  Note down the alarm tag and descriptions from the HMI or Graphic workstation. The alarm details must match with the heat detector tag number and installed location.

§  Confirm the heat detector activation status from the respective graphics page. You have to visually identify the colour change signals of the respective heat detector on the graphics.

§  Reset the alarm of the Heat detector from the Fire Alarm Panel.

§  The detector LED status is changing from steady red to blinking red.

§  Heat Detector is now working normally.

§  Repeat the above procedure for all the remaining Heat Detectors.

§  Normalize the forced interlocks or logics if any.

§  Close the work permit.

Note: The mentioned voltages, terminals, circuit module names may change as per the vendor or model of the Heat Detector. Available in both 110 / 120 and 220 / 240 volt versions the Solo 423 and 424 are the professionals’ choice where cables and leads are acceptable. Unconstrained by energy availability they provide the quickest of test times and are, perhaps, most suitable for the highest temperature detectors.

Maintenance is required to be performed in accordance with the manufacturer’s published instructions, with an emphasis on cleaning. Cleaning should be in strict accordance with the manufacturer’s instructions and as frequently as the ambient conditions of the placement area demand. For example, the manufacturer of a smoke detector could recommend annual cleaning, but ambient conditions might dictate cleaning be conducted at 3-month intervals. Areas subject to accumulations of dust and dirt that require more frequent cleaning include elevator hoistways and machine rooms, HVAC ducts, and boiler rooms. Recommended at list 20% of total heat detector test as per above procedure if your Fire Detection System age is 1 – 5years. After 5 year recommended at list 40% of total heat detector test as per above procedure. SSA Integrate is provide Maintenance service for AUTRONICA Fire Product.

The system owner is responsible for maintaining records retained for 1 year thereafter. The records shall be on a medium that will survive the retention period. Paper or electronic media shall be permitted. The owner is to be provided with and maintain a copy of the site-specific software so that it is available to determine how the system is programmed and to reprogram the system if the program in the control unit is corrupted or deleted.

This type of Maintenance Scope will increase Maintenance commercial value. Some of Maintenance Company quote low and do not doing this way. Always prefer certified person or Authorised Company to maintain properly of your Fire Detection & Alarm System. Do avoid utilised your friends for life safety product Maintenance. SSA Integrate will help you neutrally to get proper decision for your Fire Detection System.


Wednesday, September 15, 2021

INTERPRETATION & INSTALLATION REQUIREMENTS

INTERPRETATION & INSTALLATION REQUIREMENTS

What is a Style “A” Loop?  What is a Style “B” Loop?  What is a Style “C” Loop?

First off, don’t get confused between “Class” and “Style”!  “Style” refers to the functionality of communications loops between Listed control panels, transponders, and field devices (provided to the loop controller through a combination of the system’s firmware or software and strategically placed isolators).  “Class” refers to the wiring scheme used to interconnect them.  A Style “A” and Style “C” loop are actually wired identically in a Class “A” scheme.  Both Style “A” and Style “C” loops have an independent return path which becomes an alternate means of communicating with connected control units,  transponders and field devices should a portion of the loop become compromised by an “open” on the circuit.  Style “C” loops however, provide a higher level of functionality when the loop becomes compromised by a short circuit on the wiring.  A Style “C” loop is a continuous Class “A” type circuit that goes from one floor area to another without interruption.  A Style “A” loop is limited to one floor area (and doesn’t usually require isolators as it’s powered by a dedicated loop controller).  In a Style “B” loop, an “open” (or short) will sever communications with any control unit (or transponder) wired in the shorted circuit.

Field devices are wired either Class “A” or Class “B” in a floor area.  To add to the confusion, you can also “T” tap within the same floor area when you’re using addressable field devices or route both the return and primary loops into a single five conductor cable assembly in certain circumstances which are illustrated within the Installation Standard.

Table 1 in CAN/ULC-S524-14 serves to illustrate the various pros and cons of the different “Styles” utilized in the communications between control panels and transponders (it also provides the means for the Verifier to identify whether-or-not the correct response occurs when a short is imposed on the communications loop between control panels and transponders).  A Style “B” type loop is NOT ALLOWED in Canada for a DCL riser between control units or transponders, but it IS ALLOWED between buildings in a Campus Style Network.  Class “B” wiring is NOT ALLOWED for a DCL or a Power Buss common riser between a control unit and connected active (or supporting) field devices.

CLASS “A” CONNECTED FIELD DEVICES:

In order for isolators to work properly in this type of configuration, the “out” side of the first unit on the floor area must face the “out” side of the last unit on the floor area.  An exception exists for isolators that may employ bi-directional communication protocols.  You should definitely check the manufacturer’s information and installation guide.  Either way, if they identify an “in” and an “out”, you can’t go wrong.  A short anywhere on the floor will result in both isolators activating which limits the loss of data/power to only the devices in that single area.  This having been said, it must be noted that isolators employed on a DCL “A” loop will only have a single wire connected under each terminal, positive “in”, negative “in”, positive “out” and negative “out”.

This photograph depicts an isolator terminated in a DCL “A” loop that’s wired incorrectly.

You will note that, in both our wiring circuit diagrams, there is an additional isolator added to the mix, which the diagram in the 2014 version of the Installation Standard does not include.  This unit protects the return side riser between the common control and the last floor area.  Please note that if the control panel’s DCL/PBR loop is equipped with on-board isolators, the first two units immediately shown in line from the common control (which we’ve highlighted in RED) are not required.  Please ensure that the control panel’s documentation clearly identifies that the DCL/PBR loop is isolated (and indicates the configuration)!  An exception to this rule exists where the manufacture may RECOMMEND the installation of isolators in this location as a means of preserving the integrity of the loop controller over the life of the fire alarm system.

Class “A” DCL/PBR loop wiring diagram (both Style “A” and Style “C” loops are illustrated)

Class “A” DCL/PBR loop wiring diagram (both Style “A” and Style “C” loops are illustrated)

CLASS “A” LOOP RISER WITH CLASS “B” CONNECTED FIELD DEVICES:

In order for isolators in this configuration to operate as intended, both “out” sides of the two isolators installed in the floor area are “T” tapped to the Class “B” wired devices on the floor.  There is an additional wiring method which is perfectly suited to a control panel replacement within a building where a traditional conventionally zoned fire alarm system was installed.  Both methods are illustrated in the diagram in below image.

TESTING/SERVICE

The testing methods vary slightly depending upon the type of isolator (as well as who manufactured it).  It’s a good idea to have the installation instructions handy for the model of isolator you’re testing.  This will usually include a recommended test procedure that might differ slightly from what you read here.

NOTE:  The manufacturer’s suggested test methods should be used in EVERY case.

SLC (Signalling Line Circuit) or DCL (Data Communication Line) Isolators:

Testing method - There are two termination points on every isolator.  One is an “in” from the common data loop and the other is an “out” to the field devices it serves.  Short the “out” side to ensure the unit functions correctly (yes, this means that you will have to remove the cover on each unit!).  Depending on the number of devices on the “out” side, you should see a string of error messages on the common control that are most commonly identified by the phrases “missing device” or “device error”, or “data loop short”.  Maintain the short until you have scrolled through and noted each device that fails to report.  Part of your “test” ensures that the total number of devices for each isolator does not exceed the manufacturer’s maximum limit.  If more than one floor area’s devices fail to report while the short is in place you will have to note this as a deficiency on your report!  If the isolator you’re testing happens to be bi-directional proceed to short the “in” side.  Maintain the short until your helper has scrolled through and noted each device that fails to report.  The other part of the test (with the short still in place) requires you to proceed to another floor area and initiate an alarm from there.

Field devices which employ isolator bases must also be tested.  If the system you’re testing employs these units (it’s usually the first smoke detector on the loop), you’ll have to find an addressable device (a manual station is usually the easiest to access) downstream of the isolator.  Drop it and short the loop terminals from here.  Maintain the short and have your helper scroll through and note each device that fails to report.  Again, you’ll have to perform the alarm test component from a field device located outside of the shorted zone.

Power Supply & Audio Riser Buss Isolators:

Testing method - While shorting a power supply (or audio output circuit) is not normally recommended, opening the circuit on the “out” side of the isolator will identify the devices it protects.  You must ensure the maximum current for the unit is not exceeded (or the recommended maximum number of devices).  Use your meter (set to “amps”) to determine what each isolator is handling.  In EVERY case, follow the manufacturer’s suggested test methods and note the results in your report.

Suite Signal (Bell/Buzzer Circuit) Isolators:

Normally these units are installed in the common area corridor outside of the suites they serve.  They’re always located behind a suitable cover which identifies them as a fire signalling component or fire alarm device.  There are two “flavours” available:  “supervised” and “unsupervised”,  The unsupervised isolator is NOT allowed by Code or the installation standard (CAN/ULC-S524) despite the fact that the devices may be ULC Listed!  If you come across one (they will have a label affixed to them identifying them as such), you must fail the unit.  No further testing is required.

Testing method - There are two phases to the required testing.  One is performed while the system is in normal supervisory mode, the other is performed while the system’s sounders are active.  For these tests, it is recommended they be performed inside the suite the unit serves.  You will notice that there are two “outputs” on each isolator (it serves two separate suites or units).  All in-suite devices controlled by an isolator are wired in a Class “A” loop.

Step 1 - Remove the cover from the isolator to expose the wiring terminals.
Step 2 - Identify the common NAC circuit input and output terminals from the fire alarm control panel.
Step 3 - Perform the circuit testing required of any notification appliance utilizing these terminals.  Replace the cover when the testing is complete.
Step 4 - Remove and drop any one of the in-suite buzzers. 
Step 5 - Disconnect one of the terminals (or terminal leads).  You should receive an “open” fault at the common control.  If the isolator you’re testing happens to be a Potter/Amseco IS-S, then one of the LED’s should also illuminate on the cover.  With the wire disconnected, have your partner initiate a “drill test”.  The buzzer in your hand (and all the buzzers in the suite) should sound.  This is the supervisory test and Class “A” operational test for the buzzers in the suite.
Step 6 - Reconnect the terminal. 
Step 7 - Now short positive and negative together.  Observe the display on the common control (as well as on the isolator - if applicable) and note it. 
Step 8 - With the short still on, have your helper initiate a fire drill test.  None of the buzzers in the suite should be sounding, but the buzzers on the other side of the isolator (as well as the other suites on the floor) should be unaffected. 
Step 9 - With the system still in active “drill test”, REMOVE the short.  The buzzer in your hand should start to sound. 
Step 10 - Reinstate the short.  The buzzer in your hand (as well as any others in the same suite) should all stop sounding.  The buzzers in the other suite served by the isolator should continue to sound. 
Step 11 - Have your helper deactivate the “drill test”.

If all of the above tests are completed satisfactorily, you can move on to the next suite on the floor (after reinstalling the buzzer that is!).

NOTE:  If, in step 8, none of the buzzers in the suites sound, then the notification appliance circuit is programmed incorrectly!  You must ensure this is corrected before proceeding with the testing of the rest of the insuite appliances.  Some systems utilize a jumper setting to activate the signals if isolators are on the circuit.  Other systems require access to the physical panel programming to enable this feature.