Saturday, October 5, 2013

Changes to NFPA 13

13 Changes to NFPA 13


As the newest edition of NFPA 13 is set to be presented next month, NFPA has published some of the notable changes to this document:
1.               CPVC compatibility - where corrosion inhibitors are used in combination systems that include coated steel pipe and CPVC pipe, the coating must be tested for compatibility with CPVC.
2.               Freeze protection requirements - tentative interim amendments regarding antifreeze solution to prevent the freezing of water in sprinkler pipes has been formally adopted into the standard
3.               Sprinkler requirements for elevator spaces and hoistways - allows fire sprinklers to be omitted from elevator machine rooms, elevator machinery spaces, control spaces, or hoistways of traction elevators where a number of conditions are met, and brings the standard in alignment with other model building codes
4.               Title change to NFPA 13R - Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies
5.               Sprinkler protection in small bathrooms - Apartment buildings with bathrooms less than 55 square feet (5 square meters) must now have sprinkler protection where they were not  previously required to do so.
6.               Shadow areas -  shadow areas are permitted in the protection area of a sprinkler as long as they do not exceed 15 square feet per sprinkler.
7.              
"Sprinkler system" definition - modified to describe a system as an integrated network of piping that includes a water supply source, a water control valve, a water flow alarm, and a drain; this largely effects the requirements of 
NFPA 25.
8.               Backflow preventer requirements - a forward flow test will now be required on allNFPA 13/13R installations.
9.               Storage chapter - newly added; allows for an alternative design approach.
10.            Sloped ceilings - provides five common ceiling arrangements that allow for hydraulic calculations
11.            Water mist systems - refers users to NFPA 750.
12.            Cloud ceilings - protection to follow the use of obstruction rules.
13.            ESFR and CMSA sprinklers - these will now be permitted to protect light and ordinary hazard areas.

Friday, September 13, 2013

Coincidence Connection of Detectors for Triggering Extinguishing Systems

Guidance for Coincidence Connection of Detectors for Triggering Extinguishing Systems


This guide is a collation and explanation of the existing recommendations provided on the use of coincidence connected detectors with a particular focus on their application for triggering extinguishing systems. It defines a scheme for describing the different approaches to coincidence connection and in particular considers potential replacements for ionisation detectors.

Although predominantly aimed at assisting those involved in the automatic release of extinguishing systems, this FIA guide also provides information in situations where coincidence of detectors is needed for the actuation of other fire protection measures.

Review of Standards

There is a common misconception that BS 7273-1 Clause 5.2.3 calls for coincidence detection using two different types of detector, typically ionization and optical smoke detectors to trigger fire suppression systems. This is not correct.

5.2.3 Type of detector used

The selection of detectors should be in accordance with the recommendations given in BS 5839-1 and, where applicable, BS 6266. In some circumstances, fire detection considerations might dictate the need for use of two different principles of detection (e.g. optical smoke detectors and ionization chamber smoke detectors) to ensure the earliest warning of fire. In such circumstances, an even distribution of each type of detector should be provided throughout the protected space.

Where coincidence is used, normally it should be possible to achieve coincidence from two detectors of the same operating principle. In these cases, if, for example, two independent circuits are used to achieve coincidence, there should normally be an approximately equal number of detectors of each principle connected to each of the independent circuits. For example, where four detectors are required to protect the space and these comprise two optical smoke detectors and two ionization chamber smoke detectors; there should be one optical smoke detector and one ionization chamber smoke detector on each circuit.

However, it is not always necessary to use two different principles of fire detection. For example, given the type of fire anticipated and the speed of detection required, it might be acceptable to use detectors of a single type.

BS 7273-1 does not require the use of detectors using two different principles of operation:

·        Clause 5.2.2.1 suggests that co-incidence detection is one method of minimising the possibility of false discharge.

·        Clause 5.2.2.4 clarifies that co-incidence detection requires alarm signals from two independent detectors (whether the same type or not).

The second paragraph of clause 5.2.3 (above) was originally a continuation of paragraph 1 and as a separate paragraph is now confusing. The intent is to clarify that where mixed types are used, it is not normal to require both types (e.g. optical and ionisation) to have indicated an alarm before the extinguishant is released. In other words extinguishant may be triggered from any two independent detectors e.g. two ionisation detectors or two optical detectors or an ionisation and an optical detector.

Clause 5.2.3 only includes as examples the traditional combinations of optical and ionisation detectors. There are many other technologies which may be used, for example flame detection, multi-sensor devices, aspirating smoke detectors (ASD) which can be used to mitigate the risk of inadvertent discharge of extinguishant.

BS 7273-1 refers back to BS 5839-1 and BS 6266 for advice on the selection of fire detectors. Both these standards have been revised since BS 7273-1 was published and provide useful guidance:

·        BS 6266:2011 Clause 8.3
·        BS 5839-1:2013 Clause 21

Options for Coincidence Detection

Co-incidence detection is when at least two independent detectors are used to initiate the release of the extinguishing system. These can be of the same type or of two different types.

The type(s) chosen should be selected dependant on the fire risk and on the objectives of the fire system.

Given that ionisation smoke detection is in obsolescence, the traditional ionisation / optical combinations as exemplified in BS 7273-1 is losing relevance.

Some common possible alternative combinations include:

·        Optical & Optical
Traditional scatter type optical smoke detectors

o Optical smoke detectors must pass a range of fire tests including smouldering and flam-ing types and have proved to be suitable for many applications requiring co-incidence

o Flaming fires will be detected; however response may be slower than ionisation detec-tors


·        Optical & Optical-Heat (or Optical-Heat & Optical-Heat)

o Optical-Heat detectors speed the response of a standard optical smoke detector to a flaming fire by responding to heat

o Some Optical-Heat detectors may respond more slowly to a smouldering fire than a traditional optical detector


·        ASD & ASD (or ASD & other)
o  Very early warning of incipient fires is possible using Class A & B ASD systems which can

prompt early intervention and avoid automatic discharge of the fire suppression system
– whether to a real fire threat or an unwanted event (false alarm)
o    ASD & ASD requires two separate detectors to achieve true co-incidence detection
o    Inputs to the extinguishing system must be carefully selected (e.g. Class C only)
o    See also FIA Aspirating Smoke Detectors CoP


·        Optical & Flame (or Flame & Flame)
o    Fast detection of flaming fires
o     Flame detector requires unobstructed line of sight to area of coverage
o    Used only in special applications where flame is a particular risk


·        Multi-sensor & Multi-sensor (including dual-optical)

o   Many different types available with many different modes of operation therefore careful consideration needs to be made of the configuration of the detectors
o   Often designed to mitigate nuisance alarm risk and enhance fire detection


·        Heat & other

o   The use of heat detectors only is not recommended as heat detector response is very slow in comparison to a smoke detector

References and Applicable Standards

BS 5839-1:2013, Fire detection and fire alarm systems for buildings - Code of practice for design, installation, commissioning and maintenance of systems in non-domestic premises

BS 6266:2011, Fire protection for electronic equipment installations. Code of practice

BS 7273-1:2006, Code of practice for the operation of fire protection measures. Electrical actuation of gaseous total flooding extinguishing systems.

A small note on FM 200.

🧱 1. What is FM-200? FM-200 is a clean agent fire suppression gas stored under pressure and released into protected spaces to extinguish fires without leaving any residue. 🧱 2. Components FM-200 System 1. Storage Cylinders: • Contain FM-200 in a compressed gas state, typically pressurized to 24.8 bar or higher. • Can be located inside or outside the protected room. 2. Discharge Piping Network: • Delivers the agent from cylinders to discharge nozzles. • Designed based on hydraulic flow calculations. 3. Nozzles: • Distribute the gas uniformly throughout the room. • Their number, spacing, and type depend on room volume and layout. 4. Control Panel: • Interfaces with detection devices and controls automatic or manual release. • Receives signals from smoke/heat detectors. 5. Smoke and Heat Detectors: • Detect fire early and send signals to the control panel for verification. 6. Abort Switch: • Allows users to cancel the discharge countdown if fire confirmation is false. 7. Manual Release Station: • Enables manual activation of the system in emergency cases. 8. Audible & Visual Alarms: • Alert occupants of imminent discharge with a pre-discharge countdown (typically 10–30 seconds).
⚙️ 3. How FM-200 Works 1. Fire Detection: • The system uses two cross-zoned detectors (smoke or heat) to confirm fire presence. • Upon verification, a signal is sent to the control panel. 2. Pre-Discharge Alarm: • Audible and visual alarms are activated to alert personnel. • A time delay allows evacuation before discharge (configurable, typically 10–30 seconds). 3. Agent Discharge: • FM-200 is released through nozzles into the room. • It absorbs heat and interrupts the combustion chain reaction, extinguishing the fire rapidly (<10 seconds). 4. Post-Discharge Actions: • HVAC and ventilation systems are automatically shut down. • Motorized dampers and openings are sealed. • The agent remains in the room for a specified holding time to prevent re-ignition. 🔌 4. Integration with BMS (Building Management System) 🔍 A. Monitoring: • Display system status: Ready / Activated / Fault / Discharged. • Monitor cylinder pressure and room conditions. • Supervise detector status (smoke, heat). • Log all events and fault alarms. 🎛️ B. Control: • Automatically shut down: • HVAC units (AHUs, FCUs). • Ventilation fans. • Motorized dampers and air intakes. • Manage pre-discharge delay and manual override (Abort). • Enable smart discharge logic (e.g., smoke + heat + room occupancy). 🔗 C. Integration: • Full integration with: • Fire Alarm Control Panel (FACP). • Voice evacuation systems. • Access control (e.g., door locks, room isolation). 📢 D. Notifications: • Trigger alerts in BMS central station. • Send notifications via email or SMS to technical teams.


Saturday, September 7, 2013

Fire alarm installation practices and workmanship

Fire alarm installation practices and workmanship

The nature and quality of the fire alarm installation work needs to be such as to maintain the integrity of the fire alarm system and minimize the duration and extent of disablement of the system during maintenance or modifications. Installation practices and workmanship need to conform to the requirements of BS 7671. 
Penetration of construction (e.g. for the passage of cables, conduit, trunking or tray) need to be “fire stopped” to avoid the free passage of fire or smoke, regardless of whether the construction has a recognized degree of fire resistance.

Recommendations:
The following recommendations are applicable.
1) The entire electrical fire alarm system installation should conform to the requirements of BS 7671. In general, the recommendations of this standard supplement, but do not conflict with, these requirements. Where any such conflict is considered to exist, the recommendations of this standard should take precedence.
2) Cables which are directly fixed to surfaces should be neatly run and securely fixed at suitable intervals, in accordance with the recommendations of the cable manufacturer. Cables should not rely on suspended ceilings for their support.
3) The installer should ensure that all wiring complies with, at least, 26.2f) to 26.2o).
d) Joints in fire alarm cables, other than those contained within the enclosures of equipment, should be avoided wherever practicable [see 26.2g)].
4) So far as is reasonably practicable, cable routes should be selected to follow the recommendations . Care should be taken to ensure the electrical continuity of electromagnetic screens, including metallic sheaths of cables.
5) Where new conduit, trunking or tray is installed, its capacity should be in accordance with the recommendations given in BS 7671.
6) Where a cable passes through an external wall, it should be contained in a smooth-bore sleeve of metal or other non-hygroscopic material sealed into the wall. This sleeve should slope downwards towards the outside and should be plugged with a suitable non-hardening waterproof compound to prevent the entry of rain, dust or vermin.
7) Where a fire alarm cable passes through an internal wall, a small clearance hole should be provided. If additional mechanical protection is necessary, a smooth-bore sleeve should be sealed into the wall.
8) Care should be taken to ensure that the ends of any sleeves are free from sharp edges which might damage cables during installation.
9) When a cable passes through a floor, the considerations a sleeve should extend as far above floor level as is required for protection of the cable it is to carry, but never less than 300 mm.
10) Where cables, conduits, trunking or tray pass through floors, walls, partitions or ceilings, the surrounding hole should be as small as reasonably practicable and made good with fire stopping materials that ensure that the fire resistance of the construction is not materially reduced. Spaces through which fire or smoke could spread should not be left around the cable, conduit, trunking or tray.
11) If cables or conduits are installed in channels, ducts, trunking or shafts that pass through floors, walls, partitions or ceilings, barriers with the appropriate level of fire resistance should be provided within the channels, etc. to prevent the spread of fire unless, in the case of ducts and shafts, the construction of the duct or shaft affords equivalent fire resistance to the structure penetrated; in the latter case fire stopping need only be provided where cables pass into, or out of, the duct or shaft.

Saturday, August 3, 2013

L2 Fire Alarm

L2 Fire Alarm

IS 2189 : 2008: Indian Standard. Selection, Installation And. Maintenance Of Automatic Fire. Detection And Alarm System
IS 11360 (1985): Specification For Smoke Detectors For Use In Automatic Electrical Fire Alarm System [CED 22: Fire Fighting]

A fire alarm system is number of devices working together to detect and alert people through visual and audio appliances when smoke/fire is present. These alarms may be activated from Smoke Detectors, Heat Detectors, MCP etc.

Smoke detectors do not have a listed spacing. They have a recommended spacing of 30 feet between detectors. However, smoke detectors can be installed up to 41 feet apart in corridors up to 10 feet wide. The main fact to remember is that all points on the ceiling must be within 21 feet of the detector.

Commercial systems are categorized as follows (All include manual call points):
·         L1 – Detection provided throughout the entire premises
·         L3 – Detection provided on all escape routes and adjoining areas
·       L3/L2 – Detection provided on all escape routes and adjoining areas, as well as additional detection in specified high risk areas
·         L4 – Detection provided on all escape routes only
·      L4/L2 – Detection provided on all escape routes and additional detection in specified high risk areas
When a system is installed in a premises where there is more than one interlinked system in operation, then the suffix “X” is used.

Many fire authorities are now insisting on specific standards of fire alarm systems within buildings.  These categories are defined in the recommendations of BS5839.  One of the most common categories which is being asked for is a BS5839 category L2 Fire Alarm System.  The prefix 'L' for the category type stands for life protection.  This means that the primary purpose of a category L2 Fire Alarm is to protect life.  Whereas BS5839 system designs with a 'P' prefix are primarily designed to protect damage to property.


L2 Fire Alarm Systems are designed to offer automatic detection on all escape routes within a building, with the addition of all rooms adjoining to the escape route.  An L2 Fire Alarm design should also take into account any further areas of high risk which may not necessarily be covered with detection on the escape routes and adjoining rooms.  Examples of these areas could be boiler rooms, plant rooms and other areas with heavy plant machinery (such as in roof voids).
An Example of an L2 Fire Alarm Design
L2 Fire Alarm designs should also incorporate audible sounders throughout the building which operate when the fire alarm system is activated.  These sounders should achieve a minimum sound pressure of 65 dB (A) throughout the building and a minimum of 75 dB (A) at the bedhead where there people sleeping within the building.

An L2 Fire Alarm should also include manual call points on all exits to open air, and in buildings above a single storey all entrances to stairwells on the floors above the ground floor.  In large buildings it should also be noted that nobody should have to travel for more than 35 metres to reach a call point.  This means that further call points may be needed to be positioned within the property to achieve this.  Call points may also need to be positioned in high risk areas.  One example of this may be a paint booth where high flammable substances are present.  A call point may need to be positioned in close proximity to enable an alarm to be raised quicker should an incident occur.

Awareness of the system user is also essential, less able bodied people may or may not be capable of exiting without assistance, but high levels of people with sporting injuries or with hearing difficulties may require a system which addresses their needs.

Saturday, July 6, 2013

Smoke Detector & Heat Detector Mounting Heights

Smoke Detector & Heat Detector Mounting Heights BS5839
There are essentially two types of initiating devices used in a typical fire alarm system: automatic and manual.

Typical automatic devices include spot-type smoke detectors, rate-of-rise heat sensors, fixed-temperature sensors, photoelectric smoke detectors, sprinkler heads and duct-type smoke detectors.

Manual activation is commonly accomplished using a manual fire pull, and automatic detection happens without human intervention. NFPA 72, also called the National Fire Alarm Code (NFAC), is the primary document used when an engineer designs, and an EC or fire alarm technician installs, a fire alarm system.

BS5839 makes reference to recommendations of maximum mounting heights for different types of detectors.  This is to ensure that the detector is still effective when mounted at high levels.  The recommendations of BS5839 split the mounting heights up into two categories.  These categories are standard BS5839 systems and systems with a 5 minute fire service response time.

Below is a series of recommended mounting heights for fire alarm system equipment including different types of smoke detector (including Optical Beam Detectors) and Heat Detectors.
The table below also shows heights which detectors are permitted to be mounted at if 10% or less of the ceiling is the height shown.

Mounting Heights 
Detector Type
Maximum Ceiling Height (m) Cat L/P
5 Minute Response (m) Cat P
Rate of Rise Heat Detector
9 Meters (10.5 meters for 10% of Ceiling)
13.5 Meters (15 meters for 10% of Ceiling)
Fixed Temperature Heat Detectors
7.5 Meters (10.5  meters  for 10% of Ceiling)
12 Meters (15 meters for 10% of Ceiling)
Smoke Detectors
10.5 Meters (12.5  meters  for 10% of Ceiling)
15 Meters (18 meters for 10% of Ceiling)
CO Point Detectors
10.5 Meters (12.5  meters  for 10% of Ceiling)
15 Meters (18 meters for 10% of Ceiling)
Optical Beam Detectors
25 Meters (25  meters  for 10% of Ceiling)
40 Meters (40 meters for 10% of Ceiling)

Automatic smoke detector placement is another important aspect of a fire alarm installation. Unless every smoke detector is placed properly, false alarm, or even no alarms, can occur. Either way, the client suffers, and the low-voltage contractor looks bad in the process.
The most common type of smoke detector used in residential and commercial settings is the spot-type detector. According to Section 5.7.3.2, NFPA 72, 2007 Edition, spot-type smoke detectors can be mounted either on the side wall or ceiling. When using the side wall, mount the device no closer than 4 inches from the ceiling.

The maximum distance is 12 inches. The distance from detector to side wall when mounting the same smoke detector on a ceiling is the same 4 inches. Ceiling-mounted units also must be placed no closer than 4 inches from a side wall.

Spacing between smoke detectors is likewise important. On a smooth ceiling, the common distance between each smoke detector is 30 feet. According to Section 5.7.3.2.3.5, all points on a smooth ceiling should have a smoke detector within 0.7 times the selected spacing or 21 feet.

Not all ceilings are smooth; thus, the spacing between smoke detectors will vary. To ensure optimum performance and compliance, refer to Chapter 5 of NFPA 72, 2007 Edition, for a specific situation. Read also Codes & Standards, page 140.

Space and placement both matter when planning your fire alarm package. Thorough preparation often leads to a successful installation.

As per IS: 2189:2008 under clause 6.3.2 Siting and spacing of detectors (common to all types of smoke and heat detectors):
  1. Under flat ceilings, the horizontal distance between any point in a protected area and the detector nearest to that point shall not exceed 7.5 m in case of smoke detector, and 5.3 m in case of heat detector.
  2. In case of a sloping roof or pitched ceiling (where the distance between the top of apex and bottom of the roof exceeds 600 mm), spacing of detectors at or in the vicinity of apex may be spaced between 7.5 m and 8.5 m for smoke detectors.
  3. Detectors shall not be mounted within 500 mm of any walls, partitions or obstructions to flow of smoke or hot gases, such as structural beams and duct work, where the obstructions are greater than 250 mm in depth.
  4. Where structural beams or duct work for light fittings or any other ceiling attachments, not greater than 250 mm depth, create obstacles to the flow of smoke, detectors shall not be mounted closer to the obstruction than twice the depth of the obstruction.
  5. Where partitions or storage racks that reach within 300 mm of the ceiling, they shall be construed as walls that extend to the ceiling for the purpose of siting the detectors.
  6. Similarly, ceiling obstructions, such as structural beams, deeper than 10 percent of the overall ceiling height shall be construed as walls for the purpose of siting the detectors, that is, each bay formed by such beams shall be treated as separate enclosure for provision/spacing of detectors.
  7. Detectors shall not be mounted within 1m of any air inlet (supply air inlets of H VAC system) or a forced ventilation system.
  8. Detector siting shall be such that a clear space of 500 mm is maintained below each detector.
  9. Where detectors are constrained to be fixed to the wall, they shall be sited in such a way that the top of the detection element is between 150 mm and 300 mm below the ceiling and the bottom of the detection element is above the level of door opening. Additional detector shall be placed on the ceiling at a position 1.5 m from any opening which might act like a flue.
  10. A detector shall be placed on the protected side of the premises on the ceiling 1.5 m from any door, window or any opening in the wall partitions separating the protected premises from the other premises.
  11. All stairwells, lift shafts, other utility shafts, etc, shall have a detector at the top. Lift machine rooms shall be provided with a detector.
  12. All unenclosed staircase shall have one detector at each main landing within the staircase.
  13. The detector shall also be provided in cable tunnels, ducts, false floors, AC and AHU room, long AC return ducts and distribution boards.
  14. No detector shall be subjected to any interior decoration treatment, that is, painting, alteration of exterior cover, etc, to conform with the environment.
  15. Every enclosure (that is, room or cabin) shall have a detector at ceiling level and also under false ceiling, if provided.
  16. Where there is more than one such enclosure per floor, a response indicator shall be installed at the entrance to such enclosures to indicate where the detector has actuated. This arrangement shall also be followed in case of all concealed detectors in false floors, plenums, shafts, tunnels, etc.
  17. Voids as in false ceiling/flooring more than 800 mm shall be protected with detectors with spacing like in normal installation. However, voids as in false ceiling/flooring less than 800 mm height need not necessarily have independent coverage unless the void is such that the spread of fire products between the rooms or compartments take place through it. Bathroom, lavatories, WC, etc, however, need not be protected.
  18. For irregular shaped areas, the spacing between the detectors may be greater than the determined spacing provided the maximum spacing from the detector to the farthest point of a side wall or comer within its zone of protection is not greater than 0.7 times the determined spacing.
As per IS: 2189:2008 under clause 6.3.3 Compensation to the Spacing of Detectors
  1. Height consideration
Spacing of 7.5 m for smoke detectors is valid up to a height of 7 m only and that of 5.3 m for heat detectors is valid only up to a height of 5 m. beyond these heights, spacing between the detectors shall be adjusted as follows:
    1. Smoke detectors for heights between 7 m and 10 m - 5 m spacing
Beyond 10m height - Only beam detectors or aspirating type detection systems
    1. Heat detectors for heights between 5 m and 7 m - 3.5 m spacing
Beyond7m height- Not allowed to install heat detectors
  1. High air movement consideration
    1. Spacing between detectors shall be suitably reduced in areas where high air movement or where high air changes prevail.
    2. Detectors shall not be located in the vicinity of supply air diffusers. Minimum distance between the detector and the air inlets/diffusers shall be at least 1.5 m.
    3. Detectors shall be so mounted as to favour the air flow towards return air openings.
    4. The above provisions shall not disturb the normal population (count) of detectors, which is provided assuming that air-handling systems are off.
    5. After designing the detector spacing, it shall be cross-checked to ensure that there is at least one smoke detector for every 100 m2 or one heat detector for every 50 m’ of the compartment area.