Friday, August 15, 2025

Upcoming changes in NBC 2016 Part 4 ANNEX J (Clause 6.4.4) J-8 & J-9

Upcoming changes in NBC 2016 Part 4 ANNEX J (Clause 6.4.4) J-8 & J-9 

As on date 15-08-2025, latest version of NBC 2025 still not released. This post is tentative only. Latest version of NBC 2025 is applicable for existing buildings when they are altered (see clause 12.4 of Part 2) or in the opinion of the authority constitute a hazard to the safety of the adjacent property or to the occupants of the building itself or are unsafe.

Annex J for FIRE AND LIFE SAFETY REQUIREMENTS FOR METRO STATIONS.

J-1 APPLICATION AND SCOPE

J-2 TERMINOLOGY

J-3 GENERAL

J-4 LIFE SAFETY REQUIREMENTS

J-5 EGRESS PROVISIONS

J-6 FIRE SEPARATION AND COMPARTMENTATION

J-7 OTHER SPECIFICS REGARDING SAFETY REQUIREMENTS

New upcoming J-8 POWER SUPPLY SYSTEM

New upcoming J-9 EMERGENCY LIGHTING SYSTEM

J-8 POWER SUPPLY SYSTEM

In NBC 2016 Part 4 says “the back-up/emergency power supply shall have a capacity to cater all critical loads such as emergency lighting, protective signalling system, communication system, fire station and control room, lifts providing required egress capacity, etc.”

Now upcoming NBC 2025 Part 4 under Annex J-8 says.

J-8.1 General

The Auxiliary Substation at Metro stations can be provided at any location, for example, Ground Level, Concourse Level, Platform Level, etc. The access for dismantling and replacement in future and ease of operation and maintenance of the equipment are to be ensured.

J-8.2 Uninterrupted Power Supply (UPS) System

The UPS shall be an online parallel redundant system with battery back-up for emergency power supply. The batteries shall provide backup for minimum 90 minutes.

If, DG set power backup to UPS is provided, the battery backup time shall be suitably selected.

J-8.3 Back-up or Emergency Power supply

a) The back-up/emergency power supply shall have a capacity to cater all critical loads such as emergency lighting, protective signaling system, communication system, station control room/fire command centre, lifts providing required egress capacity, etc.

b) Power supply to these systems and equipment shall be from normal and emergency (standby generator power sources with changeover facility).

c) If the power supply is taken from HT source and HT generation, the transformer shall be selected with standby capacity to ensure continuity of power supply to such systems. Where parallel HV/LV supply from a separate independent source is provided with appropriate transformer for emergency, the provision of Diesel Generator for emergency supply may be waived at the discretion of Metro Authority. In such a scenario, in case of failure of Mains power, the transfer to emergency power supply should be automatic and within 10 s for ensuring uninterrupted supply to emergency systems.

J-8.4 Cables

a) Fire resistant/survival, low smoke zero halogen, copper conductor, armoured, XLPE insulated cables shall be used at enclosed stations for fire and life safety equipment like Fire Alarm System (FAS), Tunnel Ventilation Fans, Smoke Extraction Fans, Staircase Pressurization Fans, fire pumps, emergency lighting, etc.

b) All cables and wiring used for fire and life safety equipment shall have a 3h fire survival capability at 950 °C.

c) For all other essential services at enclosed stations like Chillers, AHU, Normal lighting, Chilled Water pumps etc. flame retardant, low smoke zero-halogen (LSZH), armoured, XLPE insulated Aluminium/copper conductor cables shall be used.

d) At open stations, flame retardant, low smoke halogen free (FR, LSH), armoured, XLPE insulated Aluminium/copper conductor cables shall be used for power supply.

e) Fire alarm system signalling loop circuit (SLC) cable must be in red colour. Other hand Power cable must be in black colour.

J-9 EMERGENCY LIGHTING SYSTEM

a) LED lighting fixtures shall be used for lighting at Metro stations.

b) Emergency illumination shall include illumination of means of egress, illuminated exit signs, and all other luminaires specified as necessary to provide required illumination. Emergency lighting systems shall be designed and installed so that the failure of any illumination source cannot leave in total darkness any space that requires emergency illumination. Emergency lighting shall not provide less than average of 10 lux. Minimum illumination of 10 lux shall be maintained on egress route.

c) Fire resistant (FR), low smoke and zero halogen (LSZH) copper conductor wires shall be used for wiring of emergency lighting system at underground stations.

Emergency lighting system (ELS) circuit shall have 3hr fire survival (FS) capability at 950°C.

d) Out of total light fixtures installed at any station, at least 30% of the total lights, all uniformly distributed shall be connected to emergency power source,  that is, UPS.

e) Emergency lighting shall be powered from a source independent of  that supplying  the normal lighting.


REFERENCE:

CED 46(26992) WC - Draft Code for Comments Only.







Sunday, December 1, 2024

Summary of NBC 2016 Part 4 Fire and Life Safety

Summary of NBC 2016 Part 4 Fire and Life Safety 

Bureau of Indian Standards (BIS) is the National Standards Body of India established under the BIS Act 2016 for development of standards, marking and quality certification of goods and for matters connected therewith or incidental thereto.

The National Building Code of India 2016 (NBC 2016), a comprehensive building Code prepared by BIS, is a national instrument providing guidelines for regulating the building construction activities across the country.

Thus, the Code gives all the information required by the architect, engineer, structural engineer, construction engineer, services engineer and other professionals from the early stages of planning to translating the building on to terra firma. The comprehensive NBC 2016 contains 13 Parts some of which are divided into Sections and Subsections totalling 33 chapters.

Key Content - Fire and Life Safety

All buildings shall satisfy minimum requirements for safety of life from fire, smoke, fumes or panic arising from these or similar causes.

Classification of buildings based on occupancy

The city or area under the jurisdiction of the Authority shall be demarcated into distinct fire zones depending upon the existing layout, types of building construction, classification of existing buildings based on occupancy and expected future development of the city or area. Intermixing of hazardous occupancies should not be allowed in other zones.

1) Fire resistant walls, floors and compartments

• To limit the spread of fire

• No compromise for openings such as shafts, refuse chutes, vertical openings, etc.

2) Shafts

• To be provided with fire resistant rated inspection door for passage of building

services such as cables, electrical wires, telephone cables, plumbing pipes, etc

depending upon location.

3) Refuge area

• An area within the building for a temporary use during egress. It generally serves as

a staging area which is protected from the effect of fire and smoke.

4) Fire detection and firefighting installations

• These include fire alarm, fire extinguishers, hose reels, wet riser, down comer,

yard hydrants, sprinklers, deluge system, water spray, foam, water mist systems,

gaseous or dry powder system, water storage tanks and pumps, etc.

5) Means of egress

• Consists of three separate and distinct parts, that is, exit access, exit and exit discharge

• Exit access are working/functional areas

• Various types of exit access and exits are doorways, corridors and passageways, horizontal exits, internal staircases, exit passageways, external staircases and ramps.

6) Firefighting shafts

• With fire man talk back, fire door, wet riser, hose reel, signage showing floor plan and stairways and fire man’s lift

Fire prevention

Fire prevention is based on the following:

        Occupancy

        Fire zones

        Types of construction

        General requirement of all occupancies

        Electrical installation

a.   Emergency power for fire and life safety system

b.   Substation

c.    Lightning protection

d.   Escape lighting and exit signage

e.   HVAC and smoke control

f.     Glazing

g.   Surface interior finish

h.   Fire Command Centre

        Fire resistance rating of structural and non-structural elements updated

        Fire resistance rating of service shaft and duct opening of 2 hours.                                 Inspection door and duct opening should have same resistance rating of  service shaft.

        Facade protection and openable windows in facade shall have fire protection and smoke exhaust aspects

        Compartment criteria of different occupancies and fire separating wall & floor partitions are modified

        Provision of fire/smoke damper design more elaborated like provision of damper

A.   At the fire separation wall

B.   Where ducts/passage enter the vertical shaft

C.   Where the duct passes through floor

D.   At the inlet of supply air duct and return air duct of each compartment on every floor.

Glass facade

  1. For fully sprinkler building having fire separation of 9 m or more, tampered glass in a non-combustible assembly with ability to hold the glass in position shall be provided
  2. It shall be ensured that sprinklers are located within 60 cm and there is full coverage of glass. All the gaps between floor slab and facade assembly shall be sealed at all level by fire resistant sealant material of equal rating of floor slab to prevent fire and smoke propagation from one floor to another.
  3. Openable panels shall be provided in each floor and shall be spaced not more than 10 m apart, measured along the external wall from the centre to centre of the access opening. Such opening shall be operable at a height between 1.2 m and 1.5 m from the floor in the form of openable panel (Fire Access Panel) not less than 1000 mm x 1000mm opening outward.

FIRE OPENABLE PANEL DO NOT OBSTRUCT IN  25 mm lettering in the inner side can also act as smoke exhaust at the time of distress.

Service Sector in Focus

Some important features considered in Hospitals

        Each compartment shall be able to accommodate patients from adjoining compartment and Density Factor (Number of patient) area to be allotted 3.5 sq.m/person

        Critical patients, incapable of self-preservation and physical impairment shall be housed within 30 m height

        Other types of patient and occupancy like Nurses’ centre, Medical shop, Canteen, etc to be in between 30-45 m in height

        Operation theatre, Delivery room, ICU, Recovery room shall have a separation with 2 hours of fire resistance rating

        Passage width of aisles, corridor, ramp, etc shall be 2.4 m unobstructed through which patients are being moved and in case of inpatient width not less than 1.5

        All exits from Hospital or Infirmary Section shall not be less than 2m

        Minimum door width single/double occupancy shall be 1.25 m; for 3-5 patients, door width shall be 1.50 m; for more than 5 patients and patient evacuation bed (i.e. ICU) it shall be 2.0 m; for single/double doors, it shall be 1.5 m

        Any sleeping accommodation or suite exceeding 100 sq.m in area, 2 no.s of access door leading to escape route, corridor, etc to be provided

        Room designed for laboratory or like facility shall be limited to 100 sq.m in area for additional area coverage. Fire separation shall be done by 2 hours fire resistance.

        A stretcher lift in the lift bank shall also act as a fireman lift

Life safety is based on:

        General exit

        Occupant load

        Declaration of occupant load

        Egress components

        Smoke control of exit

        Compartmentation

        Smoke control above and below ground

        Gas supply

        Hazardous area

        Fire detection

        Fire drill

Safe electrical supply system

        The electrical supplies towards the critical aspects of emergency power for fire and life safety addressed for respective system.

        Power supply to the panel and distribution board be through fire proof enclosure or circuit integrity cable or through alternate route in the adjoining fire compartment is protected within the compartment of vulnerability and require location of the panel/distribution board feeding shall be in fire and safety zone and ensure supply of power to these system.

        The high voltage electrical equipment safety including aspects of emergency and exit lighting of large and public assembly occupancies

        HVAC system, smoke control and mitigation also to be taken care of with comprehensive approach towards compartmentation and spread of fire and smoke.

Life safety

        To calculate the number of exit requirement with Density Factor

        Exit Layout for better understanding of various aspects of means of egress, corridor, passageways, stair ways and exit

        Provision for access control door, electromagnetic door, revolving door and turnstile (conditions to be fulfilled)

        Provision of handrail at both sides of stairs and ramp width exceeding 1.5m

        Internal stair width of residential building increased to 1250 mm from 1000 mm

        External stairs width increased from 1250 mm to 1500 mm

        Each fire rated door shall have a marking on the product of its certification. Door assembly parts like hinges, locks, panic bars, door closer and door viewer shall be certified.

        Updated staircase pressurization requirement (Smoke control of exit) for lobbies & corridors

        Smoke exhaust and pressurization of area below the ground floor

        Requirement of smoke exhaust system having make up air system for the theatre and atrium

        Smoke exhaust fan in the mechanical ventilation system shall be fire rated of 250 degrees centigrade for 2 hours (120 minutes)

        Provision of smoke barrier and sprinkler around the opening for escalator

        Requirement of display of occupancy load for assembly occupancy and call center.