Sunday, December 1, 2024

Summary of NBC 2016 Part 4 Fire and Life Safety

Summary of NBC 2016 Part 4 Fire and Life Safety 

Bureau of Indian Standards (BIS) is the National Standards Body of India established under the BIS Act 2016 for development of standards, marking and quality certification of goods and for matters connected therewith or incidental thereto.

The National Building Code of India 2016 (NBC 2016), a comprehensive building Code prepared by BIS, is a national instrument providing guidelines for regulating the building construction activities across the country.

Thus, the Code gives all the information required by the architect, engineer, structural engineer, construction engineer, services engineer and other professionals from the early stages of planning to translating the building on to terra firma. The comprehensive NBC 2016 contains 13 Parts some of which are divided into Sections and Subsections totalling 33 chapters.

Key Content - Fire and Life Safety

All buildings shall satisfy minimum requirements for safety of life from fire, smoke, fumes or panic arising from these or similar causes.

Classification of buildings based on occupancy

The city or area under the jurisdiction of the Authority shall be demarcated into distinct fire zones depending upon the existing layout, types of building construction, classification of existing buildings based on occupancy and expected future development of the city or area. Intermixing of hazardous occupancies should not be allowed in other zones.

1) Fire resistant walls, floors and compartments

• To limit the spread of fire

• No compromise for openings such as shafts, refuse chutes, vertical openings, etc.

2) Shafts

• To be provided with fire resistant rated inspection door for passage of building

services such as cables, electrical wires, telephone cables, plumbing pipes, etc

depending upon location.

3) Refuge area

• An area within the building for a temporary use during egress. It generally serves as

a staging area which is protected from the effect of fire and smoke.

4) Fire detection and firefighting installations

• These include fire alarm, fire extinguishers, hose reels, wet riser, down comer,

yard hydrants, sprinklers, deluge system, water spray, foam, water mist systems,

gaseous or dry powder system, water storage tanks and pumps, etc.

5) Means of egress

• Consists of three separate and distinct parts, that is, exit access, exit and exit discharge

• Exit access are working/functional areas

• Various types of exit access and exits are doorways, corridors and passageways, horizontal exits, internal staircases, exit passageways, external staircases and ramps.

6) Firefighting shafts

• With fire man talk back, fire door, wet riser, hose reel, signage showing floor plan and stairways and fire man’s lift

Fire prevention

Fire prevention is based on the following:

        Occupancy

        Fire zones

        Types of construction

        General requirement of all occupancies

        Electrical installation

a.   Emergency power for fire and life safety system

b.   Substation

c.    Lightning protection

d.   Escape lighting and exit signage

e.   HVAC and smoke control

f.     Glazing

g.   Surface interior finish

h.   Fire Command Centre

        Fire resistance rating of structural and non-structural elements updated

        Fire resistance rating of service shaft and duct opening of 2 hours.                                 Inspection door and duct opening should have same resistance rating of  service shaft.

        Facade protection and openable windows in facade shall have fire protection and smoke exhaust aspects

        Compartment criteria of different occupancies and fire separating wall & floor partitions are modified

        Provision of fire/smoke damper design more elaborated like provision of damper

A.   At the fire separation wall

B.   Where ducts/passage enter the vertical shaft

C.   Where the duct passes through floor

D.   At the inlet of supply air duct and return air duct of each compartment on every floor.

Glass facade

  1. For fully sprinkler building having fire separation of 9 m or more, tampered glass in a non-combustible assembly with ability to hold the glass in position shall be provided
  2. It shall be ensured that sprinklers are located within 60 cm and there is full coverage of glass. All the gaps between floor slab and facade assembly shall be sealed at all level by fire resistant sealant material of equal rating of floor slab to prevent fire and smoke propagation from one floor to another.
  3. Openable panels shall be provided in each floor and shall be spaced not more than 10 m apart, measured along the external wall from the centre to centre of the access opening. Such opening shall be operable at a height between 1.2 m and 1.5 m from the floor in the form of openable panel (Fire Access Panel) not less than 1000 mm x 1000mm opening outward.

FIRE OPENABLE PANEL DO NOT OBSTRUCT IN  25 mm lettering in the inner side can also act as smoke exhaust at the time of distress.

Service Sector in Focus

Some important features considered in Hospitals

        Each compartment shall be able to accommodate patients from adjoining compartment and Density Factor (Number of patient) area to be allotted 3.5 sq.m/person

        Critical patients, incapable of self-preservation and physical impairment shall be housed within 30 m height

        Other types of patient and occupancy like Nurses’ centre, Medical shop, Canteen, etc to be in between 30-45 m in height

        Operation theatre, Delivery room, ICU, Recovery room shall have a separation with 2 hours of fire resistance rating

        Passage width of aisles, corridor, ramp, etc shall be 2.4 m unobstructed through which patients are being moved and in case of inpatient width not less than 1.5

        All exits from Hospital or Infirmary Section shall not be less than 2m

        Minimum door width single/double occupancy shall be 1.25 m; for 3-5 patients, door width shall be 1.50 m; for more than 5 patients and patient evacuation bed (i.e. ICU) it shall be 2.0 m; for single/double doors, it shall be 1.5 m

        Any sleeping accommodation or suite exceeding 100 sq.m in area, 2 no.s of access door leading to escape route, corridor, etc to be provided

        Room designed for laboratory or like facility shall be limited to 100 sq.m in area for additional area coverage. Fire separation shall be done by 2 hours fire resistance.

        A stretcher lift in the lift bank shall also act as a fireman lift

Life safety is based on:

        General exit

        Occupant load

        Declaration of occupant load

        Egress components

        Smoke control of exit

        Compartmentation

        Smoke control above and below ground

        Gas supply

        Hazardous area

        Fire detection

        Fire drill

Safe electrical supply system

        The electrical supplies towards the critical aspects of emergency power for fire and life safety addressed for respective system.

        Power supply to the panel and distribution board be through fire proof enclosure or circuit integrity cable or through alternate route in the adjoining fire compartment is protected within the compartment of vulnerability and require location of the panel/distribution board feeding shall be in fire and safety zone and ensure supply of power to these system.

        The high voltage electrical equipment safety including aspects of emergency and exit lighting of large and public assembly occupancies

        HVAC system, smoke control and mitigation also to be taken care of with comprehensive approach towards compartmentation and spread of fire and smoke.

Life safety

        To calculate the number of exit requirement with Density Factor

        Exit Layout for better understanding of various aspects of means of egress, corridor, passageways, stair ways and exit

        Provision for access control door, electromagnetic door, revolving door and turnstile (conditions to be fulfilled)

        Provision of handrail at both sides of stairs and ramp width exceeding 1.5m

        Internal stair width of residential building increased to 1250 mm from 1000 mm

        External stairs width increased from 1250 mm to 1500 mm

        Each fire rated door shall have a marking on the product of its certification. Door assembly parts like hinges, locks, panic bars, door closer and door viewer shall be certified.

        Updated staircase pressurization requirement (Smoke control of exit) for lobbies & corridors

        Smoke exhaust and pressurization of area below the ground floor

        Requirement of smoke exhaust system having make up air system for the theatre and atrium

        Smoke exhaust fan in the mechanical ventilation system shall be fire rated of 250 degrees centigrade for 2 hours (120 minutes)

        Provision of smoke barrier and sprinkler around the opening for escalator

        Requirement of display of occupancy load for assembly occupancy and call center.


Sunday, July 16, 2023

MS FOR FIRE ALARM SYSTEM INSTALLATION

METHOD STATEMENT FOR FIRE ALARM SYSTEM INSTALLATION

 

Ø TABLE OF CONTENTS

1. SCOPE

2. definitions

3. HEALTH AND SAFETY

4. OPERATION

5. installation and fixation

6. RESPONSIBILITIES

7. MANPOWER REQUIRED

8. MATERIALS REQUIREMENTS

9. EQUIPMENTS REQUIREMENTS

10. WASTE MANAGEMENT

11. SPECIAL CONTROL MEASURES

12. SUPPORTING DOCUMENTATION

13. DISTRIBUTION

1. SCOPE

Ø  This procedure to clear the method of the supply, installations of Fire Alarm system for the project.

Ø  This document details the Fire Alarm system Installation:

1.  Preparation of work.

2.  Delivery and inspection upon arrival of material at site.

3.  Installation of the system.

2. definitions

           PQP             : Project Quality Plan

PSP              : Project Safety Plan

QCP             : Quality Control Procedure

HSE             : Health, Safety and Environment

MS               : Method Statement

ITP               : Inspection Test Plan

QA/QC         : Quality Assurance / Quality Control Engineer.

WIR              : Inspection and Test Request

MIR              : Material Verification Record.

3. HEALTH  AND  SAFETY

Ø  Strictly followed as per the manufacturer's Health and Safety recommendations for handling and use of the materials.

Ø  Ensure all involved personnel shall be aware of the same.

Ø  Specific safety measures have to follow as applicable, and all the safety measures are covered separately in the project safety plan.

4. OPERATION

Ø  Material: 

§  Material used will be as approved by the Engineer.

§  The sizes and routes routing will be as per the approved Shop Drawings.

Ø  Storage and Protection: 

·       Deliver components parts to site, completely identified in accordance with shop and certified CAD Drawings prepared for this work.

·       Store in accordance with the manufacturer’s instructions, above ground, properly protected from the weather and construction activities.

5. INSTALLATION and fixation

Ø  Pre-Installation:

·       Make sure that civil clearance done prior to start the installation.

·       Installation will be carried out as per manufacturer recommendations Approved shop drawings and project specifications.

 

Ø  Installation:

§  Verify that hardware and devices are NRTL listed (In South Florida) or UL, FM, EN, VDS & NFPA for use with fire-alarm system before making connections.

§  Make addressable connections with a supervised interface device to the following devices and systems.

§  Install the interface device less than 3 feet (1 m) from the device controller.

§  Make an addressable confirmation connection when such feedback is available at the device or system being controlled as follows :

1.     Alarm-initiating connection to smoke-control system (smoke management) at fire-fighter smoke-control system panel.

2.     Alarm-initiating connection to stairwell and elevator-shaft pressurization systems.

3.     Smoke dampers in air ducts of designated air-conditioning duct systems.

4.     Alarm-initiating connection to elevator recall system and components.

5.     Alarm-initiating connection to activate emergency lighting control.

6.     Alarm-initiating connection to activate emergency shutoffs for gas and fuel supplies.

7.     Supervisory connections at valve supervisory switches.

8.     Supervisory connections at low-air-pressure switch of each dry-pipe sprinkler system.

9.     Supervisory connections at elevator shunt trip breaker.

10. Supervisory connections at fire-pump power failure including a dead-phase or phase reversal condition.

11. Supervisory connections at fire-pump engine control panel.

 

Ø  Installation of Components:

·       The devices/peripherals (Smoke detectors, heat detectors, break glass, duct detectors, beam detectors, control and monitoring modules) are connected in Class A circuit with the Control panels.

·       The speakers & speaker with strobes are connected in Class A circuit with the Control panels.

·       2 Core 1.5sqmm cable to be used for cabling the Initiating Device Circuits (IDC) or Signaling Line Circuits (SLC) to the panel, additional 2c x 2.5sqmm cable is required for the smoke detector with sounder base for the activation of the sounders units.

·       2 core 1.5sqmm cable to be used for cabling the Speakers with the panel, additional 2c x 2.5sqmm  cable is required from the FACP for the speaker with strobe for the activation of the strobe unit allied in vertical walls the run of conduit will be kept straight.

·       Comply with NFPA 72 for installation of fire-alarm equipment.

 

Ø  FIRE ALARM CONTROL PANEL

·       Install the semi-recessed Back box provided at the location as per the approved shop drawings.

·       Power supply for the FACP shall be through an un-switched SPUR outlet located above the FACP concealed above false ceiling. The un-switched SPUR switch shall be a separate branch circuit.

·       The back box must be dust free and clean before dropping all the field cables inside the back box.

·       Fire Alarm Control Units and Remote Annunciators - Display and/or operating controls shall not be more than 72” (1830 mm) above the finished floor level.

 

Ø  MANUAL CALL POINT

·       Install the recessed recommended back box at the locations as per the approved shop drawings.

·       The manual call point should be installed at a height of 1.3 to 1.5m from its bottom to the ground.

·       Install and terminate the Manual call point as per the manufacturer instructions.

 

Ø  CONTROL & MONITOR MODULES

·       Water-Flow Detectors and Valve Supervisory Switches: Located near each sprinkler valve station and / or water flow detector that is required to be supervised. The module shall be mounted inside recommended 2” x 4” back box and wired to the sprinkler valve station and / or water flow detector via GI flexible conduit.

·       AHUS’, FAHU’S, Lifts, Access Controlled Doors, Public Address System etc.. Which is required to be controlled in case of a fire situation, the Control module shall be mounted inside recommended 4” x 4” back box and wired to the equipment to be interfaced.

·       Module units now will need to be installed between 1.5 feet and 5.5 feet above the finished floor.

·       Install and terminate the Monitor and Control modules as per the manufacturer instructions.

 

Ø  SMOKE & HEAT DETECTORS

·       Comply with NFPA 72, “Smoke-Sensing Fire Detectors” & “Heat-Sensing Fire Detectors”.

·       Smooth ceiling spacing shall not exceed 30 feet (9 m).

·       Ceiling-Mounted Smoke and Heat Detectors: No less than 100mm from a sidewall to the near edge. For exposed solid-joint construction, mount detectors on the bottom of joists. On smooth ceilings, install Smoke detectors not more than 9m apart in any direction and Heat detector not more than 7m apart.

·       Install and terminate the Detector as per the manufacturer instructions.

 

Ø  SOUNDERS & SOUNDER/FLASHER

·       Install the recessed recommended 4” x 4” back box at the locations as per the approved shop drawings.

·       A standard sounder should be mounted 1.8m above the floor.

·       Install and terminate the Sounders as per the manufacturer instructions.

Ø  Faults Finding For Emergency Battery System:

 

Battery Charger Faults:

·       Battery Charger Faults that can arise during the operational lifetime of a panel. You may observe one of the following Faults; Charger 2% out of range Battery Charger Supply incorrect to correctly measure the output voltage you will need to follow the steps below:

1.     To prevent damage to the system, disconnect the batteries & power down the system, disconnect the power & harnesses from the Power Supply.

2.     Connect the Multi-meter to the battery leads (with batteries disconnected), power up & measure the voltage.

3.     Calculate the difference between the measured voltage & 27.6v.

 

Positive/Negative Earth Ground Faults:

·       Fire Panels have the ability to detect positive or negative Earth Ground Faults. An Earth Ground Fault occurs when an electrical circuit is shorted to ground.

 

Ø  Installation of Wires:

·       Install cables in raceways and cable trays except within consoles, back boxes, desks, and counters. Conceal raceway and cables except in unfinished spaces.

·       Using CAT-6A type cable the maximum length of the cable not exceeds more than 90 mtrs. Of manufacturer recommendation, which will provided from structural cabling system supplier.

·       Comply with requirements for raceways and boxes specified in Division 26 Section "Raceways, Boxes, Cable Tray, Cable Ladder and Trunking".

·       Conceal conductors and cables in accessible ceilings, walls, and floors where possible.

 

Ø  Wiring within Enclosures:

·       Bundle, lace, and train cables within enclosures.

·       Connect to terminal points with no excess and without exceeding manufacturer's limitations on bending radius.

 

Ø  Grounding:

·       Comply with requirements in "Grounding and Bonding for Electrical Systems." for grounding conductors and connectors.

·       Bond metallic equipment to the system grounding bus bar, using not smaller than the specified equipment grounding conductor by local Electricity Wiring Regulations, Sections.

 

Ø  Identification:

·       Identify system components, wiring, and cabling complying with local Electricity Wiring Regulations or with consultant or with certified experts.

 

Ø  Programming

·       After making sure all the system installed in correct way from Subcontractor and supplier, programming of the system must take place before final testing and commissioning according to Consultant requirement and scenario of the system.

·       Commissioning must be implemented through certified or experienced person within your team or external body.

·       Testing and commissioning of the system submitted separetly for this system mentioned all the procedure of Testing of the system and commissioning it.

 

Ø  Technical Assistance:

·       The installation supervising technician for the system trade shall instruct the CONSULTANT Engineer, and Construction Site Manager on the programming and correct operation of the system after the installation is completed.

·       This instruction shall be scheduled at the convenience of the staff.

·       All such instruction shall be properly recorded.

·       WIR will be issued for Consultant approval upon making sure that the installation of the system equipment’s done as per approved shop drawings approved specs and manufacturer recommendations.

6. RESPONSIBILITIES

Ø  PROJECT MANAGER

1.     To ensure that all the preparation and application works are carried out according to the Contract Specification and with the approved drawings.

2.     To ensure that the progressing of works is carried out according to the planned program and as per the approved method of statement.

3.     To ensure that all the equipment and material required executing the work are available according to the planned construction program.

4.     To co-ordinate with the Main contractor, MEP coordinator, Safety Officer for a safe and proper execution of the works.

Ø  SITE ENGINEER

1.     To ensure that the works are carried out according to the Contract Specification, approved method statement and the shop drawings.

2.     To provide all necessary information and distribute responsibilities to his construction.

3.     To monitor the progress of work in relation with the work program and to report to the Project Manager.

4.     To co-ordinate with the safety officer and to ensure that the works are carried out in safe practicing method.

Ø  FOREMAN

1.     The foreman will carry out his duties by maintaining continuous coordination with the site engineer on daily basis, and ensure proper distribution of the work force on the required and planned locations.

2.     To ensure that his assistant foreman/ charge hand are aware of the job requirements and they have enough information to carry out their duties properly.

3.     To ensure that the daily work is progressing as planned and advice the site engineer of any requirement for additional resources.

4.     To ensure in consultation with the site engineer that the manpower involved in the works are moving as agreed and planned for the work.

5.     To control disposal of waste materials according to the instructions received from the site engineer.

6.     To ensure full coordination with the safety officer to maintain safe working and proper house keeping of the site, following the proved safety measures and further ensure that all his working team are aware of the same to prevent accident and losses.

7.     To inform the site engineer regarding areas ready for inspection.

8.     Foreman and the storekeeper are responsible for the distribution and control of materials.

Ø  SAFETY ENGINEER

1.     Ensure the implementation of all the safety measures in accordance with the HSE plan and everybody aware of it for it’s proper implementation.

2.     Ensure all the implemented safety measures are adequate to maintain safe working on the site.

3.     Inspect all the site activities and train the person to prevent accidents and it’s proper implementation.

4.     Ensure that the site is maintained clean and tidy.

Ø  TECHNICIAN FROM SUPPILER

1.     The carrying-out of work and the proper distribution of all the available resources in coordination with the sub-contractor Site Engineer on a daily basis.

2.     Daily reports of the works are achieved and coordinated for the future planning with the Site Engineer.

3.     Complying with the sub-contractor basic design practices, particularly those related to safety and engineering

4.     Meeting with any type of unforeseen incident or requirement and reporting the same to the Site Engineer immediately.

Ø  STORE KEEPER

1.     Responsible for overall Store operations in making sure to store the material delivery to the site and keep it in suitable area that will keep the material in safe from rusty and damage.

2.     One who will acknowledge the receiving of materials at site in coordination with QA/QC and concerned Engineer.

7. MANPOWER REQUIRED

Ø  Charge hand and Experienced Technicians. Commissioning Engineer must be certified or at list 10year experienced on same system. NFPA certified person give you extra mileage. 

8. MATERIALS REQUIREMENTS

Ø  FAS  Components  and  Accessories. Check MOQ / BOQ / Engineer BOQ to verify FAS componants UL FM EN54 approved.

9. EQUIPMENTS REQUIREMENTS

Ø  The Equipment that will be engaged for Fire Alarm System Installation will be as follows:

1.     Power source

2.     Drilling machine

3.     Tool Box

4.     Measuring Tape

5.     Calibrated Ohm Meter / Multi meter

6.     Ladders / Scaffoldings

7.     Hammer

8.     Safety requirements tools such as safety shoes, safety helmet, safety glasses, fluorescent vest, and safety gloves to ensure maximum ability of safe work and dust mask when required.

 

10. WASTE MANAGEMENT

Ø  The Rubbish which would be created from our scope of works will be disposed to the designated dumping ground.

11. SPECIAL CONTROL MEASURES

Ø  The following general control measures against Safety, Environment and Quality shall be required for our scope of work and special control measures are not applicable for us :

·         Proper PPE must be worn at all time

·         Permit to work at height > 2m where applicable

·         Lifting operation permit (using crane) where applicable.

·         Confined space permit where applicable.

·         Approved work method statement and risk assessment will be made available to site.

·         All workers doing the work shall be briefed on this method statement and risk assessment.

12. SUPPORTING  DOCUMENTATION

Ø  This method Statement should be read in conjunction with the below referenced documentations:

  • ITP for Anti – termite Treatment.
  • Insulation Resistance and continuity Test Report.

13. DISTRIBUTION

Ø  Copy of this method statement shall be issued to the following for information/ action/ comments:

  1. Project Manager
  2. Site Engineer
  3. Foremen
  4. Safety Engineer
  5. Technician From Supplier
  6. Store Keeper