Wednesday, April 1, 2026

Diluting NBC Part IV-good or bad

Diluting NBC Part IV-good or bad

The National Building Code (NBC) of India is the country’s foundational safety framework for all buildings. It integrates structural design, fire and life safety, building services, environmental performance, and accessibility. Because it is based on scientific research, disaster lessons, and professional consensus, any dilution of the NBC raises a serious concern for public safety and long-term societal risk.

However, recent discussions in policy and regulatory circles suggest that there may be a move to significantly modify NBC Part IV or convert it into a simplified handbook-style document, largely under the broader objective of improving the country's Ease of Doing Business.

India is witnessing one of the fastest urban transformations in the world. High-rise residential towers, mega hospitals, airports, shopping complexes, data centres, and industrial facilities are rapidly shaping the country’s built environment. As buildings grow taller, denser, and more complex, the importance of fire and life safety regulations becomes more critical than ever before.

The first and most critical impact is on structural safety. NBC provisions, aligned with IS codes for loads, concrete, steel, seismic actions, and ductile detailing, ensure buildings can withstand both everyday usage and extreme events. Even a minor relaxation in material quality, detailing, or load assumptions can significantly increase the probability of structural distress or collapse, especially in seismically active or cyclone-prone regions. With growing urban density, such risks magnify, affecting thousands of occupants at once.

This raises a fundamental question that the entire built-environment community must carefully examine:

When most nations strengthen their fire safety regulations after every major fire incident, why should India consider weakening its own fire safety framework?

Fire safety regulations are not administrative obstacles. They are life-saving systems embedded in building design. Every provision—from staircase width to smoke extraction—exists to protect human life during emergencies.

Diluting these provisions in the name of convenience or economic efficiency could have serious consequences for public safety.

The role of Karnataka’s civil engineers

The warning raised by Karnataka’s civil engineers on the dilution of the National Building Code (NBC) deserves serious and immediate attention.‼️

The NBC is not a procedural formality—it is the backbone of structural safety, fire protection, accessibility, sustainability, and disaster resilience. Any dilution, whether in the name of ease of construction or short-term economic considerations, directly compromises public safety and long-term urban resilience.

As India moves towards the vision of Viksit Bharat 2047, growth cannot come at the cost of engineering ethics, scientific rigor, and hard-earned lessons from past failures. Weakening codal provisions risks creating unsafe buildings, increased lifecycle costs, and irreversible damage to public trust.

It is imperative that policymakers engage deeply with practicing engineers, academicians, and professional bodies before implementing amendments. Codes must evolve, but only through evidence-based research, field experience, and a commitment to safeguarding human life.

Why the Potential Dilution is Considered Bad (Risks)

·        Endangering Public Safety: NBC Part IV sets strict standards for fire resistance, evacuation (staircases, exits), and refuge areas in high-rise buildings. Diluting these can lead to fatal disasters.

·        "Ease of Doing Business" Pressure: Experts argue that the push to weaken the code is driven by developer interests looking to cut costs and accelerate construction, rather than prioritizing safety.

·        Undermining Expert Standards: The NBC is a comprehensive document developed over 65+ years by experts. Critics believe changes driven by non-engineering lobbies threaten to undermine this legacy.

·        Structural Failure Risk: Weakening the code risks increasing the likelihood of fire spreading due to poor compartmentation (the division of buildings into fire-resistant sections). 

Fire Safety Codes Across the World:

Across the world, governments treat fire safety as a national responsibility that cannot be compromised. Most developed nations operate with clear, unified and enforceable fire safety codes that apply across the country.

For example:

• The United States follows the NFPA (National Fire Protection Association) codes and standards.

• The United Kingdom enforces strict fire safety regulations under its Building Regulations and Fire Safety Order.

• Australia’s National Construction Code integrates comprehensive fire safety provisions.

• The International Fire Code (IFC) provides globally recognised fire safety guidelines.

Whenever catastrophic fires occur, governments in these countries respond by strengthening regulations, increasing inspections, and improving enforcement mechanisms.

After incidents such as:

• The Grenfell Tower fire in London,

• The Station Nightclub fire in the United States,

• Major high-rise fires in Dubai,

Regulatory authorities moved quickly to tighten safety provisions, improve building compliance systems, and increase professional accountability.

The global philosophy is clear:

Fire safety regulations are designed to save lives and must never be weakened for convenience.

The Misinterpretation of “Ease of Doing Business”

Cabinet Deregulation cell proposals to Dilute NBC results in huge Energy consumption & increases carbon footprints in buildings become unsustainable. People suffer from health issues & medical expenses increase exponentially.

India’s efforts to improve the Ease of Doing Business have played an important role in simplifying procedures, reducing delays, and encouraging investment.

However, the concept of ease of doing business must not be misunderstood as a justification for weakening essential safety regulations.

In certain sections of the construction industry, there is a perception that fire safety provisions:

• Increase construction costs

• Require additional building space

• Add complexity to approval processes

While these concerns may arise from project feasibility considerations, they must be examined carefully.

Fire safety requirements such as refuge areas, fire stairs, fire compartmentation, smoke extraction systems, and fire command centres are not optional features. They are the result of decades of global learning from fire tragedies.

Removing or weakening such provisions may reduce construction costs in the short term, but it could dramatically increase the risk to human life.

Safety cannot be compromised in the pursuit of convenience.

India’s Real Challenge: Implementation

The real challenge India faces today is not the strength of the regulations but the effectiveness of implementation.

Across the country, many urban local bodies responsible for building approvals often lack:

• Adequate fire engineering expertise

• Proper training in NBC provisions

• Dedicated systems to verify fire safety compliance

As a result, the same provisions are interpreted differently across jurisdictions, leading to inconsistencies in enforcement.

The solution to this challenge is not to dilute the code, but to strengthen the ecosystem responsible for implementing it.

India must focus on:

• Capacity building for approval authorities

• Training municipal engineers in fire safety design

• Establishing uniform compliance mechanisms

• Integrating digital approval systems with fire safety checks

• Strengthening third-party fire safety audits

Improving implementation will enhance both efficiency and safety, without weakening regulatory safeguards.

Under the Constitution of India, Fire Services fall under the State List and therefore legislation and enforcement are primarily the responsibility of individual State Governments. The National Building Code (Hereafter it will be renamed as National Build Standard) indeed serves as a model framework and its implementation depends on state adoption through local Acts, Rules, and municipal by-laws.

However, the concern being raised by many professionals today is the growing inconsistency in safety requirements across states, particularly in the built environment. When buildings, technologies, and risks are becoming increasingly uniform across the country, the safety expectations of citizens should ideally not vary significantly from one state to another.

The intent behind advocating “One Nation – One Safety Rule” is not to dilute the constitutional role of the States, but to encourage a stronger national consensus on minimum fire and life safety standards, supported by technical bodies, professional institutions, and regulators. Just as the NBC acts as a model code, a coordinated national framework with broader adoption could significantly improve consistency in implementation and enforcement.

The Risk of Converting a Code into a Handbook

There is also discussion in certain circles about converting NBC Part IV into a handbook or advisory document.

While the intention may be to simplify interpretation, such a move carries significant risks.

A Code is mandatory and enforceable. A Handbook is advisory and interpretative. Codes form the basis for legal compliance and building approvals, whereas handbooks provide guidance but cannot enforce safety obligations.

If a critical section such as Fire and Life Safety is reduced to a guidance document, compliance could become subjective rather than mandatory.

For a country constructing thousands of high-rise buildings every year, such ambiguity would be dangerous.

India needs clear, enforceable safety regulations, not optional guidelines.

The Way Forward for India

India’s rapid urbanization requires stronger safety frameworks, not weaker ones.

The country must focus on:

• Strengthening NBC implementation

• Training municipal authorities

• Promoting professional accountability

• Encouraging multidisciplinary collaboration

• Enhancing awareness among building owners and citizens

Fire safety must remain a non-negotiable pillar of national development. For NBC it says Central Govt doesn’t have authority over land & buildings & proposed to dilute it by removing parts 0, 1, & 3, etc . But here it comes out with new proposals on same land & buildings. Dilution of NBC provisions such as 100% coverage, unlimited FAR, any height & setbacks, etc will lead to Health, Fire & other Engg safety disasters. Cabinet Secretariat proposals are un-sustainable & damage the built environment. of public & private safety.

One Country-One Constitution, one country-one Tax, one country-one grid, one country-one card, one country one PM, why not One country-One Code (NATIONAL BUILDING CODE) Since 1970 it is guiding construction. Approx 1.25 cr Cost involved, all Engineers request govt not to dilute it. 

Please Stop Dilution of NBC.


Tuesday, April 1, 2025

Open Protocol & Closed Protocol under Fire Alarms

Open Protocol & Closed Protocol under Fire Alarms 

Thanks to all of my viewr to promote me and thanks for nice name is given to me as "Fire Ka Doctor". Below Article is quite different then others. In fire industry verious miscommunication / mishandling / wrong concept is going on. This open protocol & Close protocol is one of them. Yes after reading this article set your mindset and ask your perchaser. Dont beleave blindly any OEM or nominated persons. 

We are often asked about “Open Protocol” or “Open Architecture” systems or “Closed Protocol” or “proprietary”. Although this is quite a technical question, it is one of the fundamental issues to be addressed when specifying a fire detection and alarm system. Fire alarm industry creates a misunderstanding of what an Open Protocol System or Closed. 

·        Some of OEM said we have Over 1000 of Distribution globally and we believe Open protocol business strategy.

·        Another OEM said our Fire alarm product is Open Protocol, it is unlocked, and any third-party company is then available to maintain the system.

·        We are believing one of best open protocol product we supply globally that any one can do programming commissioning from our panel Keypad. All manuals are easily available in online search engines. No need training no software not mandatory.

·        We have Open Protocol Interfaces such as BACNet, Modbus and OPC Server, that can be easily handshake with any Third Party system.

Lots of OEM is there globally, each and every one is correct in terms of their “strategy – thinking”. These terms primarily relate to fire alarm systems' communication and compatibility aspects.

All fire detection and alarm systems are technically similar. In very simple terms, they consist of numerous fire detection devices, including smoke detectors and “break glass” call points for example, which are connected to a central control panel. When a smoke detector detects smoke, it informs the control panel, which then turns on circuits of alarm sounders. Smoke detector operates, alarm sounders ring. (if you want to be really simple about it!). The connection between the detection devices, alarm sounders and the control panel is either cabling or wireless. For simplicity, we will focus on systems where the devices are connected to the control panel by cabling, commonly called in the industry a “hard wired” system.

What is a Protocol?

Each component uses a particular protocol, which is essentially the language that electronic products use to communicate with each other. So a protocol is a fire alarm system's language for communicating between loop devices. 

There are two types of protocol for fire systems: open or closed.

BS EN 54-13-2017 stated

“The components forming a FDAS are designed to provide a system with a particular aspect of its overall functionality. Only when all the components are connected together is the system likely to perform in the desired manner and then only if the components intercommunicate effectively.

For the purposes of this document, the CIE is the focal point of the system and all other components are required to communicate effectively with the CIE. Communication requires the consideration of communication protocols along with other aspects such as power supply requirements and data transmission characteristics.

A separate voice alarm system can be assessed for compatibility and connectability independently of the fire detection and alarm system.”

In general you can say Open Protocol fire alarm is Conventional type & Close protocol Fire Alarm is Addressable type or Intelligent type.

Open Protocol Fire Alarm System

In an Open Protocol System, the panel and devices manufactured by different companies – as long as they are compatible. Open Protocol System designed to be more flexible and open to communication with a wider range of devices and components. This flexibility can make it easier to expand, upgrade, and maintain the fire alarm system, as components from various manufacturers can be integrated into the system more easily. Open protocol systems often offer more choices and competitive pricing for replacement parts and devices.

A conventional system employs one or more initiating circuits called zone’s, connected to sensors (initiating devices) wired in parallel. These sensors are devised to decrease the circuits resistance when the environmental influence on any sensor exceeds a predetermined threshold. No programming needs to be done, just plug & Play. The conventional fire panel range comes in 2, 4 or 8 zones or more versions.

NFPA 72 Standard says

1) Each zone has a maximum area of 2000 square meters.

2) The maximum length of each zone is 3000 meters.

3) The maximum number of elements in each zone (including fire alarms, sirens, mcp, detectors, etc.) is 24, and it is better to have a maximum of 20 elements.

4) Each residential floor can be placed in one zone.

5) It is suggested that each escape staircase should be included in a zone and a fire alarm should be installed on the escape route.

6) False ceilings and ceilings with a height of more than 80 cm need a detector.

7) If the partition distance is less than 30 cm, the detector is considered separate.

8) If the height of the ceiling is more than 50 cm, a separate detector is considered for each space.

9) The maximum coverage area for the smoke detector is 100 square meters and for the heat detector is 60 square meters.

10) The maximum height of the detector is 12 meters for the detector and 8 meters for the thermal detector.

The Gent 3260 is a conventional fire alarm system support up to 32 devices per zone.

Ravel Conventional panel can support 28nos elements/detectors in each zone if Ravel brand conventional elements, It supports 20 or 18nos if other then Ravel conventional elements. It depends on Current consumption. Yes it supports other brand elements.

GST conventional Fire panel each zone can be connected with 15 conventional fire detectors in same brand or other brand conventional detectors.

Agni Protection conventional fire panel support Maximum 20 nos. detectors in each zone. If other brand detectors, then also same.

AGNI Devices conventional fire panel support Maximum 25 nos. detectors in each zone. If other brand detectors, then also same.

EATON conventional fire panel support maximum loading is 32 detectors and manual call points per zone,

System Sensor Fire Alarm Control Panel support maximum 600m cable connectivity per zone, typically 20 Detectors per zone+ 5 MCP's. Other brand Detector can be connected with respect to Max 2mA current per Detector Circuit.

Apollo conventional ranges including Series 65, Orbis and Series 65A support any brand Conventional Fire Panel. Any series cover 10-year warranty policy. Apollo Fire Detectors Limited is a Halma Company.

In case of Addressable or Intelligent system, only apollo brand field elements (including modules, Strobe, MCP, detectors, etc. Apollo is manufactures smoke detectors, call points, VADs, and more recently, pull stations and magnetic door holders.) are compatible with

1.   Mtech Fire Detection Systems Ltd

2.   Labor Strauss Sicherungsanlagenbau GmbH (LST)

3.   NIBBLE - Engenharia Lda

4.   Ampac Europe Limited

5.   Safetec SRL

6.   Paradox Hellas (SmartX)

7.   Haes Technologies Ltd (Esprit)

8.   Kentec Electronics Ltd (Syncro, Taktis)

9.   NSC Sicherheitstechnik GmbH

10.Teledata SRL

11.VES LLC

12.C-TEC  (Apollo & Hochiki)

13.Advanced Electronics Ltd (MxPro)

So there are two different OEM involve in Fire Detection & Alarm system. You can Design for small to Enterprise customers, in any sector. Apollo products are certified in a global arena to meet the highest standards set by both our customers and the dynamic and challenging environments in which they operate. We meet global type approval standards including EN, UL, CCC as well as specific approvals for specialist or extreme applications such as Marine or explosive environments. The compliance to these standards can be denoted by a third-party marking on the product including LPCB, VdS, BOSEC and AFNOR.

You able to add any of above brand Fire Panel for your design, free to select as per your customers / end users need. Apollo is single brand who offer open protocol field element compatible with lots of Fire alarm control Panel.

Advantages of Open Protocol

·        Offers the building owner more freedom when it comes to sourcing products or an installation company as there is the ability to choose between numerous compatible manufacturers.

·        Allows the installer to choose whichever products are suitable for the project.

·        The building owner is able to choose whichever company they want for ongoing maintenance or adding to the system, enabling them to shop around for the best price

·        When innovative products are released, and the building owner would prefer this solution to protect their building (like our flush mounted Soteria Dimension) having an open protocol system makes it easier to change manufacturer. Meaning they have more flexibility to choose the solution they want, not the ones they are tied into.

·        open protocol systems can sometimes offer more competitive pricing and long-term cost savings.

·        Different manufacturers for panels & devices – when things do go wrong, more than one company may have to be involved to find a solution, software, etc.

Disadvantages of Open Protocol:

·        No training required, so no proof of competence. Installer, Customers need to find out actual competent person who can make healthy system.

·        Easy access to software can lead to untrained engineers working on systems. No license / Dongle is required.

·        open protocol systems offer flexibility but may require careful selection and integration of components to ensure seamless operation.

Closed Protocol Fire Alarm System

With a Closed Protocol system a single manufacturer produces a range of devices AND control panels that all utilise its own specific protocol. This manufacturer does not provide general access to the technical details of its protocol and restricts the use of it to trained approved installation companies only. The equipment produced will not be compatible with devices from different manufacturers of closed protocol fire systems. Once you choose one closed protocol you are, in effect, locked into one company for the manufacture, supply and maintenance (and in some instances the installation) of the complete system. which can lead to higher costs and potential limitations in system flexibility.

Conventional system with close protocol is not possible, due to conventional system is plug & play. On the other hand analog addressable or intelligent addressable system is with close protocol.

Close Protocol Communicate with Same Brand Field Element & Fire Panel Only

Fire Brand Name

Main Company

Protocol Name

Compatible Panel

 

Remarks

Notifier

Honeywell

Flashscan
Clip

NFS 320
NFS2 640E
NFS2 3030
N16e

UL & FM

Detector, Devices can be program through auto program Panel
Integrated Digital Voice program via license Software (VeriFire tools) only.
License software open for Distributor Trained Person Only.

ESSER

Honeywell

Profi BUS
EDP

ESSER 8xxx
IQ8
FlexES

EN54, Vds, BOSEC, Ex, CCC, CNBOP, AFNOR & DIBt

Programming through Tools8000 software only.
License software open for Distributor Trained Person Only.

Farenhyt

Honeywell

IDP

IFP-2100ECS (RED)
IFP-2100
IFP-300
IFP-75

UL

Auto Programming through Fire Panel.
License software HFSS is open for Distributor Trained Person Only.
System is partly open with Apollo & Hochiki Field element.

Silent Knight & Farenhyt

Honeywell

IDP

IFP-2000
IFP-1000
IFP-100
IFP-50

UL

Auto Programming through Fire Panel.
License software HFSS is open for Distributor Trained Person Only.
System is partly open with Apollo & Hochiki Field element.

Silent Knigh

Honeywell

IDP

6820 EVS
6700
6808
6820

UL & FM

Auto Programming through Fire Panel.
License software SKSS2 & and the SKST selection tool is open for Distributor Trained Person Only.
6700 Honeywell will provide product support until October 2029

FireLite

Honeywell

CLIP

ES-1000XC
ES-200X
ES-1000X
ES-50XP
ES-50X
ES-200XP

UL

Auto Programming through Fire Panel.
Panel programming via a USB drive

Gamewell-FCI

Honeywell

Velocity protocol

GWF-7075
SLP-S3

UL & OSHPD (CA)

Auto Programming through Fire Panel.
Panel programming via license CamWorks software open for Distributor trained person only

GENT

Honeywell

 

COMPACT-PLUS
VIGPLUS-24
VIGPLUS-72
NANO-24

EN54

Commision Tool Gent, VigInSite Tool, Loop Diagnostic Tool & NanoTool are license-based software is open for Distributor Trained Person Only.

MORLEY IAS

Honeywell

CLIP

DxC
ZXSe
PL 1000
LT-159

MA-2000

MA-8000

EN54 & LPCB

Auto Programming through Fire Panel.
Panel programming via software open for trained person only

Simplex

JCI

IDNet or MAPNET II

4100ES
4007ES
4010ES

UL

License Based ES Programmer Software is for programming, only for distributor trained person.

FireClass

JCI

 

FC 700
FC 600
FC 500

 

Hand-held programmer is required for Detector / Devices Programming.
Panel programming via software open for trained person only

ZETTLER

JCI

 

PROFILE

UL

Hand-held programmer is required for Detector / Devices Programming.
Panel programming via software open for trained person only

PROTEC

PROTEC

Algo-Te 6000PLUS

6100
6500
VIGPLUS-72
NANO-24

EN54

Protec X600 for panels / Commisioning tool for protec 6100 Full licensed software availlable with distributor trained person only.

EATON / COOPER

EATON

 

CF1000
CF1200
CF3000

EN54 & Vds

Auto Programming through Fire Panel.
License software Site Installer is open for Trained Person Only

EDWARDS

Carrier

SIGA

iO 64
iO 1000
EST3
EST3X
EST4

UL & FM

Programming through License software (IO-CU, 3-SDU, 4-CU) only.
License software open for End User, Distributor, System Integrator Trained Person Only.

GST

Carrier

 

GST100
GST200N
IFP8
IFP4E

EN54 & LPCB

Hand-held programmer is required for Detector / Devices Programming.
Panel programming via software is open download.

Kidde

Carrier

 

VM series
VS Series

 

VMS CU License is required for Detector / Devices Programming.
Panel programming via software is open for trained Person Only

BOSCH

BOSCH

LSN

FPA 1000
FPA 2000
FPA 8000

EN54 & Vds

Programming through License software (FSP 5000 RPS) only.
License software open for Distributor, System Integrator Trained Person Only.

Advantages of Closed Protocol

·        Because each and every device in the system, including the control panel, is provided by the one manufacturer there is a common design and production plan, meaning compatibility is assured.

·        When individual devices do need upgrading they are tested alongside the rest of the manufacturer’s product range to ensure the system’s compatibility before the new products are brought to market.

·        System failure due to unauthorised tampering is reduced as access to the system is restricted by the manufacturer to approved installation and maintenance companies.

Disadvantages of Closed Protocol:

·        Upgrades to the system could be restricted to the technology currently available from the chosen manufacturer/supplier, potentially affecting your choice of brand new or innovative solutions available elsewhere in the marketplace.

·        Closed protocol manufacturers can lack competition for maintenance services and this can encourage lapse service, slow call-out responses and expensive maintenance contracts which are impossible to get out of

·        As a building owner you are wholly dependent on one manufacturer for access to new equipment, upgrades, spares and maintenance. Without direct competition this tends to allow manufacturers to charge you a premium rate for these services.

·        If you do decide to upgrade or change the system, it can be an expensive and disruptive exercise as the majority of the original supplier’s system would have to be removed from the premises and replaced. In some circumstances, this might involve multiple risk assessments and a complicated series of temporary closures of the building to the public and staff for the duration of some of the work (to comply with local legislation).

·        There is a complete dependency on one manufacturer for spare parts, and access to the protocol for servicing, modification, and upgrades. All of this may put a premium on ongoing maintenance.

·        Some of well-known OEM directly stated to End user that, do purchased from only our authorised distributor and commissioning through them only, otherwise we not able to provide warranty support. Some of them told if you commissioned system through another agency then you will not get any warranty support in case any product not in working condition.

Making the right choice

The question you need to ask yourself and your installer at this point is “What is the best investment option for me and my building, considering the whole lifetime of the fire detection system”. This “whole lifetime” investment is sometimes referred to as the Total Cost of Ownership (TCO) and is an important long-term consideration.

If you decide to choose a fire detection system provided by a Closed Protocol manufacturer you will have access to devices and panels specifically designed to operate together with complete compatibility. This solution will then be installed and maintained by an approved supplier who has been trained in that specific system.

You need to be aware of some potential issues here, for example

·        Does the manufacturer have a strict upgrade policy restricting you to one upgrade per year or 5 year.

·        Do they guarantee complete backwards compatibility for their new products or will you be forced to replace some other components that don’t quite fit with the new devices? Without upgrading Firmware Versions. Some of Well known OEM discontinued old detector series and immediate effect new detector series, not End user mandatory to upgrade firmware on chargeable basis, otherwise new detector & old detector can not work jointly under loops.

·        Are there other solutions on the market that despite being more cost-effective cannot be utilised as they are not part of the manufacturer’s system offering?

·        Check there product commissioning process, does need license / dongle for every addition or deletion or modification. If yes then how many certified or non-certified technical person there in market ?

·        Do the market survey – take suggestion from experienced field person.

Potentially you might be tied-in to a lengthy maintenance contract so consider whether the manufacturer has a good reputation within the industry for the provision of equipment and services.

Opting to choose an Open Protocol system allows you and your installation company the freedom to make decisions about the precise equipment needed based upon the exact requirements of the building rather than being restricted to one manufacturer’s product range. Make sure your chosen installation company has the experience and expertise in many different manufacturer’s product ranges so that you can be sure they will offer accurate and impartial advice on the system design. It is also recommended that you check their fire industry accreditations such as BAFE or LPS1014.

Choosing the correct fire detection protocol system is dependent upon circumstance. Open protocols offer a greater degree of freedom, choice and long term value for money; however if cost is not a primary concern you may prefer the closed protocol system which can offer a straightforward alternative.

Open Protocol Systems - An Explanation. Generally Open Protocol systems allow fire detection equipment and control panels to be compatible between a greater selection of manufacturers, offering you more freedom of choice when sourcing products and installation companies.

Bearing in mind the TCO as mentioned previously, it is always important to understand the levels and restrictions of your fire alarm system maintenance contract, regardless of who is supplying or installing. You need to be able to calculate upfront the expected costs of future maintenance to properly evaluate the TCO of the intended system.

Reference:

·        https://www.chrislewis.co.uk/blog/fire/open-v-closed-protocol-fire-systems

·        https://www.apollo-fire.co.uk/products/system-types/communication-protocol/

·        https://blazequel.com/blog/open-protocol-vs-closed-protocol-fire-alarms/#:~:text=Open%20protocol%20systems%20are%20generally,features%20and%20technology%20are%20preferred.

·        http://firealarmengineers.com/forum/showthread.php?tid=2665&pid=17208

·        https://www.hochikieurope.com/whitepapers/Open-Closed-Protocols.pdf