Like your monthly inspections, these
inspections must follow the manufacturer’s guidelines. However, they are much
more comprehensive and detailed in nature and as such, require more time and
expertise than monthly inspections do. At minimum, these inspections require
the following:
❏ An evaluation
of your system from a hazard perspective – Has the hazard changed in any way
that might make the system less effective?
❏ An
examination of every component of your system – This includes your fire
detectors, the containers that hold the extinguishing agent, your system’s
releasing devices, piping, hose assemblies, nozzles, and signals as well as any
auxiliary equipment.
❏ A check of
the agent distribution piping throughout your system – are there any
obstructions that might prevent the release and/or proper flow of extinguishing
agent?
❏ An
examination of the wet chemical in your system – If there is any evidence of
corrosion or pitting or structural damage to the cylinders, the chemical may
not feed properly through your distribution system and should be replaced and
the system recharged.
ITEM |
ACTIVITY |
FREQUENCY |
NFPA REF |
Extinguishing
system nozzles are located directly above grease producing equipment |
Inspection |
Monthly |
17A:7.2.2 |
17:11.2.1.1 |
|||
The Manual
actuators are unobstructed |
Inspection |
Monthly |
17A:7.2.2, |
17:11.2.1.1 |
|||
The tamper
indicator’s and seals are intact |
Inspection |
Monthly |
17A:7.2.2 |
17:11.2.1.1 |
|||
The
maintenance tag or certificate in place |
Inspection |
Monthly |
17A:7.2.2 |
17:11.2.1.1 |
|||
No obvious
physical damage or condition exists that might prevent operation |
Inspection |
Monthly |
17A:7.2.2 |
17:11.2.1.1 |
|||
The pressure
gauge(s) are in operable range. |
Inspection |
Monthly |
17A:7.2.2 |
17:11.2.1.1 |
|||
The nozzle
blow-off caps are intact and
undamaged. |
Inspection |
Monthly |
17A:7.2.2 |
17:11.2.1.1 |
|||
Neither
protected equipment nor hazard has been replaced, modified, or relocated |
Inspection |
Monthly |
17:11.2.1.1 |
17A: 7.2.2 |
|||
Gas and
electric power shutoff are operational |
Test |
Semiannually |
17:11.3.1.4 |
Water-wash
hood cleaning systems are operational in conjunction with hoods protected by sprinkler systems |
Test |
Semiannually |
96:11.2.1 |
Remove grease
from exhaust system |
Maintenance |
Quarterly/ Semiannually |
96 :11.3, |
96 :11.4, |
|||
Recirculating
systems operation and safety interlocks perform in accordance with mfg’s
instructions |
Test |
Every 6 mos
or more frequently |
96:13.6.5 |
Recirculating
systems. Electrostatic Precipitators
cleaned |
Maintenance |
Weekly |
96:13.6.3 |
Recirculating
systems. Clean entire hood Plenum and
blower section. |
Maintenance |
Quarterly |
96:13.6.4 |
Fixed
temperature sensing elements of the fusible alloy type |
Replace |
Annually |
17:11.3.2, |
17A:7.3.3, |
|||
96:8.2.1.2 |
|||
Clean fixed
temperature sensing elements other than the fusible metal alloy type |
Maintenance |
Annually |
17:11.3.3 |
17A:7.3.4 |
|||
Manual
release stations are operational and send a signal to the building fire alarm
control panel. |
Test |
Semiannually |
17:11.3.1.4 |
17A:7.3.2.3 |
|||
Automatic
release devices are operational and send a signal to the building fire alarm
control panel. |
Test |
Semiannually |
17:11.3.1.4 |
17A:7.3.2.3 |
|||
Water flow,
valve tamper, and low water pressure cut-offs are operational |
Test |
Quarterly |
72: Table |
7-2.2 - 13i |
|||
Examine
detectors, expellant gas containers, agent containers, releasing devices,
piping, hose assemblies, nozzles, signals, and all auxiliary equipment |
Maintenance |
Semiannually |
17:11.3.1. |
17A:7.3.2.3 |
|||
Verify that
the agent distribution piping is not obstructed |
Test |
Semiannually |
17:11.3.1 |
17A:3.2.1 |
|||
Examine dry
chemical in stored pressure systems for caking |
Inspection |
Every 6 years |
17:11.3.1 |
Hydrostatic
pressure test on wet and dry chemical extinguishing systems (agent
containers, aux. pressure containers, hose assemblies) |
Test |
Every 12 years |
17:11.5.1 |
17A:7.5.1 |
Ref:
NFPA 17 (latest edition), 17a (latest edition), 72 (latest edition), and NFPA 96 (latest edition).
Thanks for sharing this post. This post clear my doubts, Thanks for sharing.
ReplyDeleteISO 45001 Certification
Amazing blog
ReplyDeleteI was looking for part-time or Flexible classes for doing the Nebosh safety course in Chennai. And I finally found this National Safety school, where they offer quality training at our own time. It's was easy to study Safety skills while working as a professional as well.
Thank u for dedicated training sir.
NEBOSH Course in Chennai
Fire and Safety Course in Chennai
IOSH Course in Chennai
Thank you for share this informative article. it was really helpful.
ReplyDeleteHere's another source of fire fighting equipment in Pakistan that provides the same equipment and services.
Your article is such a unique piece of information related to fire protection. Because of increasing number of fire hazards, everyone building owner should install the fire fighting equipment in Pakistan. For installing fire fighting equipment in Pakistan. Visit Fire Fighting Equipment in Pakistan
ReplyDeleteI really like your post. Thanks for sharing such a informative blog. Keep posting and upgrading our knowledge.
ReplyDeleteVacuum Gauge Tester | Laboratory Testing Equipment & Instruments
Hi..
ReplyDeleteI appreciate your Informative post and thanks for sharing.
Vacuum Leak Tester | Bottle Testing Equipment | Bottle Burst Tester
Thanks for this Post.. Eiwaa Group provide our clients with safe operating systems for the Pressure Testing Services of assemblies and components, and remotely controlled test systems allowing hydraulic flushing and testing to be controlled within a safe environment.
ReplyDeleteZone Certification
Eddy Current Testing
Storage Tank Survey
Welder Qualification Test
Awesome Blog! Its very interestingly and informative in reading. This is really a great Stuff for sharing. Keep it up. Thanks for sharing.
ReplyDeleteTesting Instruments
Box Compression Tester
Bursting Strength Tester
Salt Spray Chamber
Vacuum Leak Tester
Cobb Sizing Tester
Melt Flow Index Tester
Muffle Furnace Manufacturer
Tensile Test Machine
Paper GSM Tester
Thanks for sharing this informative post. It's very helpful. Keep it up!
ReplyDeleteSalt Spray Chamber | Box Compression Tester | Bursting Strength Tester Digital | Digital Tensile Testing Machine Cap 2500KG | Wall Thickness Gauge - MagnaMike 8600 | Testing Instruments | GSM Machine
hydrostatic tests
ReplyDeleteCapacitación en petróleo y gas natural - EIES, Cochabamba (Cochabamba, Bolivia). 13,006 likes · 17 talking about this. Escuela Internacional para la.
to get more -Facebook.com/Capacitacion.Petrolera
Hello Dear..
ReplyDeleteI appreciate your Informative post and It's very helpful.Thanks for sharing Keep it up!
Salt Spray Chamber
Bottle Cutting Tester Machine
Bursting Strength Tester Digital
Cobb Sizing Tester
Dart Impact Tester
Digital Gloss Meter
Drop Tester
Edge Crush Tester Digital
Laboratory Testing Instruments Equipment
Paint Plating Testing Instruments
Plastic Bottle Color Measurement
Puncture Resistance Tester
Roofing Color Measurement
Stiffness Tester
Tearing Strength Tester
Tensile Strength Tester Machine Manufacturer
Top Load Tester
Torque Tester
Vibration Table
ReplyDeleteThank you for sharing the valuable content
Foamtech Antifire Company is a leading Fire Fighting Foam Manufacturers Company. And ISO 9001:2015, 14001:2015 & ISO 45001:2018 certified, the company deals in a wide range of products, meeting national and international standards. And also avail Dry Chemcial Powder at best price, With the base of high class Engineering technology and superior quality of work with base of our customer needs.
I have just gone through your blog......your information is so valuable. Thanks for sharing this information. ABS Instruments Pvt. Ltd. is a Thirty Years old company that supplies the best in materials testing equipment from all over the world to our customers in India.High Cycle Fatigue
ReplyDeletevery interesting blog post. Shop for Stone Kitchen Hoods by Southern Stone Crafters LLC.
ReplyDeleteThanx for Sharing, The content is well-written, informative, and engaging.
ReplyDeleteTop Load Tester
Nice blog!
ReplyDeleteAre you searching for a service center in Dubai for your Macbook?? Scorpionfix is here, one of the best Apple service center in Dubai.
Surface pro 8 repair in Sharjah
Surface pro service center Sharjah
Surface pro service center Dubai
Macbook repair in Sharjah
Macbook repair in Dubai.
Laptop repair in Dubai
Laptop repair in Sharjah
Surface pro 8 repair in Dubai
macbook service center abu dhabi
macbook repair abu dhabi
Laptop repair abu dhabi
Laptop service center abu dhabi
Apple service center Sharjah
Discover the best fire safety products and Guardia: Your trusted choice for superior protection. Explore top-rated safety solutions today!
ReplyDeleteExplore a wide range of industrial fire safety products at Ezzi Engineering. Buy top-quality fire safety solutions to safeguard your industrial space. Ensure the protection of your assets with our reliable and advanced products. Shop now for peace of mind
ReplyDeletevisit : https://www.ezziengineering.com
Very significant Information for us, I have think the representation of this Information is actually superb one. This is my first visit to your site. Get more information from Fire Suppression System Inspection.
ReplyDeleteThanks for providing valuable information. if you need hood suppression system to ensures safety of your lives and property in Pakistan, please contact Green Tech Solution. https://greentechsolution.net/
ReplyDeleteI found this blog post quite informative! I know a company called Adnan & Sons that offers high-quality fire safety products; you can visit their website at www.adnansons.com for more information.
ReplyDelete