Why Restaurants Fire Protection Need To Upgrade
On Oct 16, 2021 a fire broke out at a popular restaurant in the southern part of Kolkata during the busy hours on Saturday afternoon, police said. No casualty was reported. Three fire tenders were pressed into service to douse the blaze, which probably started from the kitchen of the Mughlai restaurant at, a police officer said.
Restaurant
or kitchen fires have always been some of the most dangerous because a fire can
begin on a cooking appliance, or in a hood, or ductwork and quickly spread to
involve the entire building. Statistics show that many restaurants never
re-open after a fire. A kitchen fire suppression system is a fire safety
system that prevents fires from travelling from your kitchen area to other
areas in the building.
In
1994, Underwriters Laboratories released "Fire Testing of
Fire Extinguishing Systems for Protection of Restaurant Cooking Areas,"
also known as UL 300. The standard outlines specific guidelines that fire
protection equipment manufacturers must meet for systems to receive a UL 300
label.
Each manufacturer must submit their system to Underwriters Laboratories for testing, which includes real-world fire testing on commercial cooking equipment used in today’s restaurants. Fire suppression systems that meet the UL 300 standard are significantly more effective at controlling kitchen fires than systems designed to meet previous standards.
Most states have adopted NFPA 17A and NFPA 96 as a part of their fire code, requiring all commercial kitchen fire suppression systems to be UL 300 compliant. Additionally, most insurance companies require compliance with this standard as a prerequisite to coverage.
General
Requirements
Egress
For restaurants with an occupant load of 50 or
more, which would classify them as an assembly occupancy, the main entrance
must be sized to be able to accommodate at least one half of the total occupant
load. Other exits must be provided to handle the additional capacity with the
total number being based on layout and maintaining acceptable travel distances.
Sprinkler Protection
Sprinklers have not traditionally been required for
all restaurants. Beginning with the 2021
edition of NFPA 101 Life
Safety Code, restaurants that are assembly occupancies of new construction
will require sprinkler protection. Like fire alarms, a lot of variables can
play into the need for sprinkler protection, including construction type,
height, other uses of the building, and more. Where considering a standalone
building used only as a restaurant its classification as an assembly occupancy
does not require sprinkler protection for any existing construction unless it
can also be considered a nightclub, dance hall, or discotheque in which case
they are required for occupant loads over 100.
Fire Alarm
Whether or not a fire alarm system is required can
come down to many variables but if it is a standalone building it is only
required to be provided with a fire alarm system where the occupant load is
greater than 300. Where required, the system will need to be initiated by
one of or a combination of manual operation (pull stations), automatic
detection, or sprinkler system waterflow. Notification of the
occupants is required to be a voice announcement and include visible signals.
Wet-chemical extinguishing system
As referenced earlier, the majority of fires in restaurants are caused by cooking equipment. For this reason, any cooking equipment used in processes that produce grease-laden vapors must be provided with ventilation and a fire extinguishing system. The fire extinguishing systems must be listed to UL 300 or equivalent standards which is currently only achieved by wet chemical extinguishing systems. The wet chemical is able to separate the oil and air for a sufficient amount of time to allow complete cooling. These systems are most commonly activated automatically through the use of fusible links that are in the exhaust airflow and have a manual release that can also be used by staff in the area. The manual release should be located in the path of egress from the space to allow for safe use.
Some
common issues with the fixed extinguishing systems include the caps on
discharge nozzles being taken off for day-to-day use. These caps prevent grease
from getting into and clogging the nozzles and are designed to blow off when
the system activates. The rearrangement or replacement of cooking equipment can
also be problematic as the systems are specifically designed for the original
equipment, changing these out without analyzing the system could result in a
failure to extinguish a fire.
Class-K Fire Extinguisher
While the
fixed extinguishing system is intended to be the primary means of
extinguishment, at least one portable fire extinguisher is also required to be
provided in the kitchen area. Extinguishers in kitchens need to be Class K to
be appropriate for use on the cooking medium. Signage is required at the
extinguisher in the form of a placard that is conspicuously placed near each
Class K extinguisher that states that the fire protection system must be
activated prior to using the fire extinguisher.
Requirements for a UL 300
Fire
suppression systems that are UL 300-compliant
must use a wet chemical agent. Wet chemicals suppress flammable vapors but also
cool the source so it can’t reignite. Remember that although a system may be
labeled as a “wet chemical,” that doesn’t necessarily mean it is UL
300-compliant.
In
addition to using a wet chemical agent, UL 300 systems must also include:
·
A manual pull station
·
An automatic fire detection system
·
Automatic fuel shut-offs for gas and electric
·
Nozzles located in the hood and duct
·
Nozzles located over each grease-generating cooking
appliance
·
Wet chemical system serviced semi-annually by an
authorized licensed service company
· Hood and duct maintenance and cleaning semi-annually by an authorized licensed service company
Inspection
and Maintenance
Routine
inspection and maintenance of cooking equipment, the hood and exhaust systems,
and fire extinguishing equipment (including fire extinguishers) are vital to
ensuring that protection is maintained consistently for the restaurant. In
addition, instructions need to be provided to new employees on hiring and to
all employees annually on the use of portable fire extinguishers and the manual
actuation of the fire-extinguishing system. Hoods need to be inspected for
grease build-up at a frequency that is typically semi-annually for most
restaurants but can be more or less frequent, depending on the type and volume
of cooking. When that inspection finds grease build-up the hood and exhaust
system must be cleaned.
NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, 2021 |
The fire extinguishing systems must be maintained at least every 6 months and all actuation and control components, including remote manual pull stations, mechanical and electrical devices, detectors, and actuators, must be tested for proper operation. Fusible links of the metal alloy type and automatic sprinklers of the metal alloy type must also be replaced at this interval.
Installing
a UL 300-compliant fire suppression system is more than a requirement for your
restaurant. It’s a critical step in protecting your employees, customers, and
livelihood. Restaurant owners should partner with a qualified fire and
security company to design and install a reliable and code-compliant fire
suppression system that best meets their needs. For any code compliance
questions, our fire and life safety specialists are available 24/7/365.
Hi Nice blog!
ReplyDeleteFire and Safety is an important need in daily life. So learning about Safety is more important. Study Fire and Safety Course in Chennai. Fireandsafetycoursesinchennai.in is a professional Training Institute on providing qualified Safety training.
For more information:
Fire and Safety courses in Chennai
IOSH Course in Chennai
Industrial Safety courses in Chennai