NBC - LIFE SAFETY REQUIREMENTS FOR DATA CENTRES
There are
no specific annex in NBC 2016 Part 4 Fire & Life Safety regarding life
safety requirements for Data Centres. In upcoming NBC 2025 (currently in Draft
& BIS now accept valid comments from professionals) add new annex named ANNEX
G (Clause 6). This Article just recommendation to BIS can include in
upcoming NBC 2025, Writeups have copy from Draft NBC 2025. In NBC 2016 ANNEX
G (Clause 6) indicates Commercial Kitchens.
G-1 GENERAL
Data
centres are classified under Group E Business occupancy and in particular as
E-6 sub-occupancy considering its primary use, scale, and presence of process
equipment. A comprehensive fire risk assessment should be conducted at the
planning stage and periodically during operation. Assessments must include
ignition sources, fire load, electrical risks, HVAC systems, etc. For guidance
on the facilities and infrastructure of datacentres, refer the following good
practices.
G-2 BUILDING DESIGN AND CONSTRUCTION
G-2.1 The fire resistance rating for the structural and non-structural elements shall be based on guidelines as per approved and accepted standards. The fire rating shall be validated and certified with a view to meeting the requirements of Table 1 above. In the absence of any validated/certified rating, guidance may be obtained from the information available in Annex C.
G-2.2 An anti-static floor system is highly recommended to prevent electrostatic discharge and support cable management. The data centre must be completely isolated from dust, water, vibration, and humidity. All external openings should be sealed, and no water sources or pipelines should be routed through or above the data centre, UPS room, or communications room to eliminate risks of leakage or moisture intrusion. However, any location of chillers at higher heights be opted considering the operational efficiency, the same should be adequately considered in the structural design; authorities may consider exempting the increased building height in such a case. Such floors shall have no other occupancy else considered in the calculation of floor area ratio and height.
G-2.3 Server rooms, battery banks, fuel storage, and other high-risk areas should be physically separated using fire-rated assemblies. Cable trays and ducts openings for cable trays and ducts should be sealed with materials having fire resistance rating of the compartment.
G-2.4 The number of basements should be kept
as minimum and it shall not be more than 2. The basement(s) shall be within the
building line and their total area shall not exceed the area of ground floor.
Basement must not use for electronic garbage.
Basement-Specific
Considerations
·
Moisture
Control: A
primary concern for basements is the potential for water or moisture leakage
from other parts of the building.
·
Plumbing
Isolation: Keep
plumbing, except for fire suppression and HVAC systems, away from the data
center space to minimize leak risks.
·
Sealed
Enclosure: Data
centers should ideally be "room-in-a-room" to ensure none of their
walls form the external building facade, preventing air and moisture
leakage.
· Air Filtration: Use appropriate filters, such as MERV 8 or higher, to trap contaminants, preventing them from entering the sensitive electronic environment.
G-2.5 The parking requirement shall be
arrived at considering the requirement for administrative building (at 1 ECS
per 100 m2). The parking requirement for the data centre/utility building shall
be based on the actual required number and area (of trucks) for which
additional considerations of loading and unloading spaces for services. Rack
Placement consideration emphasize the hot-aisle, cold-aisle
configuration for rack placement, where racks are arranged in
alternating rows with their fronts (air inlets) facing the cold aisles and
their backs (air exhausts) facing the hot aisles. This strategy, detailed
in publications like the "Thermal Guidelines for Data Processing
Environments," prevents the mixing of cold and hot air, ensuring efficient
cooling by directing chilled air into the front of the racks and the warm
exhaust air from the back of the racks back to the cooling units.
Requirements
for Fire Truck Movement:
·
Minimum
Approach Width:
A clear, unobstructed path of at least 4.5 meters must be maintained for the
fire tender's movement around the building.
·
Height
Clearance: The
height clearance for the approach path must be a minimum of 5 meters to allow
for the passage of the fire truck.
·
Turning
Radius: A
minimum turning radius of 9 meters is required for fire tenders weighing up to
45 tonnes to facilitate their movement on site.
·
Open
Spaces: The
approach to the building must have a width of not less than 6 meters on all
sides, in addition to the required turning radius.
·
Remote
Access: Buildings
require at least two means of access to the site, positioned remotely from each
other, to ensure fire units can move freely and effectively.
Note: If above criteria not fulfil then consideration for the fire truck and its movement shall be ensured in consultation with the local Fire Authority.
G-2.6 Lifts when planned to consider respectively for administrative building (as passenger lift as per Part 8/Sec 5A of the Code) and for the datacentre building (as special goods lifts and special service lifts, for which OEMs should be consulted considering the size, speed and weight of payload; and any required special requirement.
G-2.7 Heights of stories should be arrived at based on the size of racks opted and the associated services (like cooling/ducting) and the same is effectively addressed in the structural design. The total height of the datacentre building shall be arrived based on the FAR (which shall not exceed 5.0 and only Type 1 construction, see also Table of Part 3 ‘Development Control & Promotion Rules and General Building Requirements’ of the Code). Ground coverage shall not exceed 60 percent considering the peculiar requirements and the essential nature of these buildings which are required in the society in the current times.
G-2.8 Environmental Guidelines
·
Temperature: Recommends maintaining equipment
within specific temperature ranges to ensure reliable and efficient
operation. 18°C to 27°C (64°F to 81°F) for most common data center classes.
·
Humidity: Maintain relative humidity
levels within an acceptable range, typically between 20% and 80% relative
humidity. Low humidity can cause ESD, while high humidity leads to
condensation and corrosion.
·
Rate
of Change: Control
the rate of change for both temperature and humidity to prevent rapid shifts
that can damage equipment.
·
Prevent ESD: Low humidity can cause
electrostatic discharge (ESD), which can damage or destroy sensitive electronic
components.
· High-Density Cooling: For high-density IT equipment, consider advanced cooling solutions like direct liquid cooling in dedicated areas with independent controls.
G-3 FIRE DETECTION SYSTEMS
G-3.1 Air Sampling is use of very early smoke detection apparatus (VESDA) in server areas. This system called Aspirating System. It provides extremely sensitive, pre-emptive fire detection by continuously drawing air samples through a network of pipes to a central laser-based detector that identifies microscopic smoke particles before a fire escalates. Pipe network design as per OEMs instructions. These systems, which require multiple alert and alarm thresholds, are characterized by very tight coverage limits, typically 200 square feet per detector. Aspirating system can integrate with building management systems, fire alarm control panels, and suppression systems for comprehensive fire safety. Advanced aspirating models use sophisticated techniques, like CMOS imaging and multi-directional laser scattering, to accurately distinguish smoke from dust and other pollutants, significantly reducing false alarms. As with any tool, proper maintenance is important. Set up a schedule, or use a fire prevention expert to assist you, to regularly calibrate your equipment, check for proper airflow patterns, and ensure the aspirating systems remains in proper working order.
G-3.2 For other requirements on fire detection and alarm system 4.9 be referred.
G-4 FIRE SUPPRESSION SYSTEMS
G-4.1 The fire suppression system in data centres shall be designed to ensure both operational continuity and protection of sensitive equipment. The preferred suppression technologies clean agent extinguishers (such as Inergen, HFC-236fa and HFC-227ea based system or equivalent) should be available throughout data hall areas. Aerosol extinguishing systems can be use a cutting-edge approach to fire suppression. These systems shall be effective in suppressing fires without leaving any residue, making them safe for electronic and electrical installations. Clean agent systems are essentially discharge nozzles connected to a pressurized tank that releases the contents of the tank upon system activation. The system can be activated by electronic means, such as smoke detectors, or by mechanical means, such as fusible links. Tube based suppression system at Rack level is also cutting-edge approach to fire suppression. Fire Suppression system design as per OEMs guideline. As with any tool, proper maintenance is important. Set up a schedule, or use a fire prevention expert to assist you, to regularly calibrate your equipment, check for proper patterns, and ensure the Fire Suppression systems remains in proper working order.
G-4.2 All critical areas within the data centre, including server rooms, network rooms, UPS and battery areas, and under-floor and overhead spaces, must be covered comprehensively by the fire suppression system.
G-4.3 The suppression agents should be ozone-friendly and compliant with international environmental norms. The recharge process must be easy, with minimal downtime, and the equipment should be easy to test periodically.
G-4.4 As an alternative to clean agents, special automatic fire sprinkler systems can be installed. These systems are referred to as “pre-action sprinkler systems.” Pre-action sprinkler systems are interlocked with electronic detectors, such as smoke or heat detectors, and activate only when the electronic detection system actuates. As an additional layer of protection from accidental activation, a single sprinkler head and an electronic detector need to activate before water fills the normally dry piping that protects sensitive rooms. When the system is not active, its piping is dry, and no damage would occur if a sprinkler head accidentally or inadvertently discharged (because the electronic detection system also must actuate to fill the sprinkler system with water). This type of sprinkler system is referred to as a double-interlock pre-action sprinkler system.
G-4.5 An early warning fire detection and suppression system shall be integrated with the fire alarm and Building Management System (BMS) for real-time monitoring and response. The system shall be engineered to offer reliable and quick suppression to minimize damage and downtime.
G-5
ELECTRICAL AND HVAC FIRE SAFETY (see
also Part 8/Sec 2 and Part 8/Sec 3 of the Code)
G-5.1 UPS, transformer, and generator rooms should be separated with fire-rated partitions/doors and have independent suppression systems. Should the need arise, the generators can be placed one over the other/stacked (upto 5 numbers) parallel to the data centre building, but adequate fire safety should be ensured for which OEM’s advice and specialist literature should be referred. Height of datacentre shall be the upper limit for height of DG sets, if stacked. Integrate smoke detectors into the system to provide early warning of fire hazards, such as from short circuits or overheating components.
G-5.2 Wherever batteries are provided, the
same shall be segregated by 120 min fire rated construction. Ventilation to the
room shall be provided as per manufacturer’s instructions. Ventilation system
must provide a minimum of 1 cubic foot per minute per battery cell and operate
based on hydrogen concentration.
Battery room, generally requires a hydrogen gas detection system to mitigate explosive risks from lead-acid batteries. The system should include hydrogen sensors located high in the room where the gas accumulates, smoke detectors for early fire detection, and an integrated system to activate alarms, ventilation, and potentially trigger a safe shutdown of the charging system if hydrogen levels exceed a safe threshold, such as 1% by volume. Mount hydrogen sensors near the ceiling, as hydrogen gas is lighter than air and rises and accumulates at the highest points of the room. When hydrogen concentration reaches a preset level (e.g., 1% by volume), an audible and visual alarm should be activated to alert personnel. Integrate smoke detectors into the system to provide early warning of fire hazards, such as from short circuits or overheating components.
G-5.3 Air conditioning and ventilating systems shall be so installed and maintained as to minimize the danger of spread of fire, smoke or fumes from one floor to other or from outside to any occupied building or structure. Additionally, air inlets must be installed near the floor, while exhaust outlets must be placed at the high point of the room, to exploit hydrogen's low density and upward movement, maximizing ventilation efficiency. (hydrogen is lighter than air and diffuses upwards very rapidly)
G-5.4 Supply air ducts, fresh air and return air ducts/ passages must include fire dampers and smoke detectors (see 3.4.8.4).
G-5.5 Insufficient power capacity design for a data centre can result in various issues such as system downtime, data loss, Increased cost, reduced performance, regulatory non-compliance. Ensuring a robust power capacity design is crucial for the reliable and efficient operation of data centres.
G-6 MEANS
OF EGRESS
G-6.1
Exit Access
Exits for shall be provided on each floor or compartment in accordance with 4.4.2. All exits should be unobstructed, illuminated, and clearly marked.
G-6.2
Staircases and Corridors
Staircases must be enclosed, fire-rated, and positively pressurized to prevent smoke ingress. Staircases shall be of minimum 1.5 m in width, and 2 numbers of it will be required in the datacentre building. Staircase for administrative building shall be arrived at using clause 4; in any case, minimum 2 staircases are required.
G-6.3
Emergency Lighting and Signage
Emergency lighting consistent with emergency system for the building shall be provided. Addressable emergency exit lighting system is recommended, adaptive type exit signages can also be used.
G-7 MEP,
FIRE FIGHTING, AND SEISMIC SUPPORT REQUIREMENT
G-7.1 Earthquakes can cause downtime, data
loss, service disruptions, fire, etc. Seismic bracing is essential to secure
MEP equipment and systems, safeguarding them against the threats posed by
earthquakes.
G-7.2 Non-structural measures focus on
protecting operational components. These include seismic-rated mounting systems
for equipment racks, secure cable pathways, MEP and fire fighting services to
avoid disconnections, and reinforced architectural features like ceilings and
raised floors. These elements must meet seismic standards to ensure systems
stay operational during and after an earthquake.
G-7.3 Seismic analysis/calculations should
be carried out based on Part 6 ‘Structural Design, Section 1 Loads, Forces and
Effects’ of the Code and IS 16700. Each nonstructural component’s seismic
interactions with all other connected components and with the supporting
structure shall be accounted for in the design. The component shall accommodate
drifts, deflections, and relative displacements determined in accordance with
the applicable seismic requirements of standards.
G-7.4 Each straight pipe/duct/cable
containment run with two or more supports requires a minimum of two transverse
braces (perpendicular to the run) and one longitudinal brace (parallel to the
run).
G-7.5 Wire rope angular bracing should be
seismic certified/tested by third party accredited lab as per method of testing
for rating seismic and wind restraints. Rigid angular bracing and modular
support system should be analyzed for both tensile and compressive loads for
strength and serviceability for the maximum length of element being used in
worst case condition as per load combination as mentioned in standards.
G-7.6 Calculate static and dynamic loading
due to wind forces required to select/design vibration isolators, bases and
seismic and wind restraints for outdoor and roof top equipment’s/services. The
calculation of wind load shall be as per Part 6/Sec 1 of the Code. Worst case
between seismic loads and wind loads shall be considered for supporting and
vibration isolation.
G-8
SECURITY
G-8.1 It is recommended that all doors shall
be access controlled measures to restrict entry to authorized personnel only,
preventing unauthorized access and protecting sensitive data and
infrastructure. This is achieved through a layered security approach
including physical security for building entry, electronic systems like
proximity card readers or biometric authentication for server rooms, and even
integrated software for remote monitoring and control.
Key Elements
of Data Center Door Access Control
- Layered Security: Access control is
implemented in multiple layers, starting from the building's main entrance
and progressing to more secure areas like server rooms.
- Racks level Security: Access to each individual server
rack within a data center will be individually secured and controlled, not
just the overall data center facility. This implies that, in addition
to physical entry to the building and data center floor, each specific rack
needs separate authorization for access, typically using systems
like keycard readers, biometrics, or PIN
codes, to prevent unauthorized individuals from directly interacting
with or tampering with the servers and equipment housed within the racks.
- Authentication Methods: Common methods include
proximity cards, key fobs, smart cards, and biometric scanners
(fingerprint or face scans).
- Multi-Factor Authentication: Some areas may require a
combination of authentication methods, such as both a card and a biometric
scan, to grant access.
- Monitoring and Alarms: Systems record every access
instance, and alarms are triggered if doors are forced open or held open
for too long, initiating an incident response.
- Remote Control and Surveillance: Advanced solutions allow
administrators to remotely monitor door status (locked/unlocked) and
integrate real-time surveillance feeds into a central Data Center
Infrastructure Management (DCIM) system.
- Integration with CCTV & Alarm
Systems: Centralizing
security management through the integration of third-party solutions like
CCTV into the Command Centre platform enhances both visibility and
response.
For example, when access to a restricted area is denied, a critical alarm is triggered. Operators can utilize the Command Centre viewer to monitor the alarm and associated CCTV footage. Notifications can then be sent to the cardholder via email, text, or app alerts, guiding the appropriate response. This system streamlines the management of access denial alarms, consolidating all necessary information into a single interface, and facilitating seamless coordination between different security measures, enhancing overall protection. - Visitor Management: Visitors are issued
temporary photo badges and must be escorted by authorized personnel, with
their access rights being logged and revoked upon departure or as per
automatic time defined.
- Mantraps: Some highly secure areas,
like server rooms, utilize mantraps—two interlocked doors that prevent
more than one person from passing through at a time—to serve as a final
layer of defense.
- Lights-Out Data Centers: In some advanced
facilities, access is minimized, with remote management and automation
systems handling operations, further reducing the need for physical entry
and enhancing security.
G-8.2 In line with safety requirements,
access shall be open for the fire affected area.
G-9
OPTIONAL PERFORMANCE INDICATORS
For guidance
on the performance indicators of datacentres, the following good practices may
be referred.
CED 46(26992) WC - Draft Code for Comments Only.
NBC 2016 Part 4.
NFPA Portal
About
Author:
Dr. Arindam Bhadra is a Fire safety consultant & ISO Auditor based in Kolkata, India, with over 20 years of experience in Fire safety systems. He’s currently founding director of the Sprinkler Fire Safety Awareness and Welfare Foundation & SSA Integrate. He working on Fire Safety awareness, training, consultancy & Audit in same field. Dr. Arindam Bhadra is popularly known as "Fire ka Doctor" because of his expertise in fire safety, prevention, and awareness, helping people and organizations stay safe from fire hazards. He is Member of FSAI, NFPA, Conformity Assessment Society (CAS) etc. He is certified fire Inspector and certified Fire Protection professional.
No comments:
Post a Comment