Relays used for in Fire Alarm Systems
In an
emergency you may wish your fire alarm system to perform a number of automated
tasks – this could include grounding a lift or closing doors. To do this you
will require fire alarm relays, devices which allow the automation of certain
functions.
A relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit.
The
function of relay module in fire system control is to provide a way for a
high-voltage device to be controlled by a low-voltage signal. This is done by
closing a switch that activates the device when the fire alarm sends a small
current to it. In practice, a relay in a fire alarm system may be used to
perform the following functions:
·
Close Doors: A fire alarm relay can be used to
automatically shut fire doors in a building when the fire alarm is
triggered. This helps to contain the fire and prevent it from spreading.
·
Activate
Sprinklers: The
fire relay module can be used to activate the sprinkler system in a building
when the fire alarm is triggered.
·
Sound Alarms: A fire alarm relay module is often
used to activate a sound alarm in an emergency. This warns people in the
vicinity of the fire and helps them to evacuate the area.
·
Switch OFF AC
Systems: The
stream of air coming out of an air conditioner can spread the fire in a
building or even smoke and fumes. A fire alarm relay can be used to switch off
the AC system and prevent the fire from spreading.
·
Switch On Smoke
Exhaust Systems:
The smoke exhaust system in a building helps to clear out smoke and fumes. A
fire alarm relay can be used to switch it on.
·
Switch Off Loud
Music: During a
fire, it is important to be able to hear fire alarms and other warnings. a fire
alarm relay module is often used to switch off loud music when the fire alarm
is triggered so that people can hear the warnings.
Relays can
be used to control voltage feeding a particular supply and either apply or drop
voltage in the event of a fire activation.
Relays can
be used to signal to monitored inputs, these inputs would monitor a nominal EOL
resistance and in the event of a fire alarm activation would switch to pick up
the trigger value resistance.
Relays can also be used to signal a simple NO/NC contact.
The
relay’s load may be AC or DC, but must be within amperage rating of the relay
contacts. The relays must be fire alarm listed and supplied by the FACP
manufacturer, or be a Listed Fire Relay from a manufacturer.
Off-the-shelf
electrical supply relays are not permitted to be directly wired to a fire alarm
system. Additionally, polarity must be observed because of the integrated diode
used in the relay.
Testing of
the fire alarm system includes only verifying the relay changed state, and not
necessarily the operational performance of the fire-safety function itself.
Proper fire alarm relay operation will be verified by using a meter or by
observing an activation LED on the relay.
Question 1: Will your relay be used to supply electrical power or turn it off? You are not responsible for the connection and operation of any other trade’s equipment or function, but you cannot allow the relay to be used improperly. If your relay states it has contacts rated at 10 amps and the owner wishes to turn on 20 amps of outdoor lighting, then they will have to use your relay to switch another device having the proper load rating (i.e. 20 amps or less).
While it
is true that the relay, wiring, contactor or equipment could fail without
causing a trouble signal on the fire alarm system, you are only responsible for
the relay and circuit that you provide up to the switched contacts of the
relay. All equipment after your relay contacts is the responsibility of another
trade or another contractor.
Question 2: Will your relay be used to switch a small current
and low voltage signal used by another electrical system, rather than the
safety equipment load? Sometimes
the load you need to switch amounts to an electrical control signal of just 5V
– which another system’s data input needs in order to perform a function. Since
you must supply a relay that is used to perform a certain function, you are not
responsible for performing everything the owner wants to do. For example, your
relay cannot pulse an illuminated street address sign.
Question 3: Is the safety
function to be performed a code-required fire alarm feature such as controlling
elevators, or is it a customer nicety such as opening a driveway gate or
turning on outdoor lighting? For a code compliant relay, its wiring must be either
fail-safe or cause a Trouble Signal when power to the relay fails.
For
Illustrated Relay A
Power to certain emergency safety functions may need to be turned off during an alarm. Examples of these functions commonly include power to electro-magnetic door holders or electro-magnetic door locks. These two examples are normally well within the electrical rating of a fire relay, but a contactor may also be needed if you intend to cut power to a club’s DJ booth, for example, that is providing amplified sound, light and stage effects. If a contactor/relay is also needed, the electrician will supply it.
Relay A rules: Common and Normally Open relay contacts are used to supply a CLOSED circuit to keep safety
equipment operational.
This
relay’s wiring is “Fail-Safe,” since loss of power to the relay coil will cause
the fire-safety function to be performed. No EOL resistor or power supervision
relay is required if the emergency function is performed when loss of power to
the relay causes the safety function to be performed.
For
Relay B
Power to
safety functions may need to be turned on during an alarm. This may include
smoke exhaust fans and indoor/outdoor lighting. Typically, a 10 amp relay will
be used to switch an additional contactor/relay that would be needed for a
large rooftop fan, for example.
Relay B rules: Common and Normally Open relay contacts are used to supply a CLOSED circuit to deactivate safety equipment
upon a polarity reversal signal from the FACP upon alarm conditions.
This relay
wiring is NOT “Fail-Safe,” since loss of power to the relay will not cause the
fire-safety function to be performed. Instead, this wiring method will cause a
FACP trouble signal should there be a fault on the wiring supplying power to
the relay.
A circuit
fault or any other loss of power to operate the life safety function may need
to be supervised. For example, supervision of the electrical power to operate
the elevator’s shunt controller is required to ensure the 110vac power to
perform the emergency shunt trip is constantly present. The modern
self-contained elevator shunt-trip panels contain a set of relay contacts that
will close should the shunt-trip lose its operational power for any reason.
Wire a dedicated IDC with an EOL resistor across these provided open terminals.
Any loss of that 110vac operating power will cause their relay contacts to
close and initiate a Supervisory signal. This signal must be specifically and
descriptively annunciated (ie “elevator shunt-trip power loss”).
For
Relay C
Use only
for non-life safety applications or as allowed by the exception (see below).
Relay C rules: Common and Normally Closed and/or
Normally Open Relay contacts may be used to activate or to deactivate
customer’s equipment. This Relay is NOT “Fail-Safe,” since loss of power to the
relay will not cause the fire-safety function to be performed. Also, power
wiring to the relay coil can experience a fault without causing a FACP Trouble
signal.
An
exception allows this relay’s wiring configuration to be used to perform code-required safety
functions. This is when a relay output within a control unit is used to
activate a function performed by another control unit. This happens when an
FACP on-board relay is used to close a set of input contacts of another control
panel. For example, you can trip a NAC power booster using the alarm output
relay of the main control panel. This exception allows a relay circuit to
connect two control units even though the relay wiring is neither monitored for
integrity nor provides fail-safe operation.
This
wiring exception is only permitted if both control units are located in the
same room, the control units are within 20 feet of each other, and the relay
wiring connecting both panels is protected against mechanical injury by running
it either inside the wall or on the surface using conduit
An
elevator company provides a shunt-trip panel whenever the machine room or hoist
way includes sprinklers. This panel ensures the elevators will be shut down
before sprinkler water can reach sensitive electrical and mechanical
components. Your job will be to provide a fail-safe relay (example A) or
power-supervised relay (example B), and contacts that will close upon an alarm
signal from the hoist way or elevator equipment room detectors.
রিলে
কি?
রিলে একটি সুইচিং ডিভাইস। রিলে এমন একটি সুইচিং ডিভাইস যা সার্কিটে কোন ধরনোর শর্ট সার্কিট সৃষ্টি হলে নিজে ধংস হয়ে সার্কিট কে রক্ষা করে। এই জন্য রিলেকে অতন্দ্রী পহরি বলা হয়ে থাকে। রিলের মধ্য দিয়ে যদি কারেন্ট প্রবাহিত হয় তাহলে কয়েল মেগনেটাইজ হয়ে কন্টাকের মাধ্যমে সার্কিট কে অন অফ কন্ট্রোল করে থাকে। জরুরি অবস্হায় সার্কিট পুড়ে যাওয়া বা ধংস হয়ে হাত থেকে রক্ষা করে থাকে রিলে।
রিলে কতো
প্রকার কি কি
ভোল্টেজ অনুযায়ী রিলে দুই প্রকার
১. এসি রিলে
২.ডিসি রিলে
*এসি রিলে আবার ভোল্টেজ উপর ভিত্তি করে অনেক ধরনের হয়ে থাকে
1. 5VAC,6VC,12VAC,24VAC,36VAC, 110VAC,220VAC,440VAC
কয়েলের ভোল্টেজের উপর ভিত্তি করে এসি রিলে এতো ধরনের হয়ে থাকে।
*ভোল্টেজ উপর ভিত্তি করে ডিসি রিলে বিভিন্ন ধরনের হয়ে থাকে
1. 5VDC,6VDC,12VDC,24VDC,36VDC, 110VDC,220VDC 440VDC
কয়েলের ভোল্টেজের উপর ভিত্তি করে ডিসি রিলে এতো ধরনের হয়ে থাকে।
রিলে কেন ব্যাবহার করা হয়
১.এসি ভোল্টেজ কে ডিসি রিলে দিয়ে কন্ট্রোল করার জন্য রিলে ব্যাবহার হয়।
২.সার্কিটে কোন ধরনের ক্রটি বা ক্ষতির সম্মুখীন হলে রিলে হতে জানা যায়।
৩ রিলে নিজে নষ্ট হয়ে সার্কিট রক্ষা করে।
৪.সার্কিটে কোন ফল্ট হলে রিলে থেকে জানা যায়।
রিলে ব্যাবহারের নিয়ম
প্রতিটি রিলেের গায়ে ডায়াগ্রাম দেওয়া থাকে,
কতো ভোল্টেজ কতো এম্পিয়ার,
কোনটা কোন কন্টাক।
যদি রিলের বডিতে কিছু লিখা না থাকে তাহলে ভিতরে কয়েলের মধ্যে ভোল্টেজ এম্পিয়ার লিখা থাকবে।সেই ভোল্টেজ এবং এম্পিয়ার দেখে কোন জায়গায় ব্যাবহার করা যাবে তা নির্ধারণ করতে হবে।
রিলে
প্রকারভেদ
সাধারনত তিন প্রকার রিলে হয়ে থাকে
1.SPST (Single
Pole Single Throw)
2.SPDT (Single Pole
Double Throw)
3.DPDT (Double Pole
Double Throw
*SPST রিলে মূলত ৪ পিনের হয়ে থাকে
*SPDT রিলে মূলত ৫পিনের হয়ে থাকে
*DPDT রিলে মূলত ৮ পিনের হয়ে থাকে
রিলে পিন পরিচিতি
রিলেতে মূলত তিনটি পিন থাকে
1.Common
2.NO
3.Nc
1.Common: কমন কয়েলে সার্কিটের সুইচিংয়ের মান অনুযায়ী ভোল্টেজ প্রবাহিত করা হয়। রিলে কয়েলে কোন পজিটিভ নেগেটিভ প্রান্ত নেই তাই এটি পজিটিভ নেগেটিভ যে কোন প্রান্তে সংযোগ করা যায়। রিলের পরিচিত প্রকাশ পায় মূলত তার কয়েল ভোল্টেজ উপর ভিত্তি করে। যে ভোল্টেজে রিলে চালু হয় সেটি রিলের ভোল্টেজ ধরা হয়।
2.NO: NO এর ফুল মিনিং Normally Open, অর্থাৎ রিলে যখন নরমাল অথবা কয়েল না ধরা অবস্হায় থাকবে তখন Common এবং NO প্রান্ত বিছিন্ন অবস্হায় থাকবে। যখন রিলে কয়েল ধরবে তখন অথবা রিলে কয়েল এবনরমাল হবে তখন Common এবং NO প্রান্তটি নিরবিচ্ছিন্ন অবস্হায় কাজ করবে।
3.NC: NC এর ফুল মিনিং Normally Close, অর্থাৎ রিলে নরমাল অবস্থা বা কয়েল না ধরা অবস্হায় Common এবং NC প্রান্ত নিরবচ্ছিন্ন অবস্থায় থাকবে বা সংযোগ থাকবে। যখন রিলে কয়েল ধরবে বা রিলে এবনরমাল অবস্হায় থাকবে এখন Common এবং NC বিচ্ছিন্ন অবস্হায় থাকবে।
রিলে কয়েল পরিচিতি:
রিলে কয়েল ভোল্টেজ অনুযায়ী অনেক ধরনের হয়। আমরা যে রিলে ব্যাবহার করবো তার কয়েল ভোল্টেজ অনুযায়ী ভোল্টেজ সাপ্লাই দিলে কয়েলটি ধরবে এবং রিলের উপরে থাকা ইন্ডিকেটর লাইটি জ্বলে উঠবে। আবার যখন ভোল্টেজ সাপ্লাই বন্ধ হয়ে যাবে ইন্ডিকেটর টি বন্ধ হয়ে যাবে এবং কয়েলটি বন্ধে হয়ে আগের অবস্হানে চলে আসবে।
Thanks for sharing this blog content with us. Paraflex is the leading name in the industry.
ReplyDeleteHouse Wire Manufacturers
Informative Content.... Thanks 👍
ReplyDeleteNice
ReplyDelete