UL Listed and FM Approvals for Fire Protection Under NFPA 13?
Listings are required for all essential system components but acceptance of specific approvals—UL listed, FM approved, or otherwise—is determined by local code officials.
“UL listed” and “FM approval”—along with their lesser-mentioned cousin, “certified”—are terms that circulate freely in the world of fire protection. Fire pumps, fire sprinklers, pipes, extinguishers, and a vast array of other products regularly undergo rigorous, third-party testing according to the standards of groups like FM Global and UL (formerly known as Underwriters Laboratories). But for many consumers, what remains unclear is the matter of which certifications to use and when they’re required.
In this article, we bring some clarity to the subject of listings and approvals. We explain what terms like these mean and who decides when a particular organization—be it UL, FM Global/Approvals, or another group—has the credibility needed to certify specific types of fire protection products. Finally, we present readers with an overview of products requiring these certifications in NFPA 13: Standard for the Installation of Sprinkler Systems.
UL-listed and/or FM-approved residential and commercial fire sprinkler heads, check valves, hose angle valves, CPVC pipe, pipe hangers, and fire extinguishers are just part of our vast catalog of certified equipment—just take a look.
UL listed and FM
approval act as industry synonyms for “listed” or “certified”—but the different
terms have distinct definitions under NFPA codes and standards
Manufacturers, retailers, and consumers often describe fire protection products as “UL-listed,” “FM-approval,” and even “UL and FM approved.” But as Bruce Rose at CUI Insights notes, there’s really no such thing as “UL-approved”—and for good reason. “[I]f you look at their website, the only mention of ‘approvals’ is in examples of incorrect terms. UL avoids the word as a way of indicating that it really is the manufacturer’s responsibility to ensure safety and that UL only acts as an auditor[.]”
While this shorthand is popular (including, at times, in our own products), there’s another good reason to understand the difference between “listed” and “approved:” the NFPA draws a sharp distinction between those products or installations that are listed and those that are approved.
From the 2019 edition of NFPA 13
3.2.1* Approved. Acceptable to the authority having
jurisdiction.
3.2.3* Listed. Equipment, materials, or services included in a list published by
an organization that is acceptable to the authority having jurisdiction and
concerned with evaluation of products or services, that maintains periodic
inspection of production of listed equipment or materials or periodic
evaluation of services, and whose listing states that either the equipment,
material, or service meets appropriate designated standards or has been tested
and found suitable for a specified purpose.
A.3.2.3 Listed. The means for
identifying listed equipment may vary for each organization concerned with
product evaluation; some organizations do not recognize equipment as listed
unless it is also labeled. The authority having jurisdiction should utilize the
system employed by the listing organization to identify a listed product.
Code officials decide
what’s approved, but it takes third-party
evaluation to make a product listed. Based on
tests assessing durability, longevity, and proper function—along with
audits of manufacturers’ processes—listings from organizations like UL and FM
Approvals provide stakeholders with a measure of confidence in products’
performance that’s not otherwise possible.
And here’s where it gets even more confusing: FM
Approvals (the name of the independent testing branch of the FM Global
insurance company) spurs the description “FM Approved.” This is NOT an
“approval” according to the NFPA definitions above, as only the
authority having jurisdiction can approve something (more
on who that authority is in a second).
Thus, when you see either “UL listed” or “FM approved,” it essentially means it was tested by the safety organizations for a specific application and “listed,” aka “certified.”
Are
all listings equal? Only if the AHJ says so
A wide variety of organizations test and attest to the suitability of fire protection equipment. But even listed equipment must be “acceptable to the authority having jurisdiction,” or AHJ (NFPA 13 2019, 3.2.3). But who—or what—is an AHJ?
From the 2019 edition of NFPA 13
3.2.2* Authority
Having Jurisdiction (AHJ). An organization, office, or individual
responsible for enforcing the requirements of a code or standard, or for
approving equipment, materials, an installation, or a procedure.
According to the NFPA 13 Handbook, the AHJ is often a fire marshal or building code official. But the term can cover a variety of public and private people or entities tasked with enforcing standards. In some instances, even an insurance company or corporate safety officer could be an AHJ.
Applied haphazardly, AHJs’ authority to decide which listings are acceptable—and which aren’t—could cause some rather arbitrary problems. However, while some contractors claim to have encountered this exact problem, Michael Johnston at Electrical Contractor suggests that AHJs in the world of electrical work, for example, often rely on lists of testing laboratories—published by the Occupational Safety and Health Administration (OSHA)—for the sake of “consistency.”
Those lists are provided as part of OSHA’s
Nationally Recognized Testing Laboratory (NRTL) program. The NTRL “[r]ecognizes
private sector organizations” that evaluate products for compliance
with various standards. In fact, federal regulations require some products to
have approval from an NRTL, including:
- Automatic fire sprinkler systems
- Portable fire extinguishers
- Fire doors (self-closing and not)
- Fixed extinguishing systems
- Automatic fire detection devices and equipment
In the world of fire protection, thankfully, an authority having jurisdiction is often your local or state fire official or government inspector, and they usually put great stock in items that are tested and listed by UL, FM, and other companies recognized by the Nationally Recognized Testing Laboratory program.
A handful of nationally recognized testing laboratories, including UL and FM, are responsible for a wide variety of listed fire protection products.
OSHA’s list of NRTLs, then, is a likely starting point for local fire officials. The quick-reference guide below provides a current list of laboratories that test fire equipment ranging from fire sprinklers to amplifiers for fire alarms. While our list is extensive, it isn’t comprehensive—a single laboratory may be recognized for work with hundreds of standards. For more options, check out the current list of NRTLs available at OSHA.
Otherwise,
review this select list:
Fire Protection Products in the OSHA list of Nationally Recognized
Testing Laboratories (August 2019) |
||
Testing Laboratory |
Products |
|
CSA Group Testing and Certification |
Fire pumps and electrical accessories |
|
Control units, cables, and amplifiers for fire alarm and protection
systems |
||
FM Approvals |
Automatic and ESFR fire sprinklers |
|
Plastic pipe and fittings for fire protection service |
||
Foam, dry chemical, and carbon dioxide fire extinguishers |
||
Heat detectors |
||
Fire alarm control panels, signaling devices, and detection products |
||
Intertek Testing Services NA, Inc. |
Thermoplastic pipe and gasketed joints for fire protection service |
|
Foam and carbon dioxide fire extinguishers |
||
Fire doors |
||
Alarm valves for fire protection |
||
Detectors, boxes, and accessories for fire alarm systems |
||
Foam fire extinguishers |
||
Fire pumps and controllers |
||
NSF International |
PVC and thermoplastic pipe and fittings for fire protection service |
|
QAI Laboratories, LTD |
Fire door assemblies |
|
Southwest Research Institute |
Plastic pipe for fire protection service |
|
Fire doors and dampers |
||
Flame arrestors |
||
Underwriters Laboratories Inc. |
Fire sprinklers, including residential and ESFR |
|
Sprinkler system pipe (metal, thermoplastic, and underground),
flexible fittings, and adjustable nipples |
||
Alarm, pressure-reducing, check, and fire pump relief valves |
||
Fire alarm system signalling, power, amplification |
||
Dry chemical, foam, and carbon dioxide fire extinguishers |
||
Fire doors |
||
Fire pumps and accessories |
||
Indicating pressure gauges for fire protection |
One overarching rule guides NFPA 13’s requirements for system components and hardware: listings are required for any product that impacts a sprinkler system’s ability to control fires.
From the 2019 edition of NFPA 13
7.1.1.2 Unless the requirements of 7.1.1.3, 7.1.1.4, or 7.1.1.5 are met, all
materials and devices essential to successful system operation shall be listed.
7.1.1.2.1 Valve components (including valve trim, internal
parts, gaskets, and the like) shall not be required to be individually listed.
7.1.1.3 Equipment as permitted in Table 7.3.1.1 and Table 7.4.1 [select
aboveground pipes and fittings discussed below] shall not be
required to be listed.
7.1.1.3.1 Nonmetallic pipe and fittings included in Table
7.3.1.1 and Table 7.4.1 shall be listed.
7.1.1.4 Materials meeting the requirements of 17.1.2, 17.1.6.2, 17.1.6.3, and
17.1.7.3 shall not be required to be listed.
7.1.1.5* Components that do
not affect system performance shall not be required to be listed.
The NFPA 13 Handbook clarifies
that “system performance” pertains only to a sprinkler system’s ability to
discharge water as designed. Thus, signs, drains, and pressure gauges don’t
need to be listed—but fire sprinklers and pipe hangers do. That said, NFPA and
local governments also prescribe specific requirements for
signs, drains, and pressure gauges; thus, any component used in a system must
meet these enforced standards, and the local requirements (specified in
fire codes) dominate.
Because this fire sprinkler points down, the spur-shaped deflector should be convex rather than concave. That’s a tell-tale sign that this is an upright fire sprinkler—which isn’t listed for this use. Source: Fire Protection Deficiencies
Before we get to NFPA 13’s listing requirements, it’s worthwhile to remember that listed products stay listed only when properly installed. In the example above, the fire sprinkler—which may otherwise be perfectly fine—isn’t listed for use in the pendent (hanging) orientation. The deflector, which distributes water as it flows from the pipes, won’t give the water the proper shape, putting areas nearby at risk.
Underground
pipes and fittings (private fire service mains)
Underground pipes for fire service mains are a good example of an “either-or” scenario. These underground pipes must either meet one of several manufacturing standards listed in section 6.1.1.1 or they must be listed.
If it doesn’t meet the specific manufacturing standards in 6.1.1.1, a pipe otherwise listed specifically for use as part of a fire service main may be used instead, so long as it’s installed in accordance with its listings (6.1.1.2, 6.1.1.2.1). Likewise, the underground fittings listed in section 6.2 may comply with either specific manufacturing guidelines for cast iron, ductile iron, or malleable iron, or be specifically listed for this use. FM Global offers approvals (listings) for both underground fittings and pipes, including those made from iron, polyvinyl chloride (PVC), and polyethylene.
Aboveground pipes and
fittings
All aboveground pipe and tube must meet or exceed certain standards for metallic piping or, in the case of CPVC, nonmetallic piping.
CPVC pipe, however, must also be listed for installation in sprinkler systems (7.3.2.1), as must other types of nonmetallic pipe (7.3.2.1.1).
Select types of steel, brass, and copper pipes do not require sprinkler-system-specific listings if they are made in accordance with the standards of table 7.3.1.1. However, all metallic pipes not meeting the standards presented in table 7.3.1.1 must be listed (7.3.3.1).
Aboveground metal pipes are listed either
to UL 852 or, in the case of steel pipe, to FM 1630. Similarly, thermoplastic
pipes, including CPVC, are listed to UL 1821 or to FM 1635.
Thermoplastic CPVC couplings are one of
many fittings that require listings under NFPA 13.
Devices connected to these pipes also require
listings under NFPA 13, including:
- Nonmetallic pipe fittings (7.4.3)
- Fittings connecting threaded steel pipes, when
those pipes have wall thicknesses less than Schedule 30 or Schedule 40
(7.5.1.2)
- Welded fittings not meeting standards provided
in table 7.4.1 (7.5.2.3.1)
- Joining methods not specifically described in
NFPA 13 (7.5.5.1)
One notable exception to these listing requirements is the grooved coupling, which must only be “dimensionally compatible” with pipes, valves, or fittings (7.5.3.1). However, listings are required when those couplings don’t comply with the standard dimensions provided in ANSI/UL 213 (7.5.3.1.1).
Finally, grooved couplings must always be listed when used with dry pipe systems (7.5.3.2). The reason: due to reduced fire endurance and increased exposure to temperature extremes, grooved couplings serving dry pipe systems tend to degrade faster than their counterparts on wet-pipe systems.
Many other parts require listings, including fire
sprinklers, accessories, and valves
Fire sprinklers
The standard for most fire sprinklers is UL
199, Automatic Sprinklers for Fire Protection Service. But
sprinklers may be approved for more specific applications,
including:
- Control mode sprinklers, which produce
large droplets at low pressures. These are often approved (listed) under
FM 2000
- Residential sprinklers (UL 1626, FM 2030),
used in settings ranging from apartment complexes to family homes
- Early-suppression fast-response (ESFR) heads, listed in accordance with UL 1767 and/or FM 2008
The following fire sprinkler accessories also
require listings:
- Nonmetallic hole-covering plates or
escutcheons for fire sprinklers (2019 edition of NFPA 13: 7.2.6)
- Escutcheons for recessed, flush, or concealed
sprinklers (7.2.6.2)
- Fire sprinkler cover plates (7.2.6.3)
It’s worth noting that metallic escutcheons don’t require listings for non-recessed pendent or horizontal sidewall sprinklers—but all other types do.
Valves
Valves that let contractors test the system or
drain water during renovations don’t need to be listed (16.9.1.1). However,
valves designed to control water supplies do (16.9.3.1.1 – 16.9.3.1.2).
According to section 16.9.3.2, these valves—called listed indicating
valves—always require third-party listings, with one exception: wrench-operated
outdoor valves installed under a road box.
Other types of valves requiring listings include:
- Alarm (check) valves
- Dry pipe valves
- Pressure reducing
valves
- Deluge valves
- Preaction valves
So many listings, so little time
We’ve barely scratched the surface of the listings
required by NFPA’s various standards—to say nothing of the range of
certifications offered by third-party organizations. Organizations like FM
Approvals and UL have had more than a century to define what makes
some products more reliable, effective, and safer than others, and their
influence can be felt throughout the fire protection industry.
When in doubt about what’s appropriate, contact
your local authority having jurisdiction and a professional fire protection
installer.
If you’re looking for listed and approved fire
protection products, take a look at QRFS’s selection. We carry a variety of
products tested to rigorous standards, including:
- Residential
fire sprinklers
- Commercial
fire sprinklers
- Brand-name
recessed escutcheons
- Hose
angle valves
- CPVC
pipe fittings
The Victaulic
V3405 is just one of many UL-listed and FM-approved fire sprinklers in
stock now.
No comments:
Post a Comment