- Bonding is more clear word compare to Grounding and Earthing but there is a micro difference between Grounding and Earhing.
- Earthing and Grounding are actually different terms for expressing the same concept. Ground or earth in a mains electrical wiring system is a conductor that provides a low impedance path to the earth to prevent hazardous voltages from appearing on equipment. Earthing is more commonly used in Britain, European and most of the commonwealth countries standards (IEC, IS), while Grounding is the word used in North American standards (NEC, IEEE, ANSI, UL).
- We understand that Earthing and Grounding are necessary. We need to understand that there are really two separate things we are doing for same purpose that we call Grounding or Earthing.
- The Earthing is to reference our electrical source to earth (usually via connection to some kind of rod driven into the earth or some other metal that has direct contact with the earth).
- The grounded circuits of machines need to have an effective return path from the machines to the power source in order to function properly (Here by Neutral Circuit).
- In addition, non-current-carrying metallic components in a System, such as equipment cabinets, enclosures, and structural steel, need to be electrically interconnected and earthed properly so voltage potential cannot exist between them. However, troubles can arise when terms like “bonding,” “grounding,” and “earthing” are interchanged or confused in certain situations.
- In TN Type Power Distribution System, in US NEC (and possibly other) usage: Equipment is earthed to pass fault Current and to trip the protective device without electrifying the device enclosure. Neutral is the current return path for phase. These Earthing conductor and Neutral conductor are connected together and earthed at the distribution panel and also at the street, but the intent is that no current flow on earthed ground, except during momentary fault conditions. Here we may say that Earthing and grounding are nearly same by practice.
- But In the TT Type Power Distribution System (In India) Neutral is only earthed (here it is actually called Grounding) at distribution source (at distribution transformer) and Four wires (Neutral and Three Phase) are distributed to consumer. While at consumer side all electrical equipments body are connected and earthed at consumer premises (here it is called Earthing). Consumer has no any permission to mix Neutral with earth at his premises here Earthing and grounding is the different by practice.
Bonding:
Earthing:
Grounding:
Difference between Earthing & Grounding:
Illegal Practice of interchange Purpose of Grounding & Earthing wire
§ Neutral wire in grid connections is mandatory
for safety. Imagine a person from 4th floor in a building uses Earth wire
(which is earthed in the basement at Basement) as neutral to power
his lights. Another Person from 2nd floor has a normal setup and uses neutral
for the same purpose. Neutral wire is also earthed at the ground level (as per
USA practice Neutral is Grounded (earthed) at Building and as per Indian
Practice it is Grounded (earthed) at Distribution Transformer).
However, ground wire (Neutral wire) has a much lower electrical
resistance than Earth Wire (Earthing) which results in a difference
of electrical potential (i.e. voltage) between them. This voltage is quite a
hazard for anyone touching a Earth wire (Metal Body of Equipment) as it may
have several tens of volts.
§ The second issue is legality. Using ground wire instead of neutral makes you an energy thief as the meter uses only the Phase and neutral for recording your energy consumption. Many Consumers make energy theft by using Earthing wire as a Neutral wire in an Energy meter.
How to Apply to Fire Safety Systems and Installations
The NFPA 70, or NEC, sets the foundation for electrical safety in residential, commercial, and industrial occupancies in the United States. Updated every three years, it's a living document that evolves alongside the ever-advancing field of electrical technology. Let's go through a fast summary of NFPA 70 (also expressed as NFPA70 and NFPA-70). This will allow you, as a fire safety professional, to navigate and use its provisions more effectively.
Application of NEC to Electrical installation Directly
The NEC is divided into 9
chapters, with each chapter further divided into parts, articles, and sections.
The chapters cover specific aspects of electrical installations, ranging from
wiring methods, equipment for general use, special occupancies, special
equipment, to special conditions.
·
Article
210: This covers
branch circuits, the smallest units of an electrical system that directly
supply power to electrical equipment. It includes standards for circuit
ratings, protection, and load calculations.
- Article 215: It focuses on feeder
circuits, which transport electricity from service equipment to branch
circuits. Understanding this section is essential for ensuring proper
feeder size and load.
- Article 230: This provides guidelines
for service installations, the point where a building or system receives
power from the utility source. It covers service conductors, equipment,
and overcurrent protection.
- Article 240: Overcurrent protection is a
crucial safety element of any electrical system. This section provides
guidance for the selection and installation of overcurrent protective
devices.
- Article 250: This focuses on grounding
and bonding, two critical aspects of electrical safety. It defines how to
properly ground electrical systems and equipment, ensuring safety and
reducing the risk of electrical shock and fires. Digitize equipment is
thoroughly grounded to protect itself from surge damage, and this
obviously depends on the earth ground available in the building.
- Article 760: This section is of
particular interest to you, as it pertains specifically to fire alarm
systems. NEC Article 760 covers fire alarm system power sources, circuit
identification, installation, and more.
Application of NFPA 70 to Fire Alarm Installations Directly
One of the most direct overlaps between the NEC and fire safety is found in NFPA 70 Article 760, "Fire Alarm Systems," within the NEC. This article deals specifically with the installation of wiring for fire alarm systems.
NFPA 70 Article 760 outlines the specific wiring methods for both non-power-limited and power-limited fire alarm circuits. This distinction is critical as power-limited circuits are designed to limit electrical energy to a level that does not ignite a fire in normal or fault conditions. Non-power-limited circuits, on the other hand, may have enough energy to ignite a fire. That's why they require more robust safety measures.
Power-limited fire alarm circuits are generally easier to install due to fewer restrictions, as they don't pose as much of a fire hazard. They can often be installed using similar techniques to those used for regular low-voltage wiring.
Non-power-limited circuits, however, must adhere to stricter standards. They need to be installed in such a way that reduces the potential for faults and ensures a higher degree of safety. Specific types of cable or conduit may be required, and separation from other electrical cables may be mandated.
Additionally, the NEC dictates how fire alarm circuits should be protected from accidental damage or disconnection. The use of dedicated circuit breakers or disconnecting means, identifiable and accessible control equipment, and appropriately labeled circuits are all examples of NEC provisions related to fire alarm installations.
Other Overlaps between Fire Safety and NFPA 70
Beyond fire
alarm systems, several other aspects of the NEC directly influence fire safety.
For example:
- Grounding (Article 250): Proper grounding of
electrical systems is crucial for preventing electrical fires. By
providing a path for electric current to follow in the event of a fault,
grounding reduces the risk of electrical shock and fire.
- Overcurrent Protection (Article
240): Overcurrent
protection devices, such as circuit breakers and fuses, are designed to
cut off electrical power when the current exceeds a certain level. This
prevents overheating of wires and potential electrical fires.
- Wiring Methods and Materials
(Articles 300-399): These
articles provide guidelines for the proper installation of wiring and
related equipment to ensure safety and prevent electrical fires. This
includes specifications for conductors, cables, raceways, and boxes, among
other components.
Understanding
and applying these codes is crucial in minimizing fire risks and ensuring
optimal safety in all types of buildings and facilities.
How to Stay Up to Date with NFPA 70 / NEC
Given the
rapid evolution of electrical technology, it's important to stay updated with
the latest NEC revisions. The NFPA offers numerous resources for ongoing
education, including online training, webinars, and certifications.
Regularly reviewing and understanding changes in the NEC can enhance your ability to install, maintain, and use fire safety systems in compliance with the highest safety standards.
Conclusion:
Ground is
a source for unwanted currents and also as a return path for main current.
While earthing is done not for return path but only for protection of delicate
equipment’s. It is an alternate low resistance path for current. Earth is used
for the safety of the human body in fault conditions while Grounding (As
neutral earth) is used for the protection of equipment’s.