Importance of fire alarms in the workplace

The importance of fire alarms in the workplace

Fire alarms are essential in the workplace to provide early detection and rapid alerts, allowing employees to evacuate safely before a fire spreads. This critical first warning reduces the risk of injury and fatalities, prevents extensive property damage, and ensures legal compliance with safety regulations

Fire safety in the workplace is crucial to prevent and protect against the destruction caused by fire. Neglecting fire safety protocols can have devastating consequences, including loss of life, property damage, legal ramifications, and high legal costs and fines. 

Legally, employers are primarily responsible for fire safety in the workplace. They must create and document a workplace fire preparedness plan, educate all employees on fire safety procedures, maintain fire protection and prevention equipment, and plan for emergencies, among others.

However, employees likewise play a vital role in the collective responsibility of ensuring fire safety. At the minimum, they should attend fire safety training sessions, report potential fire hazards, be familiar with evacuation routes, and not misuse fire safety equipment.

Key Benefits of Workplace Fire Alarms

·        Life Safety & Evacuation: Early warning sensors detect smoke or heat to alert occupants, gaining precious minutes for employees to evacuate safely.

·        Business Continuity: Prompt alerts allow for early intervention or suppression, minimizing destruction to critical equipment, digital data, and company assets.

·        Regulatory & Insurance Compliance: Most local building and safety codes (such as those from OSHA) mandate the installation of fire detection systems. Having fully functional systems is also typically a prerequisite for business insurance coverage

Why Proactive Maintenance Matters

Installing the system is just the first step; consistent maintenance is vital.

·        Regular Testing: Experts recommend routine checks of individual detectors and alarm sounders to ensure functionality.

·        Fire Drills: Combining alarm systems with routine safety training and fire drills ensures that your team remains confident and knows exactly what to do during a real emergency

🚨 Critical Benefits

·        Early Warning: Detects smoke and heat instantly.

·        Safe Evacuation: Grants precious minutes for employees to escape.

·        Minimizes Damage: Allows fast intervention to save property.

·        Reduces Downtime: Protects critical data, equipment, and operations.

·        Legal Compliance: Meets local building codes and OSHA standards.

·        Lowers Insurance: Qualifies businesses for reduced premium rates.

·        Peace of Mind: Boosts employee morale and sense of safety

Suppose a 3-storey commercial building requires a comprehensive, interconnected fire alarm network to ensure a synchronized evacuation across all levels. Because a fire on the ground floor can quickly trap occupants on the upper storeys, early detection and multi-floor signalling are critical.

🏢 Fire Alarm Requirements for 3-Storey Buildings

·        Interconnected Detection: If a detector triggers on the 1st floor, alarms must sound simultaneously on all 3 storeys.

·        Zoned Panel Systems: The main control panel must clearly display which specific floor or room triggered the alarm.

·        Manual Call Points: Break-glass / pull stations must be placed at every exit door and stairwell landing on all 3 floors.

·        Emergency Lighting: Visual strobes and illuminated exit signs must guide occupants down stairwells if smoke cuts visibility.

·        Elevator Isolation: The alarm system must automatically recall elevators to the ground floor and ground them safely.

·        Evacuation Massage: The alarm system must automatically start evacuation massage to the on all 3 floors.

·        Integration: The alarm system must integrated with Damper, Smoke Control System, Access Control, AHU, FANs etc as applicable.

🔧 Recommended Next Steps

1.   Designate Fire Wardens: Assign at least one trained fire warden per floor to manage multi-storey evacuations.

2.   Install Dual Signaling: Use both audible horns and visual flashing strobes to ensure clear alerts over ambient office noise.

3.   Conduct Multi-Floor Drills: Practice full evacuations to ensure employees on the 3rd floor can exit via stairwells efficiently.

Power plant is also workplace, but its industrial workplace. A power plant environment shifts fire safety requirements from standard commercial compliance to high-hazard industrial suppression and specialized protection. Power facilities contain high-voltage electrical infrastructure, flammable turbine oils, and critical control rooms where a fire can cause catastrophic grid failure, massive financial losses, and extreme risk to personnel.

Critical Fire Protection Elements for a Power Plant

·        Specialized Hazard Suppression: Standard water sprinklers cannot be used in high-risk zones. Turbine rooms require deluge water spray or water mist systems, while electrical switchgear rooms and control rooms rely on clean agent gas suppression (like FM-200 or Novec 1230) to extinguish fires without damaging electronics.

·        Advanced Multi-Sensor Detection: Due to ambient dust, high heat, and heavy machinery, standard smoke alarms will cause false alarms. Power plants require a mix of aspirating smoke detection, IR flame detectors for fuel areas, and linear heat detection cables along cable trays etc.

·        Robust Notification & EVAC: A 3-storey power plant has high ambient machinery noise. The alarm system must use high-decibel industrial sirens, explosion-proof horns, and high-intensity strobe lights to guarantee everyone on all 3 floors is alerted.

·        Emergency Shutdown Integration (ESD): The fire alarm system must automatically link to the plant’s distributed control system (DCS) to isolate fuel lines, trip turbines, and shut down ventilation to stop fire spread.

·        Mass Notification System (MNS): Voice evacuation systems are critical. Operators must be able to broadcast live, specific instructions across all floors and outdoor yards to coordinate a highly technical evacuation.

THE LEGAL PERSPECTIVE

From a legal standpoint, installing and maintaining a fire alarm in the workplace is not optional; it is a strict, mandatory requirement governed by federal safety bodies, building codes, and civil liability laws. Failing to meet these regulations can result in heavy corporate fines, building closures, denial of insurance claims, and criminal negligence charges for business owners.

The Building or Property Owner is responsible for ensuring that the necessary fire safety measures are in place. This includes providing the necessary fire safety equipment, ensuring that fire escape routes are clear and accessible, and obtaining the necessary fire safety certifications.

Building Occupants, with employers at the helm, are responsible for the daily maintenance of fire safety within the premises. This involves ensuring that fire safety equipment is in good working condition, conducting regular fire drills, and educating employees on fire safety procedures.

Larger buildings or complexes in India, especially commercial ones, are often required to appoint Fire Safety Managers. The FSM is responsible for implementing and managing fire safety measures: regular inspections, ensuring compliance with fire safety standards, and coordinating fire drills.

📜 Principal Legal Frameworks

·        OSHA Regulations (US): Under OSHA 29 CFR 1910.165, most employers must install an emergency employee alarm system. For high-hazard environments or buildings with more than 50 employees, automated detection is strictly mandatory.

·        The International Building Code (IBC): The IBC mandates automated fire alarm networks based on occupancy types, square footage, and building height (such as a multi-storey structure).

·        NFPA 72 & NFPA 850 (Industrial Standards): While NFPA 72 dictates the legal installation, testing, and structural performance metrics of alarms, NFPA 850 provides the legally referenced safety standards specifically for power plants and electric generating facilities

·        UK / International Law: Under the UK Regulatory Reform (Fire Safety) Order 2005, every business must appoint a "Responsible Person" legally liable for providing "appropriate fire detection" systems.

⚖️ Exact Technical Legal Mandates

·        Decibel Levels: OSHA standards demand that an audible alarm be distinctive and register at least 15 decibels (dB) above ambient noise, or 5 dB above maximum sound levels, sustained for at least 60 seconds.

·        Tactile & Visual Signals: Regulations require visual strobe alerts alongside sirens to accommodate hearing-impaired workers and penetrate high-noise industrial sectors.

·        Testing Logs: Legally, you must log all system checks. Non-supervised systems require monthly testing, and an annual comprehensive inspection must be performed by a certified professional to maintain a building's certificate of occupancy.

Fire Safety Management Team

Fire safety management is a team work to the systematic control of fire risks and implementation of safety measures within an organization to preserve life, protect property and ensure business continuity. It involves a combination of preventative strategies, protective systems, and emergency response planning.

All Employees/Occupants

Every individual in the building is a vital part of the fire safety management team. Their responsibilities include: 

        Following established fire safety rules and procedures.

        Participating in training and fire drills.

        Reporting potential fire hazards immediately.

        Knowing evacuation routes and assembly points. 

Effective fire safety management requires continuous commitment, regular

assessments, and a proactive approach to risk management from every level of the organization. 

Operational Response Team (Fire Wardens / Marshals)

These individuals are trained staff members designated to assist during an emergency:

        Chief Fire Warden / Emergency Response Team Leader: Oversees the overall emergency response on a floor or within a specific area, coordinates with the fire safety manager and external emergency services, and ensures all individuals are accounted for at the assembly point.

        Floor/Area Wardens (Monitors): Take charge of their specific areas, ensure clear exit paths, sweep rooms to confirm everyone has evacuated, assist people with special needs, and report the status (e.g., "all clear") to the Chief Fire Warden.

        Specialized Teams: Larger organizations may have specific groups within their fire brigade:

        Communication Team: Responsible for sounding the alarm and contacting the fire department.

        Search and Rescue Team: Assists individuals who may be trapped or unaware of the emergency.

        Medical/First Aid Team: Administers immediate medical treatment to injured persons.

        Firefighting Team: Trained to use portable fire extinguishers to control incipient (small, initial stage) fires.

        Security/Traffic Control Team: Secures the area and controls access for emergency vehicles.

Core Management

Responsible Person / Employer / Building Owner/ HSE Manager: This individual or entity holds the ultimate legal accountability for fire safety on the premises. They are responsible for ensuring a comprehensive fire safety plan is in place, resources are allocated, and all duties are fulfilled.

        Fire Safety Manager / Fire Officer: A qualified professional appointed by the responsible person to oversee the day-to-day implementation of the fire safety plan. Their duties include:

        Conducting fire risk assessments and regular inspections.

        Developing and updating fire safety policies and emergency response plans.

        Coordinating maintenance and inspection of all fire safety equipment (alarms, sprinklers, extinguishers).

        Ensuring compliance with local and national fire codes and regulations.

        Organizing and documenting training sessions and fire drills. 

Fire Safety Management Team - Qualification

Qualification of Operational Response Team (Fire Wardens / Marshals)

        Must typically be at least 18 years old and possess a secondary school or diploma or high school diploma. Many departments now prefer or require an Associate's or Bachelor's degree in fire science or a related field.

        Candidates must be in excellent physical condition to pass a demanding physical ability test, such as the Candidate Physical Ability Test.

        Applicants must pass medical examinations, drug screenings, and thorough background checks, and hold a valid driver's license.

Fire Safety Manager / Fire Officer / HSE Officer

        Must typically be at least 05 years experience in same field with Level 3 (NEBOSH / EOSH / IOSH) or Level 4 Diploma in Fire Science and Fire Safety or occupational Health & Safety.

        Aim to gain professional accreditation with bodies like the Institute of Fire Safety Managers (IFSM) or the IFE or National Fire Service College (NFSC).

Core Management (Head of Health and Safety / Operation Director etc)

Must typically be at least 10 years experience in same field with Level 5 or Level 6 (OTHM/ HSEPB) or Level 7 (Qualifi / ProQual)  Diploma or SFJ Awards. Also member of country based fire related association. ISO 45001 / ISO 14001 / NFPA – CFPS or ASP/CSP by BCSP will carry extra point.

Means of Qualification – Service Provider

NFPA 72 titled "Means of Qualification," outlines the criteria for determining who is a "qualified person" to service, test, and maintain fire alarm systems, and provides examples of acceptable qualifications to meet these requirements. 

Fire alarm systems must be maintained, tested, and serviced by qualified persons. 

        Examples of Qualifications:

The clause provides specific examples of what constitutes a qualified person, including: 

1. Personnel who are factory-trained and certified by the manufacturer (OEM) for the specific type and brand of system they are servicing. Must show training certificate.

2. Personnel who are certified by a nationally recognized certification organization acceptable to the authority having jurisdiction (AHJ). 

3. Personnel, individually or through their organization, who are certified by OEM or Have Experience on same brand or multi brand on systems covered by the code. Must show exp letter.

        Evidence of Qualification:

Evidence of these qualifications must be provided to the authority having jurisdiction upon request.

Note: Request to all AHJ to check & verified service provider personal Qualification & Experience.

Preventive Maintenance Checklist

This preventative maintenance checklist is applicable for any type industry. Service Provider authorised person can prepare inspection checklist as per customer. If you are End user then also you need to prepare your own inspection checklist as per your needs and your systems.

General Information

Comments

SL No

Description

YES

NO

1

A copy of the Fire Alarm Installation Certificate and Record of completion is availlable from Customer/End User.

 

2

More then one Service Provider was responcible for Maintaining Fire Alarm System

 

3

A Copy of as-build Fire alarm system drawing signed by competent body is availlable on site.

 

4

A Copy of Fire Panel operation process is installed near Fire Panel.

 

5

For addressable system a list of each devices with corresponding location is provided. The devices addressing shall reflect actual room names or numbers that are current to the building use.

 

Fire Alarm Control Panel (FACP); Make:______________Model:______________

Comments

6

Fire panel installed location Name___RECEPTION_______________Address: _NODE 01_____

7

The dedicated 220-240V AC branch circuit for the fire alarm control panel is labeled " Fire Alarm Circuit" on the electrical panel or actual circuit breaker is colored RED as per NFPA 72

 

8

The dedicated 220-240V AC branch circuit shall be permanantly marked inside the Fire alarm control panel as per NFPA 72

 

9

UPS is use for powering up Fire Alarm Control Panel

 

10

Fire Alarm Panel is grounded properly by earth continuity conductor. Connection can be taken from electrical panel board's earth point.

 

11

Batteries are permanatly marked with Month & Year of Manufacture as per NFPA 72

 

12

The Loop Cable are properly connected to currect terminal with draessing and lebeled properly in side the Fire Alarm Control Panel.

 

13

Inter communication of each board (Power Supply, Loop card, Network card, Display Board, Motherboard etc) is correctly terminated

 

14

Comunication cable for others same Panel (Networking) or repeater or annunciator is properly terminated inside the Fire alarm Control Panel.

NA

 

15

Modbus / BACnet card is properly installed and output cable is properly terminated.

NA

 

16

Graphic communication card us properly installed and output cable is properly terminated.

NA

 

17

Any obstruction to access freely of Fire Alarm Control Panel

 

18

Fire Alarm Panel display properly shows FIRE, Trouble/Fault as with proper location text or information. Dedicated LED also indicate accordingly.

 

19

Total Fire Present in Fire Alarm Panel display before testing Fire Alarm System

___00___Nos

20

Total Trouble / Fault Present in Fire Alarm Panel display.

____00____Nos

21

Ask and check physically Fire Fire Panel Key is availlable.

 

22

Just Disconnect 220V AC Power and check through Battery Fire Panel is Run

 

23

For disconnection of Main Power Fire Panel shows any Trouble/Fault

 

24

Once Main power is ON indicate fault is automatic gone

 

25

Check Fire Alarm Panel Internal Buzer is working (Beep Sound during Fault/Fire)

 

26

Ask & Check How many loop / Zone Fire Panel are

___02___Loops

27

Ask & Check How many loop / Zone Fire Panel are connected

____02___Loops

28

During Activation of MCP Fire Alarm panel are shown proper information

 

29

During Activation of Smoke Detector Fire Alarm panel are shown proper information

 

30

After Activation of Smoke Detector / MCP Fire Alarm panel are alarming, When Press Silence, the System is Silenced

 

31

After Pressing RESET key, Fire Alarm panel is Shows "SYSTEM NORMAL"

 

Repeater Panel / Annunciator Panel; Make:__NOT AVAILLABLE_Model:___________

Comments

32

Annunciator panel installed location Name____________________________Address: ______

33

Panel is powerd through 220V AC or 24V DC is perperly labeled inside of panel and its properly terminated in correct terminal.

NA

 

34

Any obstruction to access freely of this Panel

NA

 

35

Check Main panel to this panel communication terminal are connected

NA

 

36

Check Panel Internal Buzer are in working Condision

NA

 

37

Ask and check physically Fire Fire Panel Key is availlable.

NA

 

38

Total Fire Present in Panel display before testing Fire Alarm System

_________Nos

39

Total Trouble / Fault Present in Panel display.

_________Nos

40

During Activation of MCP this panel are shown proper information in display

NA

 

41

During Activation of Smoke Detector this panel are shown proper information in display

NA

 

42

After Activation of Smoke Detector / MCP, Press Silence key check Alarm sound are stoped.

NA

 

43

After Pressing RESET key  check System are showing "SYSTEM NORMAL"

NA

 

Integrated Voice Alarm Panel; Make:_____NOT AVAILLABLE_Model:_______

Comments

44

voice alarm panel installed location Name___________________________Address: ______

45

Internal communication terminal is properly connected with Fire Alarm panel to Voice Alarm Panel.

NA

 

46

Any obstruction to access freely of this Panel

NA

 

47

Any Display availlable in Voice Control Panel

NA

 

48

How many amplifier is connect with Voice Alarm Panel

__________Nos

49

How many Zone use

__________Nos

50

Each Zone EOL resistance is properly connected

NA

 

51

Both way comminication is working

NA

 

52

During testing of Fire Alarm System Voice Evac Massage is working (Hindi, English & regional Language)

NA

 

External Voice Alarm Panel; Make:__NOT AVAILLABLE__Model:___________

Comments

53

voice alarm panel installed location Name_____________________________Address: ______

54

The dedicated 220-240V AC branch circuit for the Voice alarm control panel is labeled " Voice Alarm Circuit" on the electrical panel or actual circuit breaker is colored RED as per NFPA 72

NA

 

55

The dedicated 220-240V AC branch circuit shall be permanantly marked at External Voice Alarm Panel

NA

 

56

UPS is use for powering up Fire Alarm Control Panel

NA

 

57

External Voice Alarm Panel is grounded properly by earth continuity conductor. Connection can be taken from electrical panel board's earth point.

NA

 

58

Batteries are permanatly marked with Month & Year of Manufacture as per NFPA 72

NA

 

59

The Zone Cable are properly connected to currect terminal with draessing and lebeled properly the External Voice Alarm Panel.

NA

 

60

During Fire Test the External Voice Alarm Panel automatically started with voice evac massage

NA

 

61

Check Zonewise anauncement is in working condition

NA

 

62

Check Voice Massage / sound throughout the occupancy

NA

 

Notification Devices; Make:__MORLEY_____Model:___________

Comments

63

Fire Alarm Signaling devices sound throughout the occupancy

 

64

If sounder with flasher used, flasher is working properly

NA

 

65

Voice Evac massage is  sound throughout the occupancy

NA

 

Control Devices; Make:______________Model:___________

Comments

66

Check During Fire alarm PA system is turn ON automatically

NA

 

67

Check During Fire alarm Access Control system all door is OPEN automatically

 

68

Check During Fire alarm Fire damper oparate automatically

 

69

Check During Fire alarm Smoke damper activate / oparate automatically

NA

 

70

Check During Fire alarm AHU / HVAC oparate automatically

 

71

Check During Fire alarm Emmergency light oparate automatically

NA

 

72

Check During Fire alarm Emmergency Exit Door unlock automatically

 

73

Check During Fire alarm Presharization Fan working automatically

NA

 

73

Check During Fire alarm FIRE signal shown in BMS system software automatically

NA

 

74

Check During Fire alarm FIRE signal shown in PLC/SCADA/DCS system software automatically

NA

 

Initiating Devices; Make:__MORLEY IAS___Model:___________

Comments

75

All initiating devices labeled properly

 

76

All initiating devices Blinking properly indicate as normal.

 

77

Once Initiating devices are in Fire mode devices LED glow in RED continuasly.

 

78

Once Reset from Fire Panel Initiating Devices RED LED is Normal mode.

 

79

Smoke Detectors initiate alarm throughtout the Fire Alarm Panel

 

80

Smoke Detectors initiate alarm throughtout the Repeater Panel / Annunciator Panel

NA

 

81

Heat Detectors initiate alarm throughtout the Fire Alarm Panel

 

82

Heat Detectors initiate alarm throughtout the Repeater Panel / Annunciator Panel

NA

 

83

On activation Smoke/Heat/Multi Detector to shutdown elevator is tested

NA

 

84

Activation of the elevator lobby smoke detector activates the elevator recall and initiation an alarm signal at the fire alarm panel.

NA

 

85

Beam Detectors initiate alarm throughtout the Fire Alarm Panel

NA

 

86

Beam Detectors initiate alarm throughtout the Repeater Panel / Annunciator Panel

NA

 

87

Multisensor Detectors initiate alarm throughtout the Fire Alarm Panel

 

88

Multisensor Detectors initiate alarm throughtout the Repeater Panel / Annunciator Panel

NA

 

89

Probe Detectors initiate alarm throughtout the Fire Alarm Panel

NA

 

90

Probe Detectors initiate alarm throughtout the Repeater Panel / Annunciator Panel

NA

 

91

MCP initiate alarm throughtout the Fire Alarm Panel

 

92

MCP initiate alarm throughtout the Repeater Panel / Annunciator Panel

NA

 

93

All MCP is not obstructed, secured in place

 

94

Duct Detectors shut down HVAC unit and send supervisory signal to the Fire Alarm Panel

NA

 

95

Input Module initiate alarm throughtout the Fire Alarm Panel

 

96

Input Module initiate alarm throughtout the Repeater Panel / Annunciator Panel

NA

 

97

Clean Agent suppression system initiates alarm throughtout the Fire Alarm Panel

NA

 

98

Sprinkler Flow Switch connect through Input module, it initiate alarm throughtout the Fire Alarm Panel

NA

 

Wiring / Cableing; Make:_______UNKNOWN________

Comments

99

All the notification and initiation devices wiring by Fire resistant cable as standard and size.

FRLS

 

100

Cable for Fire Alarm System is in RED Color / RED color conduit

 

About Author:

· Certified Engineer for BOSCH Fire Product Design Programming Commissioning.

· Certified Engineer for BOSCH PAVIRO Product Design Programming Commissioning.

· Certified Engineer for Honeywell CCTV Product Design Programming Commissioning.

· Certified Engineer for Notifier (Honeywell) Fire Product Design Programming Commissioning.

· Certified Engineer for Honeywell Access Control Product Design Programming Commissioning.

· Certified Engineer for HID Access Control Product Design Programming Commissioning.

· Certified Engineer for ESSER (Honeywell) Fire Product Design Programming Commissioning.

· Certified Engineer for Honeywell PA Product Design Programming Commissioning.

· Certified Engineer for DSC Intrusion Product Design Programming Commissioning.

· Certified Engineer for Gunnebo CCTV Product Programming Commissioning.

· Certified Engineer for Gunnebo Entrance Control System Programming Commissioning.

Saturday, September 10, 2011

Fire Safety Laws Fit for Purpose ?

Is a re-think of fire safety regulations required, because some business owners appear to continually flout the rules

Looking at the continuing stream of prosecutions, you get the distinct impression that a large proportion of the business sector just doesn't get fire safety. Regularly, those people we see in the courts are small operators in high-risk sectors: hotel owners, operators of guest houses, and landlords. Then of course there's the retail sector also routinely in the dock -- an industry in which individual managers take a large share of responsibility for standards at their own stores.

What these have in common is that the level of risk from fire is high -- either due to the presence of sleeping accommodation and/or the presence of the public. As any fire risk assessor will tell you, the prosecutions are the tip of the iceberg. There's plenty of evidence that a high proportion of businesses operate with very poor fire safety standards.

What's the issue?
There seem to be a number of factors at play:
  • low likelihood of a fire;
  • low likelihood of a prosecution; and
  • low likelihood of an inspection.
It's always hard to persuade people to spend money, time, and effort to solve a problem they don't think they have. Since the resources of fire and rescue services have been diverted to domestic accommodations for higher risk residents, it seems there's less chance than ever of getting caught out for low standards.

Add to all that the difficulty duty holders have in understanding exactly what's needed to fulfil their legal obligations, plus the costs, plus the time or effort to carry out routine testing to ensure that routes are always unobstructed, etc.
If you take the carrot and stick analogy then there's not much of either.

Fire certificates
It was a totally different approach whereby certain types of premises with particular levels of occupancy had to apply for one. You were told exactly what had to be done, right down to the content of annual staff training. If you wanted to do things differently, you were supposed to notify the authority. Contravening a fire certificate could make you end up in prison.
Did it work? Well not exactly. People made changes and forgot to tell the fire brigade. And the authorities didn't have the time to do much revisiting and checking of the premises. Then, of course, as not all premises had to have a certificate. The Fire Precautions (Workplace) Regulations 1997 came in (since repealed), and as a result risk assessments were supposed to be carried out, but mostly were not.
But the part which was good about the old system was the clarity about what had to be done, something which is now sorely lacking.
A myriad of small businesses have now grasped the risk -assessment message, i.e., that they can decide for themselves. They've decided to do nothing. Or maybe they've bought a fire extinguisher but not much else.
The fire and rescue services were already fighting an uphill struggle to get these businesses sorted out, when along came a recession. Go in heavy and the smaller hotel, guest house, etc. will fold with the consequential job losses and political backlash.
And to underline the point the government is now tying regulators in to a commitment to be business friendly.

Safety and health advice days
It's a capital market place, so ideally natural pressures would lead to higher standards. For example, if there's a good supply of high-quality safe accommodation at affordable prices, the cowboy landlords would lose out in the Houses in Multiple Occupation market. Not really a likely scenario for the next couple of decades, though, I'd suggest.Could we nudge people in the right direction instead, with stories of fire victims or increasing the knowledge of managers in the higher risk sectors with free seminars?
One trick the HSE uses to good effect is SHAD events (Safety and Health Advice Days). The deal is that if you turn up for free training, you're unlikely to be inspected. Could there be scope for something similar in the fire sector?
What else could we try?
  1. Increase the penalties: even with a low possibility of prosecution, if the penalties were severe fewer would be tempted.
  2. Increase personal liability: people generally hate personal liability, they prefer to hide behind a company. If it was more likely you'd get a personal fine, community-service order or jail sentence, then as a manager maybe you'd make better fire safety decisions.
  3. Increase the number of prosecutions: When word spreads locally that so-and-so got shut down for fire safety offences, others start to take note.
  4. Increase the numbers of inspections: I'm guessing this is out of the question in the current climate?
  5. Change the law to make the requirements more rigid.
  6. Remove regionalisation and provide one central fire information source for the UK.
Perhaps the answer is a touch of all of the above. But one thing which is within our grasp is to simply make it much easier for people to know what to do. We need to return to a clear message: a means of escape, fire fighting measures, a means of raising the alarm, and maintenance.

Sunday, August 14, 2011

smoke alarms be replaced after 10 years

Smoke Alarms be Replaced After 10 years.

In 1992, the Building Regulations were amended requiring every new build to allow for mains-wired, interconnected smoke alarms to be installed. With many alarms installed under this Regulation still in use and potentially approaching their twentieth year, it was necessary to research a recommendation as to when mains powered smoke alarms should be replaced.
Current recommendations
1.     The majority of research found on this subject emanates from the US. The US National Fire Protection Association (NFPA) have issued NFPA Standard 72, National Fire Alarm and Signalling Code (2010 edition), which states:
1.     "Replace all smoke alarms, including those that use ten-year batteries and hard-wired alarms, when they are ten years old or sooner if they don’t respond properly when tested."
2.     US fire safety websites, along with those in the UK, Canada, New Zealand and Australia, tend to recommend the replacement of domestic smoke alarms, whether battery or mains-wired, when they:
o    Fail to respond to tests
o    Are ten years old (varying between date of installation and manufacture)

Why Replace Alarms?
Several reasons are provided to justify the replacement of smoke alarms after ten years.
3.     The Minnesota Department of Public Safety cite a nationwide study undertaken by the Consumer Product Safety Commission (CPSC), which states that 97% of smoke alarms should still be functioning after one year, if supplied with power. After ten years it is 73%, whereas after 20 years, this figure stands at 54%. The study also indicated that 60% of the failures were due to flat or removed batteries or a disconnected power supply and the study offered possible reasons for this. Ageing alarms may experience sensitivity drifting, which may, in turn, result in an increased frequency of accidental activation and an increase in people removing the power supply. It was thought that newer alarms with a ‘hush’ feature may contribute to remedying this
4.     An NFPA report cites a study undertaken by Canada’s Ontario Housing Corporation supporting the fact that 3% of smoke alarms will fail within one year. They also say that after 30 years, nearly all the alarms will have failed. They conclude that replacement after ten years, with roughly a 30% probability of failure, is an appropriate balance between safety and cost
5.     The South Australian Metropolitan Fire Service state that smoke alarm technology has improved significantly since legislation was introduced (similar requirements to the 1992 UK ones were introduced in Australia in 1995) and replacing old smoke alarms is an ideal opportunity to upgrade smoke alarm systems. The Australian Standard for smoke alarms (AS 3786) specifies an effective life of 10 years, suggesting that after that time effectiveness may be compromised with accumulated dust, insects, airborne contaminants and corrosion of electrical circuitry
6.     In the early 1990s, the US Consumer Product Safety Commission undertook an extensive study, called the National Smoke Detector Project, to examine smoke alarm ownership and operability. Some failures were found in smoke alarms, but there were no large or systematic problems identified with detector designs or manufacturing practices that cast any doubt on their long term reliability. However, a variety of component failures, corroded battery clips and deterioration and corrosion of the horn element contacts were found in a few smoke alarms
7.     Other reports from New Zealand and Canada looked at operability of battery smoke alarms, but no further reports on the operability and longevity of mains-wired smoke alarms could be found

Testing Smoke Alarms
8.     It should be noted that the regular testing of smoke alarms should help identify inoperability as testing a smoke alarm simulates smoke and does not simply test the power supply. This would indicate smoke alarm maintenance messages remain a priority. However, it was queried whether all smoke alarm test functions operate in this way, or whether some simply do test power supply, be it battery or mains-wired
9.     The general view from UK based smoke alarm manufacturers reflects the findings elsewhere. With contaminants such as dust, insects, grease and nicotine, the smoke alarm chamber is susceptible to becoming excessively sensitive or insensitive. This may lead to either an increase in nuisance false alarms, or to eventually becoming unable to detect smoke. One manufacturer reports that contamination is extremely variable, but that field experience indicated that 10 years is a reasonable compromise

Conclusion
10.  Evidence of smoke alarm longevity appears to be scarce and inconclusive. As with other electronic items, there will be failures in the units when they are produced and failures during their lifetime due to individual component faults. Similarly, as they get older more faults are likely to occur. Problems specific to smoke detectors include increased sensitivity
11.  In all the work identified so far, none has specifically concentrated on the failure of smoke alarms when they age. Smoke alarms do fail but the rate at which they do has not been accurately determined or related to their age.
12.  Despite there not being much research, it does seem appropriate to replace smoke alarms after ten years (in line with manufacturers advice), unless individual alarm testing suggests earlier replacement.

Mains-wired interconnected alarms – Replacement kits
13.  Safelincs has developed products designed to help facilitate the process of replacing the smoke detector heads for mains-wired interconnected smoke alarms

Disposal of old Smoke Alarms
Smoke and heat alarms fall under the WEEE (Waste Electrical and Electronic Equipment) regulations. Under the regulations retailers pay a fee to allow their customers to take old smoke and heat alarm to their local recycling centre (Distributor Take-Back Scheme). To find you local recycling centre visit the recycle-more bank locator.

Domestic Customers

Ideally old smoke and heat alarms should be taken to local recycling centres for disposal. However small numbers of alarms can be disposed of along with normal household refuse, a common misunderstanding is that the crossed-out wheelie bin on the back of the alarm means that they must not be placed in a normal waste bin. This symbol actually just means that the alarm falls under the WEEE regulations.

Business Customers

Business customers cannot dispose of smoke alarms along with their normal refuse and should instead take them to their local recycling centre.

Customer Purchasing from Safelincs


Customers that purchased their alarms from Safelincs originally or that are purchasing new alarms from us now can send their old alarms back to us for disposal.

Saturday, July 2, 2011

Emergency Lighting under BS 5266

BS 5266: Emergency Lighting


BS 5266-2:1998 - Code of practice for electrical low mounted way guidance systems for emergency use.

BS 5266-4:1999 - Code of practice for design, installation, maintenance and use of optical fibre systems.

BS 5266-5:1999 - Specification for component parts of optical fiber systems.

BS 5266-6:1999 - Code of practice for non-electrical low mounted way guidance systems for emergency use. Photoluminescent systems.

BS EN 1838:1999 - Lighting applications. Emergency lighting.

BS EN 50172:2004 - Emergency escape lighting systems.

BS 5266-1:2011 - Code of practice for the emergency escape lighting of premises.

Saturday, June 4, 2011

Fire Alarm System Classifications under BS5839

BS5839 Fire Alarm System Classifications
The British Standard splits fire alarm system designs into different classifications of system.  This article looks at the different types of fire alarm system classifications for Public, Commercial and Industrial buildings (a further article will be written to explain domestic system classifications).

BS5839 Splits fire alarm systems into 3 categories.  These 3 categories are Category P Systems, Category L Systems and Category M Systems.  Please find following a description of these categories.

All the systems described below are expected to have manual call points on all final exits, entrances to stairwells and corridors where persons are not expected to walk more than 45 metres to operate a call point.
Category P Fire Alarm Systems
BS5839 Category P Fire Alarm Systems are designed specifically for protection of property only.  Category P systems are split into 2 classifications P1 or P2.
The main objective of a Category P1 fire alarm system is to provide the earliest possible warning of a fire to minimise the time between ignition and the arrival of the fire fighters. 
The difference between a P1 and a P2 system is that a P1 system is designed to protect the whole building, whereas a P2 system is installed in defined parts of the building only.  These defined parts of the building may be areas with an extraordinary high fire risk or hazard.

BS5839 Category P Fire Alarm System Equipment
To create a category P fire alarm system it is possible to use either conventional, analogue addressable or wirelesss fire alarm system equipment.  We have an extensive range of all these types of systems available. 
For smaller installations a conventional / non-addressable fire alarm system may be more cost effective, whereas for larger installations an analogue addressable system would be more suitable.
In buildings where installations are difficult wireless fire alarm system equipment can lead to cost savings.  These systems can also be used for category P systems.

Category L Fire Alarm Systems
The main objective BS5839 Category L Fire Alarm System is life protection.  These systems are split into 5 classifications L1, L2, L3, L4 and L5.

BS5839 Classification L1 Explanation
A BS5839 L1 classification includes automatic fire detection in all rooms, on all escape routes and in all voids over 800mm in height.  Sounders positioned throughout the building to achieve a minimum of 65dB(A) throughout the building and 75dB(A) at bedhead where there is a sleeping risk.  In areas of high ambient noise sound levels the fire alarm sound levels should be 5dB(A) above the normal noise level although not exceeding 120dB(A).

BS5839 Classification L2 Explanation
A BS5839 Classification L2 System should include automatic fire detection on all escape routes and rooms leading onto escape routes.  An L2 system can also include additional areas deemed as a high risk not included in the escape routes and adjoining rooms, such as boiler houses.  The sounders in the building should be according to the description in the BS5839 Category L1 description as above.

BS5839 Classification L3 System Explanation
A BS5839 Classification L3 system is very similar to a category L2 system in that automatic fire detection should be positioned on escape routes and adjoining rooms, although it does not have to include for additional areas deemed to have a high fire risk.  The sounders in the building should be according to the description in the BS5839 Category L1 description as above.

BS5839 Classification L4 System Explanation
A BS5839 Classification L4 system includes automatic fire detection on escape routes only, and not in the adjoining rooms as per the L2 and L3 classifications.  The sounders in the building should be according to the description in the BS5839 Category L1 description as above.

BS5839 Classification L5 System Explanation
A BS5839 Classification L5 System is designed for buildings that have a particular fire risk identified which warrants some special attention.  For example if there is an area of high fire risk which is considered worthy of having some automatic detection but a manual system is also needed, then this will be termed as L5/M.  The sounders in the building should be according to the description in the BS5839 Category L1 description as above.

Category M Fire Alarm Systems
A BS5839 Category M Fire Alarm System is a manual operation only system which has call points on all exits as well as corridors where persons are not expected to walk any more than 45m to operate one.

Category L Fire Alarm System Equipment Available At The Safety Centre
Have you been informed that you require a BS5839 Category L Fire Alarm System?  If so, The Safety Centre has hundreds of products available suitable for creating BS5839 Category L Fire Alarm Systems.  We have products available to suit all budgets.  We have extensive ranges of equipment from many of the worlds leading fire alarm system manufacturers.  These ranges include fire alarm panels, detectors, manual call points, sounders and beacons all suitable for use on BS5839 Category L fire alarm systems.

Sunday, May 1, 2011

BS5839 Part 6 2004 - Fire Alarm System Installations in Dwellings

BS5839 Part 6 2004 - Fire Alarm System Installations in Dwellings
The British Standard Associated with Fire Alarm System Installations in Dwellings is BS5839 Part 6 2004.  This part of the British Standard is split up into 3 categories of systems.  These categories are as follows:-
  • LD1 - Alarms in all circulation spaces that form part of escape routes and all areas where a fire might start, but not bathrooms, shower rooms or toilets
  • LD2 - Alarms in all circulation spaces that form part of escape routes and rooms or areas that present a high fire risk
  • LD3 - Alarms in circulation spaces that form part of escape routes
The category of system that should be installed in a building is often defined by Councils, Insurance Companies, Fire Officers, Building Control and many others.
The above categories indicate the category of system that should be installed.  Further to this information different grades of system may be specified.  
These are as follows:-
  • Grade A - A full system with control and indicating equipment installed to BS 5839: Part 1
  • Grade B - Detectors and sounders using simpler specified equipment
  • Grade C - Detectors and sounders or alarms with central control
  • Grade D - Mains powered alarms with an integral stand-by power supply
  • Grade E - Mains powered alarms with no stand-by power supply
  • Grade F - Battery powered alarms
These grades are used in conjunction with the category type, to indicate what type of system should be installed within the property.  For example if an LD2 Grade A system is requested, this would require a system with alarms in circulation areas that form escape routes and high fire risk areas with the equipment with control and indicating equipment compliant to BS5839 Part 1.