Sunday, January 17, 2021

Reduce Unwanted Alarms

Reduce Unwanted Alarms 

“Fire alarm! – fire alarm? – meh, probably just another false alarm....”

This is the unfortunate common perception of automatic fire alarm systems – very few people have personal experience of a major fire but almost everybody has experienced a false alarm at some time in their lives.

As well as being a considerable drain on fire authority resources, this causes business disruptions (leading to a loss of productivity) and reduces the confidence of the general public in fire alarms.

A false alarm is a fire alarm signal from a fire detection or fire alarm system which is not caused by a fire. Examples include:

·       a fire-like phenomenon (e.g. a smoke machine triggering a smoke detector)

·       accidental damage to the system

·       environment effect

·       inappropriate human action (e.g. malicious manual call point activation)

·       equipment malfunction.

It is important that the detector’s location and performance are correctly matched to ensure optimum fire detection ability with minimal risk of unwanted alarms.

Selecting Detector Types to Limit Unwanted / false Alarms – There are many different types of detector, which operate on different sensing principles and offer specific performance related to the detection of fires as well as their immunity to certain sources of unwanted alarm. Therefore, it is important to select the correct detector for the application.

Variable Detector Performance – detector performance can be adjusted, usually at the control panel, so as to reduce the risk of unwanted alarms for given periods. For example:

·        A smoke/heat detector may be switched to a heat only mode

·        Alarm verification delays may be enabled

·        Smoke detector sensitivity may be reduced

Multi-Sensor Fire Detectors – based on the combination of two or more sensor technologies aimed at minimising the possibility of unwanted alarms while maintaining reliable fire detection. Multisensor detectors usually have several modes of operation so it is important that manufacturers' application design guides are used to determine the correct mode.

Drift compensation - automatically adjusts the sensitivity of the smoke detector, as it becomes dusty or dirty. However, the detector's performance in measuring and responding to smoke remains unaffected. The result is a reduced chance of nuisance alarms, without sacrificing detector performance. This features not available in Conventional detector. Very few addressable detector has this.

Pre-Alarm – to provide an indication that the probability of an alarm is increased

Many detectors can provide a pre-alarm signal to indicate that an alarm condition is approaching. Other systems (such as aspirating smoke detectors) can provide early warning signals that indicate abnormal conditions have been detected, which may lead to an alarm but are not yet threatening. Such signals can be transmitted to trained personnel to maximise the time they have to investigate and in many cases to mitigate the cause of an unwanted alarm before it escalate to a disruptive alarm state.

During periods of reduced activity (e.g. when people are sleeping) the detection system reverts to its normal operating mode where system delays are disabled and a higher detector sensitivity is used.

Manual Call Points – seldom a source of unwanted alarms. However, in certain applications, the possibility of malicious operation needs to be taken into account and locally managed. Where there is a risk that manual call points may be inadvertently operated, consideration needs to be given to protecting them with a cover with adequate signage (WE CHECKED VIDEO FOOTAGE EVERYDAY) and CCTV where required. Re-site call points to a less vulnerable location.  This will need to be carried out in conjunction with your fire risk assessment and competent authorized fire alarm engineer. 

Siting of Detectors – very important in regards to unwanted alarms. In any given situation, likely sources of unwanted alarms need to be assessed (see the table above) before deciding on which type of detector to install and where to position it. For example, smoke detectors should not be cited near a source of steam such as kettles or shower cubicles. Likewise, heat detectors should not be placed in areas of excessive hot or cold drafts.

Typically a detector may be sited up to five meters away from a potential alarm source and still meet the British Standard and NFPA 72.

Environment effect – come from Electrical storms, High humidity, Substantial fluctuation in temperature, Pressure surges on water mains serving automatic sprinkler systems, External smoke or fumes, High air velocities etc.

Contractors working on site - Ensure that all contractors are fully briefed on your fire safety arrangements, location of fire detection systems, and the emergency plan applicable to their working location. Ensure that proper procedures are in place to control the nature of any work e.g. hot work permits, and to ensure that you and your contractors clearly identify the areas in which the work can take place. Detectors in the area could be temporarily covered, or the zone isolated from the fire alarm system during the work period and control measures introduced.

Equipment faults - If there are equipment faults, these will need to be discussed with the fire alarm system authorized maintainer and appropriate action taken to remedy them. Effective, regular maintenance, which includes the internal and external cleaning of smoke detectors, will minimise such faults occurring in the first instance. Do not repair with anyone except OEM. If repaired then any time component will malfunction. Conventional system giving more false alarm then addressable system.

Maintenance – plays an important role in ensuring that fire alarm detection devices remain in good functional order and perform as they were originally intended when first installed. Only certified professional can provide best services support. When there are any changes of environment/risk or changes of use the detection type and siting must be reviewed to minimise risk of unwanted alarms.

The maintenance recommendations in NFPA 72 & BS 5839-1, and any specific instructions given by the manufacturer for each type of detector and field devices should be followed. In India SSA Integrate is dedicated Service oriented agency and certified from most of OEM with lots of appreciation.

Education - of premises staff, occupants and related visitors. It is essential that all persons are made aware of what actions to take if an alarm actuates and that they have been given adequate guidance on reducing false alarms.

Calculation of false alarm rates

Worked example 1

The system comprises:

• 20 point smoke detectors;

• 01 aspirating smoke detector;

• 01 linear optical beam; and

• 08 manual call points.

Number of false alarms in past 12 months = one from the aspirating smoke detector.

False alarm rate = 100(no. of false alarms/no. of AFD)

= 100(1/22)     = 4.5

A preliminary investigation will be needed.

 

Worked example 2

The system comprises:

• 230 point smoke detectors;

• 02 aspirating smoke detectors;

• 01 linear optical beam; and

• 42 manual call points.

Number of false alarms in past 12 months = six from point smoke detectors, one from an aspirating

smoke detector and two from different manual call points.

False alarm rate = 100(no. of false alarms/no. of AFD)

= 100(7/233)    = 3.0

A review will be needed.

 

Worked example 3

The system comprises:

• 1 150 point smoke detectors;

• 46 aspirating smoke detectors;

• 19 linear optical beams; and

• 85 manual call points.

Number of false alarms in past 12 months = 19 from point smoke detectors and three from aspirating

smoke detectors.

False alarm rate = 100(no. of false alarms/no. of AFD)

= 100(22/1 215)     = 1.8

A review will be needed.

 

Worked example 4

• 230 point smoke detectors;

• 02 aspirating smoke detectors;

• 01 linear optical beam; and

• 42 manual call points.

Number of false alarms in past 12 months = 13 from point smoke detectors

False alarm rate = 100(no. of false alarms/no. of AFD)

= 100(13/233)     = 5.6

An in‑depth investigation will be needed.


Warning – Reduction in detector sensitivity always delays the response to a REAL FIRE

Do not put yourself at risk and only attempt to use extinguishers if trained and it is safe to do so.

Sunday, August 2, 2020

Why UL listing important

Why UL listing important

Standards are all around us, even if we are not always aware of them. One example of a widely-used standard is the A4 size for sheets of paper.
A standard is a document that sets out requirements for a specific item, material, component, system or service, or describes in detail a particular method or procedure. Standards facilitate international trade by ensuring compatibility and interoperability of components, products and services. They bring benefits to businesses and consumers in terms of reducing costs, enhancing performance and improving safety.
Standards are developed and defined through a process of sharing knowledge and building consensus among technical experts nominated by interested parties and other stakeholders - including businesses, consumers and environmental groups, among others.
“UL” is short for Underwriters Laboratories, an organization which has been testing and approving products for consumer safety since 1894. Originally known as the Underwriters Electrical Bureau, UL was founded in Chicago by William Merrill, and has since expanded to include 182 service centers in more than 70 countries. Underwriters Laboratories performs safety testing on 18,750 categories of electrical, mechanical and chemical products. So, UL a third-party certification company that’s been around for over a century.
When it comes to UL certification. Certifying products within your business can get expensive, fast. However, one thing that’s never worth skimping on is safety. Your customers’ and workforce’s safety are the most important thing to ensure brand loyalty. Safety and reliability can be the difference between long-term success and catastrophic failure.

UL markers are most commonly seen on industrial equipment and home appliances. These include furnaces, fuses, electrical panels, fire control panel, circuit breakers, cameras, smoke and CO2 alarms, fire extinguishers, sprinklers, glass, and thousands of low voltage equipment. UL Listing in this case means that the product is compliant with the American National Electrical Code (NEC), and is therefore regarded as "safe", i.e., not prone to electrical faults or failures which may cause damage to equipment, facilities, or people.

If your surveillance or safety equipment is not UL listed, it can be ripped out. Technically speaking, cameras and other low-voltage devices do not require UL listing, as they fall under the limited power source (LPS) category. Products in this category do not require listing themselves. Instead, the power source, whether it be a low-voltage supply, midspan, or PoE switch, is to be listed. In practice, however, inspectors often do not follow this, requiring the UL mark other products, as well.

In the surveillance industry, UL listing varies. Many mainstream brands are UL listed. However, it may not apply to every camera in their portfolio, with some lower-cost or SMB/SOHO product being unlisted. Others have only listed the current generations of their equipment. Finally, many lower-cost brands are completely unlisted, limiting their use in some jurisdictions. Users should be aware of these variances when selecting product, and make no assumptions.

In the safety industry, UL listing must be in Detector, Fire Control Panel, MCP, Module, sprinkler, Pump etc. Some OEM follow EN listing of said item for safety i.e., not prone to electrical faults or failures which may cause damage to equipment, facilities, or people.
Listing can generally be found on data sheets, normally in an "approvals" section, though not always. Sometimes it is found only in installation manuals, and other times users must contact the company to get listing information. All these variables make UL compliance a tedious process.
While 'UL Certification' implies electrical safety, the actual standard number it satisfies varies.
For surveillance gear, there are below certification standards that address different safety aspects:
  • UL 60950: Is the most common for cameras, and applies to low voltage safety (ie: non combustibility)
  • UL 1492: Audio/Video Products and Accessories
  • UL 1995: Heating and Cooling Equipment
  • UL 2802: Tests related to performance quality of Camera image quality.
  • UL 2043: Standard for Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces.
  • UL 60065: Audio, Video and Similar Electronic Apparatuses: Safety Requirements
For Life Safety gear, there are below certification standards that address different safety aspects:
·        UL 217: Single- and Multiple- Station Smoke Alarms
·        UL 268: Smoke Detectors for Fire Protective Signalling Systems
·        UL 268A: Smoke Detectors for Duct Application
·        UL 294: Standard for Access Control System Units
·        UL 1023: Standard for Household Burglar-Alarm System Units
·        UL 1610: Standard for Central-Station Burglar-Alarm Units
·        UL 864: Standard for Control Units and Accessories for Fire Alarm Systems
·        UL 1626: Residential Sprinklers for Fire Protection Service
·        UL 1971: Signalling Devices for the Hearing Impaired
·        UL 1741: Inverters, Converters, Controllers and Interconnection System Equipment for Use with Distributed Energy Resources


For Wire and Cable gear, there are below certification standards that address different safety aspects:
·        UL 62: Flexible Cords and Cables
·        UL 758: Appliance Wiring Material (AWM)
·        UL 817: Cord Sets and Power Supply Cords
·        UL 2556: Wire and Cable Test Methods

 

Someone is shopping for a new circuit breaker or contactor; UL certification might sway their decision. If two identical products or services are side-by-side and one is UL certified and one isn’t, which one would you likely choose? It’s been shown that the UL mark can be a powerful marketing tool for businesses, and so many of them strive to get their products approved. The UL logo gives the consumer peace of mind, and the business a public seal of approval.
Whether the UL mark is required on all electrical parts in an installation varies tremendously, depending on the municipality, and even between different inspectors. We have seen various requirements for listing, in different municipalities:
  • No UL listing required: Some municipalities are extremely lenient, never checking any product for UL certification. 
  • Ceiling-mounted products: One of the most arbitrary requirements we have seen is that all ceiling-mounted equipment must be listed, but no other parts of the system were checked. 
  • High-voltage only: In other cases, only high-voltage products require UL listing. This means that electricians are required to comply, but low-voltage security equipment is exempt. 
  • Strict, 100% listing: In the most extreme cases, the building inspector will require every last part of an installation to bear the UL mark, whether it be servers, cameras, cable, or any other components. 
These variations, and others, are why we suggest users should check with their AHJ before installation. In some cases, bids and RFPs may also provide requirements for UL certification, taking the guesswork out of the process.
Since the level of compliance required may vary significantly, it is recommended that users check requirements with the authority having jurisdiction before installation takes place, or even before furnishing estimates.
If unlisted products are being used, but the inspector requires certification, users have two options:
  1. Replace the non-compliant product with compliant. This is often the simplest way to gain compliance. The major downside is, of course, that product must be removed and replaced, incurring additional material, shipping, and labor costs.
  2. Contract UL to provide a one-time certification of the system of the whole. In this case, a UL engineer visits the site and performs testing of the system in place. While this may alleviate listing issues, it is extremely expensive, commonly in the $10,000+ range for even small installations. It is therefore considered a last resort.
UL Certification allows a company to innovate its safety standards and align themselves with industry-wide best practices. Being UL certified illustrates a businesses’ dedication to consumer safety, as well as the quality of their products. Another important caveat of UL certification is for insurance purposes and customer security.

Why is this important? If, say, an inspector determines a fire was caused by a circuit breaker that was not UL certified, an insurance company can choose to deny the claim. For this reason alone, many consumers opt for certified products, not just for large appliances but for small ones as well as laptop and cell phone chargers. UL certification adds a layer of protection and accountability for accidents, as well. UL is a third-party service; consumers of your products can be confident that the UL seal is not a superficial sales ploy. Instead, it’s a true indication of an item’s safety and longevity. It protects brand’s reputation by having an established certification company standing behind what you sell. Remember if you use UL product due to some malfunction you decided to repair your device / panel. Then you must involve said product OEM/ authorised professional. Do not repair through technician / engineer / repairing centre, if you do then UL listing is void. It assumed as zero safety. In case further malfunction or electrical hazard happened then OEM are not responsible for it.
So, don’t immediately assume your products aren’t safe just because it doesn’t have a UL certification. It’s never a bad idea, however, to seek out UL certification when designing into new electronics and appliances.
Even if it might cost a bit more for your business or take extra testing time, UL gives a consumer the peace of mind and a brand a big marketing boost. In the long run, third-party certifications from a trusted source will only help your business. UL Certifications have the ability to add accountability and enhance your brand’s reputation over time.
Hopefully, now you feel a bit more familiar with that little UL logo and have a better idea of what it means and why it’s important for you and your business. When manufacturers are UL certified is shows their continued commitment to safety and quality.
Ready to upgrade your home or workplace with UL certified parts and products? Shop our full assortment of devices, switches, and other electronics.

In the fire alarm and life safety industry, UL (Underwriters Laboratories) is the "gold standard" for reliability. Without it, you are essentially guessing if a life-saving device will work when a building is on fire.

Fire Detection & Signaling System - UL

Product Short Name

UL Standard

Letest Edition

Brand

Model

 Fire Alarm Control Panel 

UL 864

10th

Edwards

EST4  and EDGE

Notifier

INSPIRE  and ONYX Series

Simplex

4100ES, 4010ES, 4007ES

Morley-IAS

STX and SMX Series

Kentec

Taktis

Smoke Detector (Commercial Systems)

UL 268

7th

Edwards

SIGA-OSD

Notifier

FSP-951 Series

Simplex

4098-9754, 4098-9714, 4098-5601

Morley-IAS

HM-PSE-UL-W

Kentec

KSU-OPT-7

Smoke Alarm (Residential Alarms)

 UL 217

8th

Kidde

20SAR (Hardwired), P3010k-CO

First Alert  / BRK

ZCOMBO (Z-Wave), SA304CN3 (with Escape Light), PRC700 (Slim Profile)

Heat Detector

UL 521

8th

Edwards

SIGA-HRD, SIGA-HFD, 281B-PL, 282B-P, SIGA-PHS.

Notifier

FST-951,FST-951R, FST-951H and FST-851, FST-851R

Simplex

4098-9733, 4098-9734, 4098-9754, 4098-9401 / 9402

Morley-IAS

MI-HSE-S2-IV/WH, MI-RHSE-S2-IV/WH, MI-HTSE-S2-IV/WH

Kentec

ATJ-EA, ATG-EA, 55000-400APO, ACC-V

Notification Appliances - hooters, horns, sirens, and bells.

UL 464

 11th

Edwards

EG1-HDVM, EG1H-HDVM, G4AVRF, G4LF Series, 757 Series (Integrity), 860 Series

Notifier

P2RL / P2WL, HRL / HWL, PC2RL / PC2WL, HWL-LF / HRL-LF, P2R / P2W

Simplex

49AO-WRF / 49AO-WWF, 49HF-WRF / 49HF-WWF, 4901-9820

Morley-IAS

System Sensor L-Series, P2RL / P2WL, HRL / HWL, HRL-LF / P2RL-LF

Kentec

GEC3-24WR, P2RL / P2WL, HRL-LF, ASBL-LF,

Notification Appliances - Speakers

UL 1480

7th

Edwards

Genesis LED GCS Series, Genesis GC Series, Genesis G4 Series, 757 Series

Notifier

System Sensor L-Series, SPSWL-LF / SPSRL-LF, SPRK / SPWK,

Simplex

49SO-WRF / 49SO-WWF, 49SOP-WRF / 49SOP-WWF, 49SOC-WRF / 49SOC-WWF

Morley-IAS

System Sensor L-Series, SPSWL-LF / SPSRL-LF, SPRK / SPWK,

Kentec

System Sensor L-Series, SPSWL-LF / SPSRL-LF, SPRK / SPWK,

Notification Signaling Devices for the Deaf and Hard of Hearing

UL 1971

3rd

Edwards

Genesis LED Series, Integrity Series

Notifier

System Sensor L-Series,

Simplex

TrueAlert ES Series

Morley-IAS

System Sensor L-Series,

Kentec

System Sensor L-Series,

Visible Notification  Signaling Devices

UL 1638

6th

Edwards

Genesis Series, Integrity Series

Notifier

SpectrAlert Advance,  System Sensor L-Series,

Simplex

TrueAlert ES Series,  4906-9101

Morley-IAS

SpectrAlert Advance,  System Sensor L-Series,

Kentec

SpectrAlert Advance,  System Sensor L-Series,

Visible Notification  Signaling Devices

UL 1971

3rd

Edwards

Genesis LED (EG1/G4)

Notifier

System Sensor L-Series

Simplex

TrueAlert ES

Morley-IAS

MI-HSR / MI-HSW

Kentec

System Sensor L-Series

Manual Signaling Boxes . MCP , MPS

UL 38

8th

Edwards

SIGA-278 and SIGA-270

Notifier

NBG-12LX

Simplex

4099-9005

Morley-IAS

System Sensor M400K, MI-MCP or F/MCP

Kentec

DCP-AMS

Control, Relay, and Monitor modules.

UL 864

11Th

Edwards

SIGA CT1, SIGA CC1, SIGA CR, SIGA CT2, SIGA MM, SIGA IM

Notifier

FRM-1, FCM-1, FMM-1

Simplex

4090-9001, 4090-9002, 4090-9008, 4090-9117, 4090-9116, 4007-9801

Morley-IAS

HM-D240CMO-UL

Kentec

DCP-FRCME-M, DCP-FRCME-4, DCP-SOM-A, DCP-SCI, K758

Power Supplies

UL 1481

5Th

Edwards

3-BPS/M, 4-PPS/M

Notifier

AMPS-24 / AMPS-24E, HPF24S6 / HPF24S8, FCPS-24S6 / FCPS-24S8

Simplex

4100-5125 / 5126, 4905-9929, 4009-9201 / 9301, 4009-9401

Morley-IAS

 

Kentec

 

 Ref: