Friday, September 1, 2023

Battery Testing - NFPA 72, 2019

Battery Testing - NFPA 72, 2019

NFPA 72 made some significant changes to battery testing requirements in the 2019 edition. Previous editions of NFPA 72 identified types of tests based on the type of battery being tested. Different requirements applied to lead-acid type, nickel-cadmium type, and sealed lead-acid type (the most common type in modern fire alarm systems).

NFPA 72, 2016 Edition, requirements for sealed lead-acid type batteries included replacement based on manufacturer recommendations, charger test to verify proper charging voltage, discharge test to test load test the battery per manufacturer instructions, and a load voltage test to test battery performance under alarm load conditions. The replacement, charger, and discharge tests were required annually, and the load voltage test semiannually.

In the 2019 Edition of NFPA 72 the battery testing requirements were updated to reflect current industry standards and eliminate batteries not commonly used fire alarm systems. The new testing requirements are intended to ensure that fire alarm batteries provide a reliable source of secondary power by focusing on battery replacement, capacity (load) testing, and alternative test methods.

The first thing you may notice is that NFPA 72 changed the term used to describe the most common battery in modern fire alarm systems to a term used by battery manufacturers and the IEEE: VRLA (valve-regulated lead-acid). VLRA batteries are defined in Chapter 3 as a sealed lead-acid cell with a valve that opens when the internal pressure exceeds a set amount. The most common type of VRLA battery is the AGM (absorbed glass mat), where the electrolyte material is held in fiberglass mats that surround the plates.

Before testing the batteries, NFPA 72 requires that the person conducting the test verify that all system software stored in volatile memory is protected from loss. Depending on the system, this may mean ensure that the system is not in programming mode or operating in any condition where normal system operation has not been restored.

A semiannual temperature test is required upon opening the cabinet door. The test needs to be measured at the negative terminal using an infrared thermometer. Any with a temperature greater than 18 degrees F above ambient must be replaced.

A semiannual charger test is conducted with the battery fully charged and connect to the charger. A voltmeter is used to measure the voltage across the battery, and then verified against the equipment manufacturer’s recommendations. If the voltage is outside the limits, the charger must be adjusted or replaced.

A semiannual cell/unit voltage test is conducted with the battery fully charged and connect to the charger. A voltmeter is used to measure the voltage across each cell/unit of the battery. A battery must be replaced if any cell/unit measures a voltage less than 13.26 volts.

Ohmic testing is conducted during initial installation when the battery is installed to establish a baseline ohmic value, and then semiannually to test performance. For the baseline value, data provided by the manufacturer may also be used.

Ohmic testing is a method of testing battery health by measuring the battery’s internal resistant. Typically, ohmic testing uses one of three techniques: conductance, impedance, or resistance to take the measurements.

Ohmic testing is based on Ohm’s Law, which states the relationship between volts, amperes, and ohms in a circuit. Ohmic testing uses the voltage and current to measure the resistive characteristics of the battery’s cells. As batteries age, they degrade and lose capacity. The degradation causes the internal resistance of the battery to increases, decreasing the battery’s ability to accept and hold a charge.

A key part of ohmic testing is establishing a baseline. Every battery has a unique ohmic “signature”, so ohmic testing upon initial installation provides the most accurate measurement. However, if this information is not available, baseline data from the battery manufacturer may be used. Ideally, the ohmic value is tested at least 72 hours after installation to allow the battery to stabilize.

Semiannual testing is conducted with the battery fully charged and connected to the charger. The battery must be replaced when any cell/unit deviate from the established baseline by 30 or more for conductance and 40% or more for resistance or impedance.

A replacement/load test is required every 3 years. The load test requires load testing the battery per manufacturer’s specifications for a discharge rate for 3 hours or more until the terminal voltage decreases to the end voltage specified by the manufacturer. The test duration is used to calculate the battery capacity based on ambient temperature. The battery must be replaced if the capacity is less than or equal to 80%, or at the next scheduled test if capacity is less than 85%. This test is also permitted to be conducted in lieu of an ohmic test.

NFPA 72, A.14.4.3.2 provides more detailed guidelines for ohmic and replacement/load testing.

Q: We have a difference of opinion in our organization that I hope you can settle for us. I believe the sealed lead-acid batteries in our fire alarm system are supposed to be tested per the requirements of NFPA 72 (Charger Test and Discharge Test annually and Load Voltage Test Semiannually). However, another point of view is that, since they're a stored emergency power supply, they're supposed to be tested the same as our Emergency Lights (30-seconds a month and 90 minutes annually). We want to be sure we're in compliance, but we've reached the point where we're turning in circles trying to figure out what we're supposed to comply with. What are your thoughts on this question?

A: Based on NFPA 110-2010, section 3.3.5.1, the definition of a stored emergency power supply system is a system consisting of a UPS or a motor generator, powered by a stored electrical energy source, together with a transfer switch designed to monitor preferred and alternate load power source and provide desired switching of the load, and all necessary control equipment to make the system functional. That does not sound like batteries for a fire alarm system.

The Life Safety Code is the document that governs whenever there is a conflict or a disagreement. Section 19.3.4.1 of the 2012 LSC requires compliance with section 9.6 in regards with the fire alarm system. Section 9.6.1.3 says the fire alarm system must be installed, tested and maintained in accordance with NFPA 72. Table 14.4.5 of NFPA 72-2010 says sealed lead acid batteries used on fire alarm systems must have a charger test and a discharge test conducted annually, and a load voltage test conducted semi-annually. This eliminates any thought that the batteries must be tested monthly.

The requirement to test battery powered emergency lights on a monthly basis is found in section 7.9.3.1.1 of the 2012 LSC, and this applies to emergency lighting systems… Not fire alarm systems. In this situation, you are clearly correct. Tell the others they owe you an ice cream cone for being right.


5 comments:

  1. Firetech fire monitors designed with advanced technology provide the high quality water jet and fog patterns.
    fire fighting equipment

    ReplyDelete
  2. We Have best electrical contractors in lower mainland. Our experience and quality of work represent who we are our and that’s the reason we have represented clients for different projects in our work. Our crew is highly skilled and professional to understand customer needs. Also, we come up with a budget that’s reasonable for the customer and can get the best work out of it. Our company is fully licensed and bonded and all our crew is insured and WCB covered. Fourteen Electrical Ltd. It is a crew of certified electricians that provide customers with all over Lower Mainland and Fraser Valley area.
    local cctv installers lower mainland
    home security cameras installation lower mainland
    security system installation lower mainland
    home alarm systems lower mainland
    residential alarm installation lower mainland
    electrical service upgrade surrey
    Electrician near me
    electrical service upgrade lower mainland
    electric panels
    electrical panel upgrade service
    Low voltage and automation services
    home automation service lower mainland
    Low voltage and automation services
    electrical contractor in lower mainland
    best electrical contractors in lower mainland

    ReplyDelete