Troubleshoot Fire Alarm Ground Faults
What
and Where is a Ground Fault?
If it’s apparent that there truly is a ground, but it is not reporting, either the fire alarm system needs repair or *it has been tampered with by removing a ground jumper on the system.
*Note: On some fire alarm systems, there are jumpers that can be removed to disable ground faults. If this is found to be the case, call for technical help as soon as possible as this can impede the proper operation of the fire alarm system.
Example: If the ground happens to be on a smoke detector circuit, the system may not go into alarm upon activation of a detector. Disabling ground fault function is not only a potential danger to building inhabitants, but it is also against fire alarm codes to leave a system in this condition.
Why technician use the “disable ground” jumper on a
fire alarm system?
In most cases, the ground
disable jumper is used during troubleshooting procedures to silence the panel’s
annunciator while working on the system. The big problem is when a technician,
either purposely leaves the jumper on to “repair” the system or accidentally
leaves it on when finished troubleshooting.
There are times when the
technician has no control over their routing schedule or they forget to return
altogether. Besides, if one leaves the system in this condition, the building
(and its occupants) are left with a faulty system that can cause a false sense
of security. What if there happened to be a real fire and occupants die in a
fire?
If you are a technician,
find a ground fault, and for some reason can’t make the repairs at the time of
your visit, DO NOT disable this feature. Instead, put the appropriate sticker
on the fire alarm panel (describing the problem) and contact building
management authorities immediately.
You’ll sleep better at
night and you’ll also be heading off a potential lawsuit (even jail time, if
more serious).
Why Does a System Develop
a Ground Fault Condition?
What are the causes of a ground fault?
Sometimes they are caused by
poor installation practices, such as attaching wires to all-thread hangers or
building structures above ceiling tiles. After being set in place for a period
of time, natural vibrations in a building can cause the wires to become worn
and eventually touch a ground potential.
Other times grounds can be
caused by other trades working in ceilings. If fire alarm wires are pulled or
accidentally brazed, this can expose the metal conductors of a circuit causing
an unwanted ground or short.
Use an Ohmmeter
Remember, if fire alarm circuit conductors are in contact with the grounded metal raceway or metal junction boxes, the problem will eventually be found using an ohmmeter. One or more circuit conductors will have continuity between it and a reliable grounding point. Finding the ground fault is only a matter of time and patience — and relatively easy to repair.
Multiple
Paths Used
To get a
signal from a device in the field to the control panel, or from the control
panel to a device in the field, the signal sometimes travels down more than one
path. Each path may be classified differently.
A pathway shall be designated as Class A when it performs as follows:
(1) It includes a redundant path.
(2) Operational capability continues past a single open, and the single
open fault results in the annunciation of a trouble
signal.
(3) Conditions that affect the intended operation of the path are
annunciated as a trouble signal.
(4) Operational capability on metallic conductors is maintained during
the application of a single ground fault.
(5) A single ground condition on metallic conductors results in the annunciation of a trouble signal.
A pathway shall be designated as Class B when it
performs as follows:
(1) It does not include a redundant path.
(2) Operational capability stops at a single open.
(3) Conditions that affect the intended operation
of the path are annunciated as a trouble signal.
(4) Operational capability on metallic conductors
is maintained during the application of a single ground fault.
(5) A single ground condition on metallic conductors results in the annunciation of a trouble signal.
If there's more than one control panel in the fire alarm system, these same signals could be sent over Class N pathways, which may involve fiber optics as well as CAT(X) wiring.
Regarding
any of the Classes of pathways (Class A, B, C, D, E, N, X), we as fire alarm
designers, installers, and technicians have to know whether a signal pathway
will allow a ground fault to affect the rest of the fire alarm system.
Coupled
Pathway
When
ground fault troubleshooting, a technician has to understand how various
communication paths work in a fire alarm system.
The pathway signals
can be divided into two groups: Direct Coupled and Indirect
Coupled.
Direct Coupled pathways would be:
·
The
Signaling Line Circuit (SLC)
·
Upload
& Download System Control and Power Loops (Four Wires - Plus, Minus, Send
to Devices, Receive from Devices)
·
RS485
circuit
·
RS232
Circuit
·
Power
Circuit (like for door holders, detectors, control circuits)
· Any other pathway that use copper wires, Like wet contact AHU Tripping, Damper operation control, Door Handling unit, solenoid activation ….. etc.
Indirect Coupled is not electrically
connected or hard wired - There is no electrical connection between any of the
electronic equipment or devices.
Indirect Coupled pathways would be:
·
Radio
Frequency (RF) Coupled like Wireless
·
Magnetically
Coupled (Transformer Coupled) like CAT(x)
·
Optically
Coupled like Fiber Optics
·
Any
other pathway that use copper wires, Like dry contact or through NO/NC AHU
Tripping, Damper operation control, PA Activation, Access Control Deactivation…..
etc.
Continuity
Test
Troubleshooting
Troubleshooting ground faults isn’t much different than troubleshooting any other electrical fault. Use a systematic approach to isolate the problem. In most cases there will be one or more conductors, or even whole circuits, that have made contact with a grounded piece of metal. Always keep in mind when it comes to fire alarm control units indicating a ground fault condition – sometimes a ground fault indication has absolutely nothing to with a grounded circuit. Every now and then there could be another reason — and that reason might be a little unusual – electrically speaking!
To find a
ground fault, the first thing you should do is *remove all wires from the fire
alarm control panel. If the ground trouble goes away, then you’ve ruled out the
possibility that it is not an internal ground within the control panel.
*Note: If you decide to remove one wire at a time instead of follow my advice (and there is actually more than one ground fault), then you may never see the ground trouble go away.
By removing all of the loop cables, you will rule out that the ground fault is not an internal panel ground. If the ground is internal, then you’ll need to replace the fire control panel or components within the panel.
If the
ground does go away, it’s time to break out the ohm meter.
To find a ground, click your meter to the highest continuity setting. Touch one of your meter leads to each conductor (not electrical circuits, of course) while also touching the other lead to a known ground. If installed properly, any electrical conduit is a good source to use as a ground reference.
Since you
are using a highly sensitive meter, make sure you are not touching or holding
any of the exposed wire leads with your fingers or you will skew the results.
Once you have found a ground, tag it and keep checking. Don’t assume this is the only ground fault.
After you’ve determined the source of the ground, it’s time to start troubleshooting in the field. If you have as-built drawings available (I know it’s rare), visually split the circuit in half and go from there.
Continue splitting the circuit into sections or areas until you narrow down the ground. If you find the ground is coming from the fire alarm cable between two devices, it is sometimes easier to simply replace the cable.
By bourn this issue need to counter and workout till it’s not gone.
If you are NOT an electrician or a licensed fire alarm technician, DO NOT attempt to make these repairs yourself. Only qualified personnel should make repairs and troubleshoot energized circuits.
If
you need further help in resolving fire alarm system issues, please contact a
certified commercial fire alarm company or electrical contractor in your area.
Experience
Sharing
There are times when a ground fault indication on the control unit has nothing to do with a grounded circuit. The following is happening with SSA Integrate Engineer.
A fire alarm system with an
intermittent ground fault condition had been giving us fits for two weeks. This
was an older conventional system and did not indicate where the ground fault
was. In the middle of trying to figure out which circuit had the problem the
ground fault indication would go away. This made troubleshooting the problem
even more difficult. We inspected and tested each field circuit looking for any
indication of a ground fault and found nothing. We inspected inside the
junction boxes for bad or damaged conductors. We looked for moisture in the
conduit. We still found nothing. Then we even tried to narrow it down to a
certain time of the day, but there was no consistent time of the day for the
problem.
After two weeks, I happened to remove one of the batteries to clean the enclosure. I noticed there was a wet spot and paint had peeled up leaving a small area of bare metal. I checked the bottom of the battery. The battery had a tiny crack and was leaking a small amount of electrolytic fluid. The fluid would contact the bare metal. There was a complete circuit from the battery charger – through the battery – to the leaky fluid – to the grounded enclosure, which created a ground fault condition. We cleaned it up, replaced both batteries and did not have another issue from that fire alarm system. Luckily, we did not replace the control unit circuit board, as that would have not solved the problem. It was by chance that the problem was resolved.
Another case we want to share,
customer reported Ground Fault trouble showing in there FACP. Standalone FACP
with 3 Loop System no Graphic software no BMS connectivity. Our Engineer visit
and find out once loop 2 cable are opened Ground fault is removed. Now team
just splitting the circuit into sections or areas until we narrow down the
ground. And ultimately found the ground is coming from the fire alarm cable
between two devices, simply we replace the cable.
Another case our engineer found Rubbing
the insulation on a sharp edge. It happened during installation of cooper
cable. Initial time it not effected in loop line. It is the cause of a lowered
insulation/voltage threshold. Even though the insulation is still covering the
copper, it is thinner at that point and the voltage required to push electrons
through the insulation is lowered.
On GST brand fire alarm control panel, on board one jumper is there to disable Ground Fault. Just open jumper to not showing Ground fault in Panel Display.
On Edwards or Notifier or Simplex, all are UL & FM listed panel. They don’t have such option to avoid ground fault.