Replacing FACP Batteries
What's the Correct Way to Note the Battery Date?
CALCULATING BATTERY STANDBY
REQUIREMENTS:
- Disconnect the jumper between the two batteries that normally form
the 24VDC supply. The fire alarm system should annunciate a trouble
condition. (This also happens to be part of the testing criteria!)
- Set your multi-meter for “DC AMPS” and ensure the leads are
connected properly.
- Clamp the RED (positive) lead to the RED (postive) terminal that
the jumper you removed in step 1 was connected to.
- Clamp the BLACK (negative) lead to the BLACK (negative) terminal
that the jumper you removed in step 1 was connected to.
- The fire alarm trouble indication should clear and the system
should appear “normal” in all respects. The current you see
displayed is the nominal charging current being output to the battery (it
should appear as a “negative” number if you’ve connected everything
properly).
- Turn off the circuit disconnect means to the fire alarm
system. The ammeter should now display the system’s supervisory
current (a positive number). DON’T SILENCE THE TROUBLE
INDICATION JUST YET!
- Turn off the circuit disconnect means to the sprinkler heat trace
controller (if provided). The reason for this is that we are
simulating a power failure to the building which means the fire alarm
panel should display all associated troubles and supervisories in order to
accurately measure the supervisory standby current.
- If your meter is equipped with a “MAX/MIN” setting, engage it and
wait for the display to stabilize at the highest current reading.
- Record the reading on your test report.
- Initiate an alarm on the fire alarm system by triggering a device
or zone. Wait for the reading to stabilize.
- Record the alarm current reading on your test report.
- Silence the alarm and trouble signals.
- Turn off the “MAX/MIN” setting on your meter.
- Restore power to the heat trace controllers.
- Reset the system.
- Restore power to the fire alarm system and observe the charging
voltage. It should read higher than the nominal charging voltage you
recorded earlier. This is normal. You will observe that this
reading will drop gradually as the system stabilizes and should return to
the nominal reading you first observed.
- Remove the meter’s leads and restore the connection through the
battery jumper you removed in step 1. (Don’t forget to move the
meter leads back to the normal “voltage” slot on your meter!)
- Take the supervisory current you recorded and multiply by
twenty-four.
- Divide the alarm current by two (if the Code requirement is for 30
minutes of alarm time). Multiply the alarm current by two (if the
Code requirement is for two hours of alarm time).
- Add the results of step 18 and step 19 together and multiply by the
manufacturer’s recommended de-rating factor (this is commonly “1.2”).
- Compare this with the results you’ve obtained by using the
manufacturer’s battery standby calculation form.
- Round up the number you get in step 20 if it’s more than the number
you calculated in step 21 (otherwise use the number you obtained in step
21). This is the MINIMUM battery capacity for the
system under test.
BATTERY SIZE REQUIREMENTS AND MAINTENANCE:
These panels require a 24 volt gel-cell battery for proper operation.
24 hours of standby power is required for Local Systems and Central Station
(NFPA-72).
The chart below will assist you in selecting the proper size battery:
(Does not include LED Annunciator)
Nice blog!
ReplyDeleteAre you searching for a service center in Dubai for your Macbook?? Scorpionfix is here, one of the best Apple service center in Dubai.
Surface pro 8 repair in Sharjah
Surface pro service center Sharjah
Surface pro service center Dubai
Macbook repair in Sharjah
Macbook repair in Dubai.
Laptop repair in Dubai
Laptop repair in Sharjah
Surface pro 8 repair in Dubai
macbook service center abu dhabi
macbook repair abu dhabi
Laptop repair abu dhabi
Laptop service center abu dhabi
Apple service center Sharjah