Smoke Detector above Fire Alarm Panel
based on NFPA 72 2013
A question we see coming
up more often is in regards to smoke detection above fire alarm control units. The
specific questions is, "Are you required to install a smoke detector above
the fire alarm control unit (FACP) or fire alarm control panel (FACP)?".
Simply put the answer is YES and can be supported by the language found in NFPA
72 2013 edition section 10.4.4. (Page #65). This sections states the
following:
"In areas that are not continuously occupied, automatic smoke detection
shall be provided at the location of each fire alarm control unit(s),
notification appliances circuit power extenders, and supervising station
transmission equipment to provide notification of fire at that location.
Exception: Where ambient conditions prohibit installation of automatic smoke
detection, automatic heat detection shall be permitted."
Also note there is an Annex section related to this reference.
A.10.4.4 states that the equipment to be covered by this automatic smoke
detection is a fire alarm control unit that is used to notify
occupants and responders of a fire.
Here are a few other key items to keep in mind when dealing with this topic:
·
The term Fire Alarm
Control Unit (FACP) does NOT include annunciators or addressable devices.
·
If the area where the FACP
is located is continuously attended, a smoke detector is NOT required.
Keep in mind this is not intended for lobbies or offices where there are
occupants coming and going throughout the day. This is intended for areas
such as lobbies with 24/7 security and security rooms where at least one guard
is in attendance at ALL times.
·
If the area where the FACP
is located has full coverage smoke detection, then an additional smoke detector
dedicated to the FACP is NOT required.
·
If the single smoke
detector intended to protect the FACP per 10.4.4 does not cover the entire
space where the control equipment is located, then additional smoke detection
is NOT required.
Now here is were it may
become confusing for the designer or AHJ. Section 10.4.4 as well as
A.10.4.4 clearly state that the FACP to be protected is a control unit that is
in place to notify occupants and first responders of a FIRE. As you may
or may not be aware of, there are additional systems we deal with in this
industry known as Dedicated Function Fire Alarm Systems.
Building Fire Alarm System vs. Dedicated Function Fire Alarm
System
As defined by NFPA 72
2013 edition Section 3.3.105 (page #24)
Building Fire Alarm
System. A protected
premises fire alarm system that includes any of the features identified in
section 23.3.3.1 and that serves the general fire alarm needs of a building or
buildings and that provides fire department or occupant notification or both.
Dedicated Function Fire
Alarm System. A protected
premises fire alarm system installed specifically to perform emergency control
function(s) where a building fire alarm system is not required.
Here is the code section
that indicates when a Dedicated Function Fire Alarm Alarm Systems can
be installed in place of a building fire alarm system per NFPA 72 2013 edition
section 23.3.3.2.1.
"In facilities
without a building fire alarm system, a dedicated function fire alarm system
shall be permitted and shall not be required to include other functions or
features of a building fire alarm system."
The two most common
dedicated function fire alarm systems typically used are:
·
Dedicated
function sprinkler monitoring system: This is a system installed when a particular building does
not require a building fire alarm system BUT still has an automatic fire
sprinkler system employing more than 20 heads. Example could be a small
strip mall (Group M) with under 100 occupants but more than 20 sprinkler
heads. Although this system is not in place to notify occupants or
responders of a fire, a smoke detector is required above the panel since this
system is in place to monitor the sprinkler system. Per NFPA 72 2013
section 10.4.4 a smoke detector is required to protect "supervising
station transmission equipment".
·
Dedicated
function elevator control system: This is a
system installed strictly and specifically to control the emergency functions
of an elevator such as elevator recall and shunt trip. These systems
will typically have your elevator lobby/equipment room smoke detectors, heat
detectors, relays and modules to perform the emergency control functions found
in NFPA 72 2013 chapter 21. Note this system would not be required to be
monitored as it is not in place to monitor the status of an automatic sprinkler
system. In this case a smoke detector is NOT required above the
control unit as it is not monitored nor is it in place to notify occupants or
responders of a fire.
FACP Smoke Detector Installation Location
NFPA 72 2013 Smoke Detector Mounting
Diagram
|
Pay attention to your
applicable code as the installation location of this smoke detector
changed
between NFPA 72 2010 and 2013 editions.
NFPA 72 2010 (A10.15 #1 and #2) state if the ceiling height is 15'
or less, the smoke detector shall be installed on the ceiling or wall within
21' of the centerline of the FACP. If the ceiling height exceeds 15', the
smoke detector should be installed on the wall no more than 6' above the top of
the FACP.
NFPA 72 2013 (A10.4.4) states the smoke detector shall be installed
in accordance with section 17.7.3.2.1. Section 17.7.3.2.1 states "Spot-type
smoke detectors shall be located on the ceiling or, if on a sidewall, between
the ceiling and 12 inches (300 mm) down from the ceiling to the top of the
detector."