HyperTerminal Settings For Fire Alarm Control Panels

HyperTerminal Settings For Fire Alarm Control Panels

Hyperterminal is a great way to connect to a fire alarm control panel(FACP).  It is also the preferred method to achieving a fire alarm control panels device parameters f you cannot access the program.  Simply connect your laptop to the fire alarm control panel with the appropriate cable and enter the correct values for HyperTerminal.  Once in, your laptop will mimic the FACPs screen or display.  From here you can capture the text file making it easy to store fire alarm testing reports and device parameters.

Here is a little trick if you need to know exactly what devices are on each loop.  While connected with Hyperterminal, pull off each SLC circuit one at a time.  Your laptop screen will then start to display every device on that loop as they go into trouble due to the lack of communication with the FACP loop card.  Capture the text file and your done.  You now have a simple starting plan to re-write a program if necessary.

Below are some of the HyperTerminal settings I have come across:

Notifier Fire Warden Series FACP: Includes NFW2-50 and NFW2-100
1.           Start HyperTerminal from its Start Menu icon.
2.           Give the connection a name (for example, Fire Warden) and select any icon that you’d like. Click OK to continue.
3.           In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
4.           Set your parameters as follows:
·                  Bits per second: 19200
·                  Data bits: 7
·                  Parity: Even
·                  Stop bits: 1
·                  Flow Control: None
5.           Click OK.
6.            You are now connected to the panel.

Fire-Lite Series FACP: Includes MS-9200, MS-9600, MS-9200UDLS, MS-9600UDLS
1.           Start HyperTerminal from its Start Menu icon.
2.           Give the connection a name (for example, Fire-Lite) and select any icon that you’d like. Click OK to continue.
3.           In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
4.           Set your parameters as follows:
·                  Bits per second: 19200
·                  Data bits: 7
·                  Parity: Even
·                  Stop bits: 1
·                  Flow Control: None
5.           Click OK.
6.           You are now connected to the panel.

Gamewell 600 Series FACP: Includes the IF610, IF602, IF650, IF630
1.           Start HyperTerminal from its Start Menu icon.
2.           Give the connection a name (for example, 600) and select any icon that you’d like. Click OK to continue.
3.           In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
4.           Set your parameters as follows:
·                  Bits per second: 2400
·                  Data bits: 8
·                  Parity: None
·                  Stop bits: 1
·                  Flow Control: Xon / Xoff
5.           Click OK.
6.           Select the pull down file menu at the top of the screen
7.           Select properties
8.           Select settings tab
9.           Set emulation to VT-100
10.        Select ASCII setup
11.        Change the line display setting to 1 milliseconds
12.        Change character display setting to 100 milliseconds
13.        Click OK twice
14.         You are now connected to the panel.

FCI E3 Series FACP:
1.           Start HyperTerminal from its Start Menu icon.
2.           Give the connection a name (for example, E3) and select any icon that you’d like. Click OK to continue.
3.           In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
4.           Set your parameters as follows:
·                  Bits per second: 115200
·                  Data bits: 8
·                  Parity: None
·                  Stop bits: 1
·                  Flow Control: None
5.           Click OK.
·                  You are now connected to the panel.

FCI 7100 Series FACP:
1.           Start HyperTerminal from its Start Menu icon.
2.           Give the connection a name (for example, 7100) and select any icon that you’d like. Click OK to continue.
3.           In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
4.           Set your parameters as follows:
·                  Bits per second: 9600
·                  Data bits: 8
·                  Parity: None
·                  Stop bits: 1
·                  Flow Control: None
5.           Click OK.
7.           You are now connected to the panel.

FCI 7200 Series FACP:
1.           Start HyperTerminal from its Start Menu icon.
2.           Give the connection a name (for example, 7200) and select any icon that you’d like. Click OK to continue.
3.           In the “Connect Using” section, select the appropriate COM port that you’d like to use to communicate with the panel. Click OK after the selection has been made.
4.           Set your parameters as follows:
·                  Bits per second: 1200
·                  Data bits: Leave Default
·                  Parity: Leave Default
·                  Stop bits: Leave Default
·                  Flow Control: None
5.           Click OK.
6.           You are now connected to the panel.


8 comments:

  1. Amazing blog

    I like the way you design it. But, I always recommend being precautioned as a Safety professional by learning all the fire safety skills from Fire safety courses in Chennai @Nationalsafetyschool.com. If you're interested in such kinda stuff, feel free to check out it. Thank you!

    NEBOSH Course in Chennai

    Fire and Safety Course in Chennai

    IOSH Course in Chennai

    ReplyDelete
  2. Residential Video Intercom Systems to add convenience and safety at your front door or gate. UnikCCTV provide best in class video camera come with video screens integrated into both the intercom box itself, as well as at stations. This allow resident to see who at the gate. even for office we provide CCTV security system, contactless doorlock, intercom for office and more.

    ReplyDelete
  3. Explanation, this exegesis is a clean culmination which often typically is aware of this activate's episode of a situation location. Think of your document in an didactic placing is actually known because "official book" is usually soporific by disciples, academy trees, flicker analysts to do the tasks. steel door

    ReplyDelete
  4. If you are searching for well secure security system for your building or apartment or even for your office. UnikCCTV offers you wide range of security system for example CCTV system, contactless door system, Building Intercom Systems, and surveillance hardware

    ReplyDelete
  5. Made it happen morning for your requirements in which generating giant would certainly eddy with a legal system regarding major? Our own bureau thought acquire someone to during that goal. Ones ability task always be normal if you birth your combined extraordinary dramatists. Many of us admit balk bivouac for you to choice your own style means. Match furthermore loved ones you.... fire door

    ReplyDelete