Showing posts with label Fire Alarm. Show all posts
Showing posts with label Fire Alarm. Show all posts

Saturday, January 2, 2016

Initiating Devices – Heat Detectors

NFPA 72 Chapter 5 Initiating Devices – Heat Detectors

This is a continuation on the series of articles about the most important requirements in NFPA 72 National Fire alarm Code Book. Make sure to read the first article NICET Study Guide – NFPA 72 Chapter 4 Fundamentals of Fire Alarm. In this articles I will discus Heat Detectors and give you the most important code requirement that you must know about for the exam.
General Requirements  for all types of initiating devices:
·        Initiating devices shall only be installed in accessible locations.
·        Initiating devices shall be protected if they are exposed to mechanical damage.
·        A mechanical guard shall be listed for use with the detector.
·        Initiating devices shall be supported by another means besides their own conductors.
·        Initiating devices shall be installed in a manner to allow for regular maintenance.
·        Duplicate terminals shall be provided on the detectors for monitoring the wires for integrity.
·        Heat & Smoke Detectors Shall not be recces mounted unless they are listed and tested.
·        In a non required application where detectors are installed to achieve specific fire safety objective, additional detectors shall not be required throughout.
Heat Detectors General Requirement

·        Heat detectors shall be classified by the temperature of operation and marked with a color code according to the following table
Temperature Classification
Temperature Rating
Max Ceiling Temp
Color Code
Low
100-134 F
80 F
Unclolored
Ordinary
135-174 F
115 F
Uncolored
Intermediate
175-249 F
155 F
White
High
250-324 F
230 F
Blue
Extra High
325-399 F
305 F
Red
Very Extra High
400-499 F
380 F
Green
Ultra High
500-575 F
480 F
Orange
·        Heat detectors shall be marked with the listed operating temperature.
·        Spot type heat detector shall also be marked with the response time index.
·        Combination heat smoke detector shall be listed for no less than 50ft spacing.
Location of Heat Detectors
·        Ceiling mounted heat detector shall be located not less than 4 inch from side wall
·        Sidewall mounted heat detector shall be located between 4 and 12 inches from the ceiling.
·        Line type heat detector shall be mounted within 20 feet from the ceiling.
·        In a solid joist construction heat detectors shall be mounted at the bottom of the joist.
·        In beam construction detectors can be mounted on the bottom of the beam if the beams are less than 12 inches deep and less than 8 inches on center.

Spacing of Heat Detectors
Smooth Ceiling
·        Any point on the ceiling shall have a detector within 0.7 times the listed spacing.
·        Distance from a detector to a wall shall not exceed 1/2 of the listed spacing.
·        Heat Detectors Shall not Exceed their listed spacing.
·        In irregular areas spacing of heat detector is permitted to be more than listed spacing, provided that it should be within 0.7 time the listed spacing from a wall.
Beam Construction
·        The ceiling shall be treated as a smooth ceiling if the beam is less than 4″
·        When beam is more than 4″ spacing shall be no more than 2/3 of smooth ceiling spacing.
·        When beam project more than 18 inches from ceiling and more than 8 feet on center. than these pockets shall be treated as a separate areas.
Sloped ceiling
·        The first row of detector in sloped ceiling shall be within 3 ft of the peak.
·        If the slope is less than 30 degrees, detectors shall be spaced using the height at the peak.
·        If the slope is more than 30 degree, then the average slope height shall be used except the first detectors on the peak.
High Ceiling
·        On ceiling between 10 feet and 30 feet high, the spacing shall be reduced according to table below.
·        The minimum spacing shall not be less than 40% the height of the ceiling
Ceiling Height Above (Feet)
Up to and Including (Feet)
Multiply Listed Spacing By
0
10
1.00
10
12
0.91
12
14
0.84
14
16
0.77
16
18
0.71
18
20
0.64
20
22
0.58
22
24
0.52
24
26
0.46
26
28
0.40
28
30
0.34
This post should be part of your study guide for NICET Level 1 and Level 2. Please pay attention to the two tables above, they are table 5.6.2.1.1 and 5.6.5.5.1 on pages 72-39 and 72-40 respectively, make sure to label these sections. I am sure that these tables are good candidate for questions on the exam. I will discuss the requirement of smoke detectors and other initiating devices in upcoming post.  as always please let me know in the comment area below on what you think about this post and what would you like to see in future articles.
Cheers!!
  • Types of initiating devices include:
    • Manual fire alarm boxes / Manual Pull Station / Manual Call Point
    • Smoke detectors
    • Heat detectors
    • Flame detectors
    • Sprinkler waterflow detectors
    • Switches indicating actuation of fire suppression systems
    • Valve supervisory devices
    • Pressure supervisory devices
    • Level supervisory devices

Saturday, October 5, 2013

Changes to NFPA 13

13 Changes to NFPA 13

As the newest edition of NFPA 13 is set to be presented next month, NFPA has published some of the notable changes to this document:
1.               CPVC compatibility - where corrosion inhibitors are used in combination systems that include coated steel pipe and CPVC pipe, the coating must be tested for compatibility with CPVC.
2.               Freeze protection requirements - tentative interim amendments regarding antifreeze solution to prevent the freezing of water in sprinkler pipes has been formally adopted into the standard
3.               Sprinkler requirements for elevator spaces and hoistways - allows fire sprinklers to be omitted from elevator machine rooms, elevator machinery spaces, control spaces, or hoistways of traction elevators where a number of conditions are met, and brings the standard in alignment with other model building codes
4.               Title change to NFPA 13R - Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies
5.               Sprinkler protection in small bathrooms - Apartment buildings with bathrooms less than 55 square feet (5 square meters) must now have sprinkler protection where they were not  previously required to do so.
6.               Shadow areas -  shadow areas are permitted in the protection area of a sprinkler as long as they do not exceed 15 square feet per sprinkler.
7.              
"Sprinkler system" definition - modified to describe a system as an integrated network of piping that includes a water supply source, a water control valve, a water flow alarm, and a drain; this largely effects the requirements of 
NFPA 25.
8.               Backflow preventer requirements - a forward flow test will now be required on allNFPA 13/13R installations.
9.               Storage chapter - newly added; allows for an alternative design approach.
10.            Sloped ceilings - provides five common ceiling arrangements that allow for hydraulic calculations
11.            Water mist systems - refers users to NFPA 750.
12.            Cloud ceilings - protection to follow the use of obstruction rules.
13.            ESFR and CMSA sprinklers - these will now be permitted to protect light and ordinary hazard areas.