Portable Fire Extinguishers: Maintenance, Use,
Placement and Testing
Qualified, well trained, and
experienced professionals only should carry out inspection and maintenance of
fire Extinguisher. Please check professionals valid experience details (Like: Appreciation
Letter, PO copy’s including End user details..etc.) and qualification before assign
job.
Fire Extinguisher inspection and
maintenance done by Qualified, well trained, and experienced professionals will
give you the reliability in quality inspection and maintenance.
Where Should a Fire Extinguisher Be Located?
OSHA requires
employers to select and distribute fire extinguishers based on the classes of
anticipated workplace fires and also on the size and degree of the hazard,
which would affect their use. The following chart contains the OSHA-specified
maximum travel distances to an extinguisher by fire class.
Fire Class
|
Travel Distance
|
Class A
|
75 feet
|
Class B
|
50 feet
|
Class C
|
Based on appropriate
A or B Hazard
|
Class D
|
75 feet
|
According to NFPA 10,
the travel distance to a Class K fire extinguisher must not exceed 30 feet.
Maintenance, Inspection and Testing
Employers must
inspect, maintain and test all portable fire extinguishers in accordance with
29 CFR 1910.157(e) and (f).
How Do You Inspect a Fire Extinguisher? OSHA
Regulations for Visual Inspection
Portable fire
extinguishers must be visually inspected monthly per 29
CFR 1910.157(e)(2). This helps ensure that:
·
The
extinguishers are in their assigned location
·
No
damage has occurred
·
No
obstructions are blocking the extinguishers from view or easy access
·
Extinguishers
are fully charged and operational
·
Pressure
gauges show adequate pressure
·
Pin
and seals are in place
·
Nozzles
are free of blockage
Fire Extinguisher Maintenance Requirements
A thorough
examination of a Fire Extinguisher internally and externally that includes
checking of extinguishing agents, gas cartridges, repair and replacement of
damaged components, and carrying out oiling, greasing, and wiping wherever
required of a fire extinguisher is known as Fire Extinguisher maintenance.
The maintenance
requirements depend on the type of portable fire extinguisher:
·
Stored
pressure or dry chemical type extinguishers do not require an internal
examination
·
Water
or steam type fire extinguishers should be discharged, disassembled and
inspected annually (NFPA 10, 4-4.1.1)
·
Dry
chemical extinguishers that require a 12-year hydrostatic test are required to
be emptied and subjected to applicable maintenance procedures every six years.
·
Non-refillable,
disposable dry chemical extinguishers are exempt from this requirement (29 CFR
1910.157(e)(4))
For additional fire
extinguisher maintenance, follow the manufacturers’ suggested maintenance
procedure.
Fire Extinguisher Maintenance
Procedure:
Frequency: Frequency for maintenance of Indian
Fire Extinguishers and American Fire Extinguishers are as below:
Quarterly For Indian Fire Extinguishers (Once in
every 3 months)
Annually For American Fire Extinguishers (Once
in every 12 months)
Responsibility: Owner/ Employer/ Appointed
Agency/Appointed Occupant of the property.
While performing maintenance of Fire Extinguishers, please
consider maintaining mechanical parts, extinguishing agents, expelling media,
and physical condition of Fire Extinguishers.
Follow the steps
given below for maintaining Fire Extinguishers:
·
Clean the Fire extinguisher
properly.
·
Polish the exteriors of Fire
Extinguisher.
·
Wash the plastic components of Fire
Extinguishers with soap water.
·
Check the porthole, vent hole, and
nozzle of the extinguishers are clear. If holes are jammed, clear it.
·
Check for the free movement of the
plunger.
·
Ensure that the cap washer and
discharge tube washers are intact.
·
Grease the threads of the cap,
plunger, and wipe clean.
·
Check the pressure gauge is showing
the correct pressure of the store pressure Fire Extinguisher.
·
Examine the cap assembly, valve
assembly, discharge hose, siphon tube, and clean it.
·
Don’t open stored pressure Fire
Extinguisher your own, the opening may injure you due to high pressure inside
it. It is recommended to get the stored pressure Fire Extinguisher servicing
done through only professional agencies.
·
Open DCP Fire Extinguisher (only
cartridge type) in dry weather only and avoid moisture contact with the powder.
Contacting moisture with powder causes cake formation.
·
Check for cake formation in DCP
powder. If caking is there, replace the powder.
·
Never mix different types of DCP
Powders (ABC/BC/TEC). Mixing different types of powders may cause a chemical
reaction that results in a dangerous pressure build-up inside the Fire
Extinguisher.
·
Shake DCP fire extinguishers well
to change the position of the powder to maintain its free-flowing properties
and avoid caking formation.
·
Weigh the CO2 Gas cartridge,
if gas weight loss is more than 10%, replace the CO2 gas cartridge with a
filled one. Send the less weight CO2 gas cartridge for recharging.
·
Weigh the CO2 Fire
Extinguisher, if the gas loss is more than 10%, replace the Fire Extinguisher
with a filled one. Send the less weight Fire Extinguisher for recharging.
·
Check the pressure gauge of stored
pressure Fire Extinguisher, if it shows pressure loss of more than 10%, refer
to the manufacturer’s instruction for further action.
·
Weigh the stored pressure Fire
Extinguisher or use alternate means to check that it contains the correct mass
of extinguishing agent.
·
Clear the discharge hose by blowing
air inside it.
·
Ensure that the maintenance tag is
available, update the maintenance date, signature on the maintenance tag.
·
Record the status of checks in the
checklist and rectify the actionable items.
Fire
Extinguisher Discharge/Performance Test Procedure:
Frequency: Annually (Once in every 12 Months)
Responsibility: Owner/ Employer/ Appointed
Agency/Appointed Occupant of the property.
Follow the steps
given below for Annual Performance Test/ Discharge Test of Fire
Extinguishers:
- · Check the Fire Extinguisher internally and externally to find out any physical damage or corrosion formations.
- · Check the painting condition of Fire Extinguisher.
- · Check the quality of extinguishing agents.
- · Check the tightness of all joints of Fire Extinguisher.
- · check the condition of the information label.
- · Check the jet length of Fire Extinguishers against the given parameters.
- · Check the discharge duration of Fire Extinguishers as per the given parameters
- · Check the discharged quantity in the percentage of Fire Extinguishers as per the given parameters.
- · Record the date, signature, and status of the performance test in the checklist. Rectify the actionable items.
Hydrostatic Fire Extinguisher Testing
Hydrostatic testing
of portable fire extinguishers is done to help protect against unexpected
in-service failure. This can be caused by internal corrosion, external
corrosion and damage from abuse, etc. Hydrostatic testing must be performed by
trained personnel with proper test equipment and facilities. OSHA requires
hydrostatic testing according to the following schedule:
Type of Extinguisher
|
Test Interval (Years)
|
Soda acid
(stainless steel shell)
|
05
|
Cartridge operated
water and/or antifreeze
|
05
|
Stored pressure water
and/or antifreeze
|
05
|
Wetting agent
|
05
|
Foam (stainless
steel shell)
|
05
|
Aqueous Film
Forming Foam (AFFF)
|
05
|
Loaded stream
|
05
|
Dry chemical with
stainless steel
|
05
|
Carbon dioxide
|
05
|
Dry chemical,
stored pressure, with mild steel, brazed brass or aluminum shells
|
12
|
Dry chemical,
cartridge or cylinder operated, with mild steel shells
|
12
|
Dry powder,
cartridge or cylinder operated with mild steel shells
|
12
|
For each extinguisher
that is hydrostatically tested, the employer must keep a record that includes:
·
The
name of the person or agency who performed the last hydrostatic test, and the
test date.
·
The
signature of the person who performed the test.
·
The
serial number or other identifier of the fire extinguisher that was tested.
This information
should also be securely affixed to the tested extinguisher. These records must
be kept until the extinguisher is hydrostatically re-tested or until the
extinguisher is taken out of service, whichever comes first.
Indian Standard IS 2190-2010 indicate Fire Extinguishers Selection, Installation and Maintenance.
PESO Approval To Recharge and HPT Testing
of High-Pressure Fire Extinguishers:
Fire
Extinguishers which refill and HPT pressure is more than 35 kgf/cm2, recharging
and the HPT test is required to be done through those agencies which are having
valid PESO (Petroleum And Explosive Safety Organisation ) license.
Obtaining
these certificates means the organization is the complaint with the
requirements of PESO.
PESO was
known as CCOE (Chief Controller of Explosives) before 2010.
In 2010
CCOE name was transformed into PESO. The CCOE head office is in Nagpur,
Maharashtra, India.
Certificates to be taken from the Servicing/testing
Agency:
When you
are sending your fire extinguishers for refilling, maintenance, and testing to
any external agency, do you know what important things that you need to collect
from the agency?
Collect the following things from the Agency:
·
Collect a copy of the PESO
certificate.
·
Collect Refilling Certificate in
the case of Refilling Services.
·
Collect Hydro Pressure Testing
Certificate in case of HPT Services.
·
Collect maintenance certificate in
case of maintenance services.
·
Collect a valid calibration
certificate of weighing machine from which weighment of Fire Extinguishers has
been done.
·
Ask to emboss/ paint HPT done date
and due date on the body of the Fire Extinguisher.
Spares/ Refills
To Be Kept In Stock:
It is important to keep 10% each type of refills
reserve in the stock to replace the empty Fire Extinguishers immediately at the
site so that, you get enough time to recharge empty Fire Extinguisher without
hampering the services.
Weigh Scale For
Fire Extinguisher:
It is important to keep a suitable size of weighing scales
separate for weighment of CO2 gas cartridge and for Fire Extinguishers to
get accuracy.
Weighing scale required for carrying out quarterly
maintenance of Fire Extinguishers.
Fire Extinguisher shall be calibrated in a timely manner to
get accurate weight and calibration certificate to be kept in a file safely to
show in audits.
When To Replace
Fire Extinguishers:
Fire Extinguishers should be
replaced in the following conditions:
·
If there is any physical damage or
rusting found on the body of Fire Extinguisher.
·
If Fire Extinguisher weight loss is
more than 10%.
·
If Fire Extinguisher body is
leaking.
·
If Fire Extinguisher pressure gauge
needle is in the red zone (low-pressure side).
·
If Fire Extinguisher is
overpressure, the pressure gauge needle is in the red zone (high-pressure
side).
Condition To Reject A Fire Extinguisher:
Fire Extinguisher that are failed in HPT, body
damaged, lifetime is over, etc. are required to reject immediately.
If observed, such Fire Extinguishers shall be immediately
removed from the site for rejection immediately and suitable replacement in
terms of type and capacity shall be provided from Fire Extinguishers kept in
stock.
How To Scrap A Fire Extinguisher?
Rejected Fire Extinguishers shall be cut centrally across
the body and will be made unusable before its disposal to prevent its
subsequent use.
The date of rejection and mode of disposal should be
recorded in the Fire Extinguisher register to keep proper tracking of Fire
Extinguishers.
Note: Before
cutting the Fire Extinguisher, ensure there is no pressure remain inside it to
avoid any injury due to pressure.
So ensure zero pressure inside it and keep the valve open to
release the residual pressure of Fire Extinguisher while cutting it.
The benefit of keeping the valve open of Fire Extinguisher
while cutting, it releases the pressure that is build-up whilst cutting
process.
This is really helpful and informative, as this gave me more insight to create more ideas and solutions for my plan.keep update with your blog post.
ReplyDeleteISO 45001 Certification
Fire Extinguisher Maintenance is very important for the proper working of fire extinguisher
ReplyDeleteRegards
Fire fighting equipment in Pakistan
I am really impressed with your blog article, such great & useful knowledge you mentioned here.
ReplyDeleteYour post is very informative. I have read all your posts and all are very informative. Thanks for sharing and keep it up like this.
fire alarm systems for commercial buildings in Maharashtra
Thank you for Sharing best Useful information !!!!
ReplyDeleteMachine Learning Training in Bangalore
Data Science Course in Bangalore
NFPA 10 - Extinguishers
ReplyDeleteDistribution of manual fire extinguishers to sites containing materials leading to type B fires
* Class B fire hazards are divided into two categories:-
1. Includes liquids with a depth of (6.4 mm) or less.
2- Includes liquids deeper than (6.4 mm).
1. In areas where liquids do not reach a depth of more than 6,4 mm, fire extinguishers shall be provided in accordance with Table 17.5.4 in the Annex.
The reason the maximum walking distance for Class B extinguishers is 50 feet (15 meters), versus 75 feet (23 meters) for Class A extinguishers, is that flammable liquid fires reach their maximum intensity almost immediately, and therefore extinguishers should be closer and within range.
If using low-rated fire extinguishers, the walking distance is reduced to 30 feet (9 m). The closer the fire extinguishers, the better.
2) In areas where flammable liquids reach a depth greater than 6.4 mm, the classification number of the fire extinguisher shall be at least twice the number of square feet of the surface area of the largest tank in the region, excluding the foam-type extinguisher.
100 ft2 tank = Extinguisher required 200B
Table 4.5.17 is also used to determine the walking distance of fire extinguishers to protect against localised hazards.
Sometimes a single fire extinguisher can be installed to provide protection for many different hazards as long as the walking distance is not exceeded.
In the case of open flammable liquid tanks with surface areas greater than 10 square feet (1 square meter), fire extinguishers should not be completely reliable, it is often recommended to install fixed fire protection systems for these tanks due to the size and severity of possible fires.
If a fixed protection system is used, the fire extinguisher may be dispensed for the area that has been protected by a fixed system and not for all locations.
Manual fire extinguishers can be useful even when we use a stationary protection system, in the event of a spill of liquid from the burning tank out of reach of fixed equipment or a fire starts near the tank and not in it.
A high-rated extinguisher may not be replaced by two or more lower-rated extinguishers, except for the type of foam.
2 x Extinguisher 10B ≠ 1x Extinguisher 20B
3) Fire extinguishers on wheel with ratings from 20B to 480B, designed primarily for outdoor firefighting, and should only be used by trained personnel, should be distributed according to walking distance rules
Maximum distance of 50 feet (15 meters) from Table 17.5.4
Nice blog!
ReplyDeleteAre you searching for a service center in Dubai for your Macbook?? Scorpionfix is here, one of the best Apple service center in Dubai.
Surface pro 8 repair in Sharjah
Surface pro service center Sharjah
Surface pro service center Dubai
Macbook repair in Sharjah
Macbook repair in Dubai.
Laptop repair in Dubai
Laptop repair in Sharjah
Surface pro 8 repair in Dubai
macbook service center abu dhabi
macbook repair abu dhabi
Laptop repair abu dhabi
Laptop service center abu dhabi
Apple service center Sharjah