Voltage on the Notification Appliance Circuit (NAC)
Notification Appliance
Circuit (NAC) -- Two Conditions
When servicing the fire alarm system, it's the difference between the two conditions that cause problems for the technicians.
Wires from a Notification Appliance Circuit (NAC) are
connected plus to +and minus to -. The trouble is that
when measuring the voltage polarity on the wires during non-alarm times, the
measured polarity is wrong for the horn or strobe.
In May 2004, Underwriters Laboratories (UL) revised UL
1971, standardizing operating current measurements to provide uniformity among
manufacturers. They now require strobe operating current to be measured using
root mean square (RMS) rather than peak and average values, and surge currents
must be maintained within levels that the system power supply can tolerate. The
operating current must be measured at the voltage where the current draw is at
its maximum. By and large, these requirements have been implemented by the
industry. However, confusion is present across the fire industry because
current draws can no longer be specified at the nominal operating voltage of
the system.
Alarm Condition
To sound the alarm, the fire alarm panel's
Notification Appliance Circuit gets people's attention (Notification) using
devices like horns, chimes, bells, and strobes (Appliance), and does this by
applying power over the building's wiring (Circuit).
Normal - Not Alarm
Condition
Then again, under normal circumstances, to supervise the
building's wiring, the panel uses a supervision voltage to drive
electrical current through the same circuit.
Voltage Powers the Devices
There's a problem with the devices, though; when power is
on -- they're turned on, when power is off -- they're turned off. The horns,
bells, chimes, and strobes don't have switches, they're really simple
devices.
Turning on the voltage turns on the horns and strobes, but voltage is also used to supervise the wiring. Because this is all sent over the same wires, the voltage is always on.
There has to be a way for the devices to tell the difference between the alarm condition, when alarm voltage is applied to their terminals, and the normal condition, when supervision voltage is applied to their terminals.
NAC Voltage Reversal
Turning on the voltage turns on the horns and strobes, but voltage is also used to supervise the wiring. Because this is all sent over the same wires, the voltage is always on.
There has to be a way for the devices to tell the difference between the alarm condition, when alarm voltage is applied to their terminals, and the normal condition, when supervision voltage is applied to their terminals.
NAC Voltage Reversal
To solve this problem, the voltage produced by the panel
on the NAC isn't just turned on and off. When the NAC in alarm, the voltage is
forward; when the NAC is supervising the wiring, the voltage is reversed.
Polarity Sensitive Device
Polarity Sensitive Device
In order to react to this polarity reversal, the horn or
strobe has an internal diode, making the device polarity sensitive.
When the voltage is forward (positive voltage applied to the + terminal of the device) the diode conducts and horn or strobe is on; when the voltage is backward (negative voltage applied to the + terminal of the device) the diode blocks the current and the horn or strobe is off.
Polarity Voltage Problems
When the voltage is forward (positive voltage applied to the + terminal of the device) the diode conducts and horn or strobe is on; when the voltage is backward (negative voltage applied to the + terminal of the device) the diode blocks the current and the horn or strobe is off.
Polarity Voltage Problems
The problem we have for the technician, though, is under
normal circumstances, the polarity of the voltage on the wires of the NAC is
backward.
Many times, before connecting the wires to the horn or strobe, installers, technicians, and other people who maintain the fire alarm system use their voltmeter to make sure of the polarity on the circuit. If the device is connected so the measured positive wire goes to the +symbol, the horn or strobe will never work.
At least from the device's point of view, supervision voltage on the NAC becomes the alarm voltage, and alarm voltage on the NAC becomes the supervision voltage.
Supervision voltage on the circuit has weak power that usually isn't enough to turn on the horn or strobe; the device won't turn on even though its internal diode conducts. When the alarm sounds, and the voltage changes to forward in the building wiring (NAC), the horn or strobe sees this forward voltage as backward and the internal diode won't conduct. In other words, the horn or strobe doesn't notify anyone.
Many times, before connecting the wires to the horn or strobe, installers, technicians, and other people who maintain the fire alarm system use their voltmeter to make sure of the polarity on the circuit. If the device is connected so the measured positive wire goes to the +symbol, the horn or strobe will never work.
At least from the device's point of view, supervision voltage on the NAC becomes the alarm voltage, and alarm voltage on the NAC becomes the supervision voltage.
Supervision voltage on the circuit has weak power that usually isn't enough to turn on the horn or strobe; the device won't turn on even though its internal diode conducts. When the alarm sounds, and the voltage changes to forward in the building wiring (NAC), the horn or strobe sees this forward voltage as backward and the internal diode won't conduct. In other words, the horn or strobe doesn't notify anyone.
Inspection Repairs
A number of times, I've had to reverse the wiring for the horns and strobes at the first annual inspection because the installers who put in the system didn't understand this voltage reversal, and never tested the horns and strobes to make sure they all worked.
Then the fire inspector, who should have been shown a fully functioning fire alarm system and not be required to troubleshoot the system for the installers, also missed their mistake.
Panel Trouble on the NAC
Unfortunately, most panels and booster power supplies
don't supervise for this problem. They supervise the wire itself, but don't
show trouble for a miss-wired device; they let an installer or technician
connect the horn or strobe backward.
What's even worse, the supervision power isn't enough to activate the device, so false activation won't indicate anything wrong with the wiring to the installer, either.
The miss-wiring issue will not be discovered until either the next inspection, or when there's a fire and that device doesn't sound. This is, of course, unless the horns and strobes are turned on right then and there to test whether they work.
What's even worse, the supervision power isn't enough to activate the device, so false activation won't indicate anything wrong with the wiring to the installer, either.
The miss-wiring issue will not be discovered until either the next inspection, or when there's a fire and that device doesn't sound. This is, of course, unless the horns and strobes are turned on right then and there to test whether they work.
Voltage Reversal on the
NAC
It's important to remember that the polarity of the
voltage, measured while the fire alarm system is normal, is backward; it is
supervision voltage -- not alarm voltage.
Start with the NAC
supply voltage at the minimum voltage allowed by UL under battery back-up.
This value is 20.4 volts (15% below 24 VDC), so 24VDC x 0.85 = 20.4 volts.
Total current draw
= (Device amps) x (Number of strobes), so Multiply 0.202 amps (for 110 cd) by 5
(number of strobes). That calculation produces 1.010 amps total current draw
{(0.202 amps) x (5) = 1.010 amps}.
Total wire resistance
= (Resistance per foot of wire) x (Length of circuit), The total resistance of
the wire is determined by the amount of resistance per foot for 12 AWG wire (2
ohms per 1000 ft.) for the length of the circuit. In this case, the circuit
length is 500 feet (250 ft. times 2, for the supply and return wires). The
resistance of the wire is 1 ohm. { (2 ohms/1000 feet) x (500 feet) = 1 ohm}.
Voltage is
equal to resistance times current. The voltage drop, due to the five devices,
is 1.010 volts (1 ohm times 1.010 amps), Resistance x Current = Voltage, (1
ohm) x (1.010 amps) = 1.010 volts.
End of line
voltage = Minimum voltage - device voltage drop, 20.4 volts - 1.010 volts =
19.39 volts.
This is an acceptable condition since the EOL voltage is
greater than 16 volts.
Only when the system goes into alarm, to turn on the horns, strobes, chimes, and bells, does the voltage change to become forward.
NAC is the acronym for Notification Appliance
Circuit. Notification: Tells people of a Fire or other Life Threatening
Emergency. Appliance: Horns, Strobes, Chimes, Bells, Klaxons,
Speakers. Circuit: Physical wire loop carrying power to the Notification
Appliances.
This is the circuit that powers the horns, strobes,
chimes, and speakers in a building. This is the circuit that notifies the
occupants of a fire. Usually, there is more than one NAC circuit
from the fire alarm panel.