Sunday, December 15, 2024

Hose reels and foam inlets Installation, Commissioning and Maintenance

Hose reels and Foam inlets Installation, Commissioning and Maintenance 

This part of BS 5306 gives recommendations for hose reels and foam inlets. It covers good practice in matters affecting the design, installation, testing and maintenance of such systems. It does not give requirements for the hose reels themselves, which are specified in BS EN 671.

This part of BS 5306 does not cover wet and dry fire mains, automatic foam systems and portable fire-fighting equipment. These systems are covered in BS 9990, BS 5306-3, BS 5306-8 and BS EN 3-7.

General design considerations Hose reels

Hose reels should conform to BS EN 671.

Pipework for hydraulic hose reels should not normally be less than 50 mm nominal bore and feeds to individual hose reels should be not less than 20 mm nominal bore.

Pipes should be made of one of the following:

a) steel in accordance with BS 1387;

b) copper in accordance with BS EN 1057, with fittings in accordance with BS EN 1254-1 or BS EN 1254-2;

c) plastics which are satisfactory to the water supply undertaking for this application, provided the pipework is protected from damage, by fire or otherwise, by location in a low-risk area such as underground or in a service duct of brick, concrete or equivalent construction.

d). The water supply to hose reels should normally be kept entirely independent from other water supplies within the building including those for other fire-fighting systems. In certain special circumstances the supply to hose reels may be taken from the supply provided for a sprinkler system (see BS EN 12845, BS 5306-2 and the Fire Protection Association publication LPC rules for automatic sprinkler installations incorporating BS EN 12845 [1]).

e) When the likely routes for the hose are tortuous, the length and size of hose on the reel should be limited, and the siting and provision of reels should be reviewed with these limitations in mind.

Consideration should also be given to the physical attributes of the individuals who are expected to use the equipment.

f) It is essential that pressures and flows should at all times be adequate to serve the designed number of hose reels likely to be used.

This is irrespective of the source of water supply.

Provision and siting

Hose reels, where installed, should be provided to cover all risk areas.

Siting

Hose reels should be sited in prominent and accessible positions at each floor level adjacent to exits in corridors on exit routes, in such a way that the nozzle of the hose can be taken into every room and within 6 m of each part of a room, having regard to any obstruction. Where heavy furniture or equipment might be introduced into a room, the hose and nozzle should be capable additionally of directing a jet into the back of any recess formed.

In exceptional circumstances it might be desirable to site hose reels in such a way that if a fire prevents access to one hose reel site, the fire can be attacked from another hose reel in the vicinity.

It is essential that the hose reels remain unobstructed and that they are available for use at all times.

In buildings that have large open floor areas such as warehouses, the stacking arrangements should provide for unobstructed access to the hose reel. It might also be considered necessary to provide guard rails around the hose reel position to prevent stacking taking place immediately adjacent, care being taken that the guard rails do not obstruct the operation of the hose.

Where stacking is taking place, notices indicating the hose reel positions should be sited at high level.

These notices could be situated over the main avenues, subject to directional arrows being provided.

Frost protection

Hose reels and their water supply systems should be afforded all possible protection against frost.

Electrical earthing

Electrical earthing should be in accordance with BS 7671 and BS 7430.


Installation of hose reels

Hose reels in recesses

Preferably hose reels should be installed in recesses so that they do not form obstructions on a route of escape. The details of installation will vary considerably owing to the wide variation of types of hose reel and their size.

Recess doors

Any doors provided for hose reel recesses should be in accordance with BS EN 671.

Hose reels in open areas

When installed on open floor areas it might be necessary to position hose reels above head height but in these cases the nozzle retainer, the hose guide and the inlet valve should be fitted at about 900 mm above floor level.

NOTE It might also be desirable to provide an anti-over-run device to prevent the hose from becoming entangled when run out.

Importance of firm fixing

Hose reel brackets should be firmly fixed to the wall so that casual knocks received during normal use of the building and the stresses incurred during use for fire-fighting will not prevent the unimpeded use of the hose reel.

Water supply for hose reels Booster pumps

1.   Where the water pressure in hose reel mains needs to be boosted, the provision of an electrically driven pump is usually a convenient method. A duplicate standby pump should also be provided.

2.   Both motors and pumps should be sited in fire protected positions and the electrical supply to them should be by an exclusive circuit with the cables following a route of negligible fire risk or be provided with adequate protection.

3.   The booster pumps system should come into operation automatically on a drop in pressure or a flow of water. Both pumps should be automatically primed at all times.

4.   All pumps should also be capable of being started or stopped manually. The standby pump should be so arranged that it will operate automatically on a failure for any reason of the duty pump.

5.   An audible and visual alarm should be provided at an agreed position to indicate that the equipment and the pumping plant have operated.

Connection for boosted supplies

Some water undertakings do not permit a booster pump to be connected directly into a supply main. In such cases the installation should be fed from a suction tank or inter-connected tanks having a minimum capacity capable of supporting operation of the hose reel for 45 min at the minimum flow rate specified in BS EN 671-1:2001.

The tank or tanks should be automatically supplied from a town’s main, controlled by a ball valve of minimum diameter 50 mm.

Use of domestic water tanks

Tanks supplying water for domestic purposes should not be used as suction tanks for hose reel installations unless arrangements have been made for these domestic supplies to be drawn off in such a manner that the requisite reserve of water for the hose reel installation is always preserved.

Security

The main stop valve controlling the water supply to the hose reels should be secured fully open by a suitable device such as a padlocked chain or strap. Hose reels should also be protected against interference and attack by thieves and vandals as far as it is possible to do so without adversely affecting operational capability.

 

General design considerations Foam inlets

Oil risks situated at or below ground level, e.g. oil-fired boiler rooms, oil storage tank chambers or transformer chambers, where they might not be directly accessible for fire-fighting and search and rescue operations, might require foam inlets so that foam can be applied to a fire from outside a building by means of a system of fixed piping and suitable outlets. The fire authority should be consulted on this matter.

Capability of inlets and lines

Not more than three outlets, having an aggregate cross-sectional area of not more than 3 200 mm2, should be supplied by one inlet and one line of delivery pipe. Where there are more than three outlets, or the aggregate cross-sectional area of the outlets appreciably exceeds 3 200 mm2, additional inlet(s) and delivery pipe(s) should be installed.

External connections

The external connection should normally be housed in a box conforming to BS 5041-5 built into an external wall of a building, or into a boundary wall so that the bottom of the box is at a level between 400 mm and 600 mm above the ground. There should be at least 2.50 m of clear working space in front of the box, and it should be clear of openings from the space protected by the foam system, so that

the inlet can be used without undue exposure of personnel to heat and smoke.

Delivery pipe

The delivery pipe from each foam inlet to the space protected should not exceed 18 m in total length and should be 65 mm or 80 mm nominal bore pipe, threaded and socketed, and of suitable heavy quality steel to meet the pressure, robustness and durability requirements of the system in question. The run of pipe should be as direct as possible with a fall away from the inlet provided on all sections of it, and any changes of direction should be made with standard bends, springs or long turn fittings; elbows should not be used. The pipe from one inlet should serve only one space.

Termination of delivery pipe

Normally the delivery pipe from the inlet coupling should terminate in the following ways:

a) in an oil-fired boiler room: about 1 m above the level of the oil burners, with a separate outlet above each burner;

b) in an oil storage tank chamber: about 150 mm above the estimated level of the oil should the total contents of the tank(s), when full, be discharged into the chamber;

c) in a transformer chamber: at ceiling level.

 

Installation, Commissioning and Maintenance

Work on site

1. Adequate provision should be made by the responsible contractor to protect materials and components on site from deterioration or damage.

2. Unloading, stacking and storage should be carried out with care to prevent damage to pipes and pipe threads, fittings, couplings and other components used in the system.

3. Pipes should be securely anchored before any pressure or flow tests are carried out.

Initial inspections and acceptance tests for hose reels

Flushing out

Before any water is introduced into the hose reel, the supply to it should be thoroughly flushed out to ensure that no harmful matter is passed into the reel. This is particularly important for automatic hose reels.

After flushing out, the tubing should be run out and the water turned on to establish that the assembly is fully operational.

Procedure (direct mains supply)

The two most highly situated and remote reels should be discharged imultaneously, one being led to waste and the other directed into a suitable receptacle to ascertain that the flow rate is achieved. For the purpose of this test it will be necessary to provide a receptacle of a suitable capacity.

Procedure (boosted supplies)

The two most highly situated and remote reels should be discharged simultaneously, until the duty pump cuts in automatically. Thereafter, with both reels still in operation, the discharge rate of one of them should be measured.

The test should be repeated. This time a simulated mechanical or electrical failure of the duty pump should be arranged, and the ability of the standby pump to come into service automatically and to maintain the required outputs should be tested.

Putting into operational readiness

1. When the tests have been satisfactorily completed, the system should be restored to its normal operating state. Reels should never be left under pressure and, where practicable, hose should be drained prior to being returned to the drum.

2. Hose should be rewound on the drums, particular attention being paid to automatic hose reels to ensure that the automatic valve is fully closed when the hose has been rewound. Where an isolation valve has been incorporated this should be closed on completion of stowage, and the nozzle interlock, where fitted, should be completed.

3. Where it is the practice of water undertakings to seal the inlet valve to the reel, the undertaking concerned should be notified of the test.

 

Initial inspections and acceptance tests for

Foam inlets

1. The layout of all foam inlets should be checked to ascertain that they conform to the approved layout plan.

2. Any inlet coupling should also be checked to ensure correct functioning, and to verify that earthing has been carried out satisfactorily or certified by the electrical contractor.

Indemnities

Before testing any system a signed indemnity should be sought from the person at that time responsible for the work site or premises.

NOTE This might be required by the appropriate authority in respect of liability for damage caused to persons or property arising out of, or in connection with, any test.

Test records

A permanent record of all inspections and tests should be maintained as part of the fire safety manual in accordance with BS 5588-12.

This should record:

a) date and time for inspection or test;

b) person carrying out the test;

c) test results noted;

d) any external factors significantly affecting the results (e.g. weather

conditions);

e) follow-up action required;

f) work carried out as a result of (e) with date and result of retest.

Maintenance and testing of hose reels

1. The maintenance and testing of hose reels should be in accordance with BS EN 671-3.

2. If booster pumps have been installed, these and their associated mechanical and electrical equipment should also be checked.

Rectification of defects

1. It is essential that all defects are rectified in the shortest possible time, to ensure that the fixed fire-fighting equipment is restored to a satisfactory condition in as short a time as possible.

2. Where, due to unforeseen difficulties, it is necessary to leave an installation not available for use, the fire and rescue service should be informed immediately in order that alternative arrangements can be made to cover this deficiency should the need arise. In addition a suitable notice to indicate that the installation is not available for use should be placed in a prominent position. In the case of foam inlets the notice should be in the inlet box.

3. When the installation is reinstated, the fire and rescue service should again be informed so that any alternative arrangements can be cancelled and, if considered necessary, an inspection and test of the repaired installation can be carried out.

Operational instructions

A notice giving full operational instructions should be displayed on or adjacent to the hose reel, whether this is manual or automatic. In the case of a manual hose reel in which an interlocking device is not incorporated the instructions should include the wording: “Open valve before running out hose”.

NOTE The interlocking device, where provided, ensures that the nozzle cannot be withdrawn until the water supply has been turned on.

The instructions should include specific instructions as to the correct method of closing the inlet valve to a manual fire hose reel, or of securing an automatic fire hose reel.

The notice should be in accordance with BS 5499-1 and BS 5499-5 for fire equipment or supplementary signs.

Temporary notices

Where reliance is being placed on the operation of fire-fighting systems or appliances during the construction period, temporary notices (to the satisfaction of the fire and rescue service) giving essential information for their protection from damage and for their efficient operation should be set up and remain until the installation becomes fully operative.

Identification of equipment

1. The pipework supplying water to hose reels should be identified in accordance with BS 1710 and should meet the recommendations given in below.

2. The following notices should be rectangular with white wording on a red background. Letter height should be not less than 25 mm and should be lower case except for the initial letter “F”, which should be upper case and in accordance with BS 5499-1 and BS 5499-5.

a) A notice reading “Fire hose reel main supply” should be displayed at the stop valve controlling the water supply to the hose reels.

b) A notice reading “Fire hose reel pump motor supply – not to be switched off in the event of fire” should be displayed adjacent to all switches in the electrical power supply to any pumps.

3. A sign in accordance with BS 5499-1 and BS 5499-5 should be displayed adjacent to the hose reel (on the door if the hose reel is in a recess fitted with a door, glazed or otherwise).

Ref:

1.   FIRE PROTECTION ASSOCIATION. LPC rules for automatic sprinkler installations incorporating BS EN 12845.

2. BS 9990, Code of practice for non-automatic fire-fighting systems in buildings.

3. BS 5306 Fire extinguishing installations and equipment on premises.



















Sunday, December 1, 2024

Summary of NBC 2016 Part 4 Fire and Life Safety

Summary of NBC 2016 Part 4 Fire and Life Safety 

Bureau of Indian Standards (BIS) is the National Standards Body of India established under the BIS Act 2016 for development of standards, marking and quality certification of goods and for matters connected therewith or incidental thereto.

The National Building Code of India 2016 (NBC 2016), a comprehensive building Code prepared by BIS, is a national instrument providing guidelines for regulating the building construction activities across the country.

Thus, the Code gives all the information required by the architect, engineer, structural engineer, construction engineer, services engineer and other professionals from the early stages of planning to translating the building on to terra firma. The comprehensive NBC 2016 contains 13 Parts some of which are divided into Sections and Subsections totalling 33 chapters.

Key Content - Fire and Life Safety

All buildings shall satisfy minimum requirements for safety of life from fire, smoke, fumes or panic arising from these or similar causes.

Classification of buildings based on occupancy

The city or area under the jurisdiction of the Authority shall be demarcated into distinct fire zones depending upon the existing layout, types of building construction, classification of existing buildings based on occupancy and expected future development of the city or area. Intermixing of hazardous occupancies should not be allowed in other zones.

1) Fire resistant walls, floors and compartments

• To limit the spread of fire

• No compromise for openings such as shafts, refuse chutes, vertical openings, etc.

2) Shafts

• To be provided with fire resistant rated inspection door for passage of building

services such as cables, electrical wires, telephone cables, plumbing pipes, etc

depending upon location.

3) Refuge area

• An area within the building for a temporary use during egress. It generally serves as

a staging area which is protected from the effect of fire and smoke.

4) Fire detection and firefighting installations

• These include fire alarm, fire extinguishers, hose reels, wet riser, down comer,

yard hydrants, sprinklers, deluge system, water spray, foam, water mist systems,

gaseous or dry powder system, water storage tanks and pumps, etc.

5) Means of egress

• Consists of three separate and distinct parts, that is, exit access, exit and exit discharge

• Exit access are working/functional areas

• Various types of exit access and exits are doorways, corridors and passageways, horizontal exits, internal staircases, exit passageways, external staircases and ramps.

6) Firefighting shafts

• With fire man talk back, fire door, wet riser, hose reel, signage showing floor plan and stairways and fire man’s lift

Fire prevention

Fire prevention is based on the following:

        Occupancy

        Fire zones

        Types of construction

        General requirement of all occupancies

        Electrical installation

a.   Emergency power for fire and life safety system

b.   Substation

c.    Lightning protection

d.   Escape lighting and exit signage

e.   HVAC and smoke control

f.     Glazing

g.   Surface interior finish

h.   Fire Command Centre

        Fire resistance rating of structural and non-structural elements updated

        Fire resistance rating of service shaft and duct opening of 2 hours.                                 Inspection door and duct opening should have same resistance rating of  service shaft.

        Facade protection and openable windows in facade shall have fire protection and smoke exhaust aspects

        Compartment criteria of different occupancies and fire separating wall & floor partitions are modified

        Provision of fire/smoke damper design more elaborated like provision of damper

A.   At the fire separation wall

B.   Where ducts/passage enter the vertical shaft

C.   Where the duct passes through floor

D.   At the inlet of supply air duct and return air duct of each compartment on every floor.

Glass facade

  1. For fully sprinkler building having fire separation of 9 m or more, tampered glass in a non-combustible assembly with ability to hold the glass in position shall be provided
  2. It shall be ensured that sprinklers are located within 60 cm and there is full coverage of glass. All the gaps between floor slab and facade assembly shall be sealed at all level by fire resistant sealant material of equal rating of floor slab to prevent fire and smoke propagation from one floor to another.
  3. Openable panels shall be provided in each floor and shall be spaced not more than 10 m apart, measured along the external wall from the centre to centre of the access opening. Such opening shall be operable at a height between 1.2 m and 1.5 m from the floor in the form of openable panel (Fire Access Panel) not less than 1000 mm x 1000mm opening outward.

FIRE OPENABLE PANEL DO NOT OBSTRUCT IN  25 mm lettering in the inner side can also act as smoke exhaust at the time of distress.

Service Sector in Focus

Some important features considered in Hospitals

        Each compartment shall be able to accommodate patients from adjoining compartment and Density Factor (Number of patient) area to be allotted 3.5 sq.m/person

        Critical patients, incapable of self-preservation and physical impairment shall be housed within 30 m height

        Other types of patient and occupancy like Nurses’ centre, Medical shop, Canteen, etc to be in between 30-45 m in height

        Operation theatre, Delivery room, ICU, Recovery room shall have a separation with 2 hours of fire resistance rating

        Passage width of aisles, corridor, ramp, etc shall be 2.4 m unobstructed through which patients are being moved and in case of inpatient width not less than 1.5

        All exits from Hospital or Infirmary Section shall not be less than 2m

        Minimum door width single/double occupancy shall be 1.25 m; for 3-5 patients, door width shall be 1.50 m; for more than 5 patients and patient evacuation bed (i.e. ICU) it shall be 2.0 m; for single/double doors, it shall be 1.5 m

        Any sleeping accommodation or suite exceeding 100 sq.m in area, 2 no.s of access door leading to escape route, corridor, etc to be provided

        Room designed for laboratory or like facility shall be limited to 100 sq.m in area for additional area coverage. Fire separation shall be done by 2 hours fire resistance.

        A stretcher lift in the lift bank shall also act as a fireman lift

Life safety is based on:

        General exit

        Occupant load

        Declaration of occupant load

        Egress components

        Smoke control of exit

        Compartmentation

        Smoke control above and below ground

        Gas supply

        Hazardous area

        Fire detection

        Fire drill

Safe electrical supply system

        The electrical supplies towards the critical aspects of emergency power for fire and life safety addressed for respective system.

        Power supply to the panel and distribution board be through fire proof enclosure or circuit integrity cable or through alternate route in the adjoining fire compartment is protected within the compartment of vulnerability and require location of the panel/distribution board feeding shall be in fire and safety zone and ensure supply of power to these system.

        The high voltage electrical equipment safety including aspects of emergency and exit lighting of large and public assembly occupancies

        HVAC system, smoke control and mitigation also to be taken care of with comprehensive approach towards compartmentation and spread of fire and smoke.

Life safety

        To calculate the number of exit requirement with Density Factor

        Exit Layout for better understanding of various aspects of means of egress, corridor, passageways, stair ways and exit

        Provision for access control door, electromagnetic door, revolving door and turnstile (conditions to be fulfilled)

        Provision of handrail at both sides of stairs and ramp width exceeding 1.5m

        Internal stair width of residential building increased to 1250 mm from 1000 mm

        External stairs width increased from 1250 mm to 1500 mm

        Each fire rated door shall have a marking on the product of its certification. Door assembly parts like hinges, locks, panic bars, door closer and door viewer shall be certified.

        Updated staircase pressurization requirement (Smoke control of exit) for lobbies & corridors

        Smoke exhaust and pressurization of area below the ground floor

        Requirement of smoke exhaust system having make up air system for the theatre and atrium

        Smoke exhaust fan in the mechanical ventilation system shall be fire rated of 250 degrees centigrade for 2 hours (120 minutes)

        Provision of smoke barrier and sprinkler around the opening for escalator

        Requirement of display of occupancy load for assembly occupancy and call center.