Fire Survival Cable
Solid/Stranded (ATC/ABC) Copper conductor,
insulated with specially formulated PVC/TPE/XLPE to form a core. Cores laid up
together or twisted to form a pair/triad depending upon the individual
requirement. Such cores/pairs/triads after laying are coated with special Fire
Resistant materials and overall sheathed with special PVC/TPE/LSZH. These Fire
Survival Cables are carefully tested as per IEC-60331 standards
to meet the industry laid parameters.
Features:
·
High tensile strength
·
Durable
·
Water proof
·
Chemical resistant
·
Shielding with Braiding/Aluminum Mylar taping will be done
overall or individually depending upon the requirement.
·
Armouring provided depending upon requirement with a extruded
inner special PVC/TPE sheath, and overall sheath of special PVC/TPE.
Conductor :
Electrolytic Grade Copper Bare / Tinned, Solid / Stranded / Annealed Flexible Conductors conforming to IS:8130:1984 or other international standard.
Electrolytic Grade Copper Bare / Tinned, Solid / Stranded / Annealed Flexible Conductors conforming to IS:8130:1984 or other international standard.
Fire Barrier :
Conductor are insulated with Mica Glass Tape / silicone rubber as per requirements. Mica Tape survives temperature up to 1000°C. It is non-toxic, chemically neutral and 100% Halogen free.
Conductor are insulated with Mica Glass Tape / silicone rubber as per requirements. Mica Tape survives temperature up to 1000°C. It is non-toxic, chemically neutral and 100% Halogen free.
Primary Insulation
:
The Insulated material may be Heat Resistant PVC / XLPE / Silicon Rubber or any other dielectric material as per customers specification.
The Insulated material may be Heat Resistant PVC / XLPE / Silicon Rubber or any other dielectric material as per customers specification.
Screening :
Individual & Overall Shielding may be of Annealed Tinned Copper Braiding/Poly Aluminum [Thin Layer of Aluminum Foil bonded to Polyester Film] Tape with Annealed Tinned Copper Drain Wire. Braiding ATC Shield has high tensile Strength and provides better coverage in flexing application. It's also done by copper Tape or nickel copper as per specifications.
Individual & Overall Shielding may be of Annealed Tinned Copper Braiding/Poly Aluminum [Thin Layer of Aluminum Foil bonded to Polyester Film] Tape with Annealed Tinned Copper Drain Wire. Braiding ATC Shield has high tensile Strength and provides better coverage in flexing application. It's also done by copper Tape or nickel copper as per specifications.
Inner Sheath :
The Inner Sheath is applied over laid up of cores by extrusion / wrapping of thermoplastic material. The Insulation, Inner Sheath can be Normal Pvc /FR PVC / FRLS PVC / ZHFR / LSF Compound depending upon their application or specification.
The Inner Sheath is applied over laid up of cores by extrusion / wrapping of thermoplastic material. The Insulation, Inner Sheath can be Normal Pvc /FR PVC / FRLS PVC / ZHFR / LSF Compound depending upon their application or specification.
Armour:
Armour is applied over inner Sheath. It may consist of galvanized Round Steel wires or galvanized Flat Steel Strips conforming to IS: 3975. Steel wire armoured cables are suitable for direct burial. One or more copper wires can be incorporated in the armour to increase the conductivity of the Armour where it is being used as an earth return. Armour can also by steel tape / double helical steel tape or aluminum wire if client's requirement. Round Wire armoring is provided, where the calculated diameter under Armour is 13.0 m.m. above this, armoring is either round wire / steel strip as per client's requirement.
Armour is applied over inner Sheath. It may consist of galvanized Round Steel wires or galvanized Flat Steel Strips conforming to IS: 3975. Steel wire armoured cables are suitable for direct burial. One or more copper wires can be incorporated in the armour to increase the conductivity of the Armour where it is being used as an earth return. Armour can also by steel tape / double helical steel tape or aluminum wire if client's requirement. Round Wire armoring is provided, where the calculated diameter under Armour is 13.0 m.m. above this, armoring is either round wire / steel strip as per client's requirement.
Outer Sheath :
A final covering of PVC Compound is applied over Armouring in case of Armoured
Cable or over Inner Sheath in case of Unarmoured Cable. The Color of Sheath is
Black,Grey or as per customer's choice.The Outer Sheath material may be FR PVC
/ FRLS PVC / ZHFR / LSF as per requirement of the specification.
Standard Specifications :
ICE 331/ BS 6387 :1994, IEC 60331,
BS 6387 - CAT A,B,C,W,Z
BS 7846 - CAT F1, F2, F3
& other customized & International Standard
Fire Survival Test:
AS PER IEC-60331
Characteristics:
* Will withstand Flame temperature of 750 degree centigrade up to 3 hours without electrical breakdown at rated voltage.
* During fire condition small quantity of toxic gases mainly, CO, CO2 are inevitably emitted. Fire Survival Cables are designed to limit these toxic gases within safety level.
* Corrosive Gases react with moisture to produce active acids which corrode metals causing extensive long term damage. Often these gases spread throughout the building through the ventilation system or within the entire installation. This is particularly damaging to electronic equipment’s and even to the exposed steel structures or even the concrete enclosed steel structures.
* Does not propagate flame. Zero Halogen Low Smoke insulation & sheath material supplied on request
This standard details the following tests to categories
cables according to their fire withstand capabilities.
Resistance to Fire 950°C for 3 hours -
Category C
Performance Table
|
Symbol
|
650°C for 3 hours
|
A
|
750°C for 3 hours
|
B
|
950°C for 3 hours
|
C
|
950°C for 20 minutes
|
S
|
Resistance to Fire with Water Spray 650°C -
Category W
Performance Table
|
Symbol
|
650°C for 3 hours
|
W
|
Resistance to Fire with Mechanical Shock 950°C
- Category Z
Performance Table
|
Symbol
|
650°C
|
X
|
750°C
|
Y
|
950°C
|
Z
|
Typical Application :
These fire retardant cables Specially designed for to maintain Long-term
circuit integrity during and after a fire like public address and emergency
voice communication systems , fire extinguishing systems, sprinklers pumps,
control panels, exit lights in high-rise building control and instrumentation
services in industrial, commercial and residential complexes, hospitals,
airports, malls and crowdy areas etc. data and voice transmission,CCTV,
security, smoke detection and evacuation monitoring applications
,interconnection of distribution boxes and end devices, where continued
functionality is required during a fire situation ,in High-temperature
installation conditions.
For fire survival cable
type and sizes. See below image.