Fire Detection for Large Spaces:
Integrating Aspiration Smoke Detection
Modern structures are complex, which makes them difficult to
protect against smoke and fire. Features like large atria, vast open areas, or
high ceilings can make the use of traditional smoke and fire detection methods
impractical, ineffective, and difficult to maintain and operate.
Large, open spaces are prone to high airflow and smoke
stratification (caused by the high ceilings and/or dilution of the smoke), making
it difficult for smoke to reach spot-type smoke detectors and for conventional
detection devices to operate properly. Additionally, significant effort is
required just to test and inspect these devices in such spaces, per code
requirements.
In general, fire detection in large volume spaces directly
relates to the size of potential fires within the space. Building contents such
as furniture, large trash containers, or merchandise displays typically burn
with enough energy to push smoke to significant heights. However, low energy
fires with a small heat-release rate are subject to stratification and can be
difficult for ceiling or near-ceiling mounted smoke detection devices to
detect.
What is considered a large space?
Large spaces are those with ceiling or roof heights
extending tens or even hundreds of feet above the floor. Some examples are:
·
Spaces containing atria, such as
hotel lobbies and shopping centers
·
Warehouses and distribution centers
·
Record/archive storage facilities
and automated storage and retrieval warehouses
·
Manufacturing plants, such as
automobile assembly plants
·
Convention centers, theatres,
auditoriums, stadiums, and indoor sports facilities
·
Cathedrals, churches, temples, and
mosques
·
Aircraft hangars and other large
storage and maintenance areas
·
Transportation terminals, such as
airport terminals and train stations
Regarding fire protection, large spaces can be classified
into two basic categories:
Category 1:
Large volume spaces with fire-load contents, generally of limited height, located
on the main floor or other floors open to the large volume. These spaces tend
to have moderate to large occupant loads. Examples: atria areas, single-story
manufacturing areas, heritage buildings, religious worship buildings, and
airport terminals.
Category 2:
Large volume spaces with stacks or piles of combustible contents, which may or
may not be in storage racks. These contents occupy a significant portion of the
volume and height of the space that is most often one story. These spaces tend
to have low to moderate occupant loads and a high value of contents. Examples:
warehouses, distribution centers, automated storage and retrieval facilities,
and library stack rooms.
Detecting Smoke in Category 1: Hotel
Atria, a popular architectural design feature, enhance the
perception of light and space within structures but can be dangerous for
occupants in a fire. One fire design challenge is compensating for the
fluctuation of solar radiation that enters through large expanses of glass,
which can often generate thermal gradients within the space and result in a hot
gas layer near the ceiling or roof. This can vary from day-to-day, depending on
thermal load and operations of HVAC or natural ventilation systems.
The base of the atrium is especially vulnerable. A fire at
this location could potentially fill the unenclosed shaft with smoke, allowing
fire to spread rapidly and transport heat, smoke, and toxic gases from floor to
floor. More importantly, traditional technologies take too long to detect smoke
in these large areas because smoke may not be buoyant enough to penetrate the
ceiling layer of stratified environments. Aspirating smoke detection systems,
however, can be designed to avoid the issues posed for ceiling-mounted spot
smoke detectors due to a solar-induced hot layer.
Detecting Smoke in Category 2: Warehouses
Category 2 spaces require additional considerations beyond
those previously discussed. Modern warehouses and storage facilities often rely
on automatic sprinkler systems for basic fire protection. However, the
potential loss of key supply chain facilities, high value storage, and
irreplaceable archived storage can warrant the installation of early warning
smoke detection for staff intervention before sprinklers are needed.
Arson and electrical/mechanical systems account for a
significant percentage of warehouse fires, but aspirating smoke detection can
provide early indications of such events and allow for manual fire suppression
or depowering of equipment. STRUCTURE FIRES IN U.S. WAREHOUSES by
Richard Campbell, published in June 2013 by the National Fire Protection Association
Fire Analysis and Research Division, says that during 2007-2011, an estimated
average of 1,270 structure fires in warehouses were reported to U.S. fire
departments each year, with associated annual losses of 4 civilian deaths, 23
civilian injuries, and $188 million in direct property damage. According to
Campbell:
·
Nearly one-fifth of these fires were
set intentionally
·
Electrical distribution or lighting
equipment was involved in 13% of fires
·
Electrical failure or malfunction
was the leading factor contributing to the ignition of warehouse fires, as well
as in contributing to direct property damage and to civilian injuries,
representing 19% of the total in each category
Integrating Aspiration Smoke Detection
There are five basic design options for integrating an
aspirating smoke detection system in warehouse and storage buildings. Selecting
a sampling pipe configuration is dependent upon the warehouse application and
internal characteristics (such as presence of high-bay racking, mezzanines, and
voids) as well as the facility’s operational objectives and smoke detection
objectives (performance-related).
1.
Near Ceiling
Detection – sampling pipes are located
close to the ceiling only
2.
Below
Ceiling Detection – sampling pipes above a
ceiling use drop down pipes or capillary tubes with sampling holes
3.
High-Low
Alternating Detection – sampling pipes are located
on the ceiling with alternating sampling holes on the ceiling and drop-down
pipes
4.
Multi-Level
Detection – this detection method
applies to warehouses comprising high bay storage racks and utilizes more than
one ASD system for ceiling and intermediate level detection.
5.
In-Rack
Detection – the sampling pipes run
horizontally or vertically between back-to-back racks at various heights.
Drop-down pipes from the ceiling can also be used for in-rack detection.
In addition to these generic warehouse scenarios, additional
aspiration protection should be considered in the following situations:
·
Office and
control area: for aesthetic reasons, sampling in
these areas is usually conducted via capillary tubes fed through the ceiling
from the main sampling pipes, which are located in the ceiling void.
·
Ceiling void: it is especially important to protect ceiling voids
containing cabling and/or any other equipment, due to an increased risk of
fire. The spacing of the ASD sampling holes is again determined using the grid
method.
·
Lighting
areas: The ASD sampling pipes should not
be placed underneath or in close proximity (<3.3 ft (1 m)) to lighting
fixtures, heaters, skylights, or other heat-emitting objects.
·
Loading bay: ASD sensitivity should be lowered to account for the truck
exhaust fumes regularly present in the loading bay environment.
Installation Scenarios
NFPA 72 provisions on the spacing and location of smoke
detectors states that, “The location and spacing of smoke detectors
shall be based upon the anticipated smoke flows due to the plume and ceiling
jet produced by the anticipated fire, as well as any pre-existing ambient
airflows that could exist in the protected compartment.”
Aspirating systems can be mounted wherever it is most
convenient – on walls, columns or rack frames – but it’s recommended to mount
the units in close proximity. For example, these units can be located in the
center of a warehouse with the pipe network extending outward, toward the
walls. This configuration minimizes the distance between detectors and reduces
wiring costs.
There are many options for warehouse detection, including:
High-low alternating detection: this option is comprised of ceiling sampling holes that
alternate with drop down pipes. This method is used to penetrate the hot air
layer that may develop at the roof level, which allows for optimal sampling
when the air at the roof level is either hot or cold. Consult local codes and
standards to determine the correct length of drop down pipes for individual
facility configurations [Figure 17].
In-rack detection:
This may be used in warehouses with high-bay racking where stratification
occurs, and/or localized detection is required. The air sampling pipe can have
either a horizontal or vertical in-rack detection configuration [Figure 18]. Ideally,
the detector is installed at the end of the rack at an accessible level. As a
safeguard against mechanical damage from forklift trucks, sampling pipes should
be located between back-to-back racks out of harm’s way.
Non-high-bay racking detection: In this case, ceiling drop-down pipes may also be used for
in-rack detection. When installing drop-down pipes, here too, it is important
to ensure that they will not be damaged by forklifts or be in close proximity
to the stored goods. The drop-down pipes can be fitted to the sheltered side of
the racking, fixed to the rack frame [Figure 19]. In-rack drop-down
pipes normally have two or three sampling holes drilled in them to provide
sampling at different heights within the racking system.
Multi-level detection:
Additionally, this option can be used in high bay storage racking areas with
expected high stratification levels and/or mezzanines (catwalks) consisting of
solid flooring that will impede/delay the rise of the smoke plume. This design option
requires one ceiling aspirating system and multiple intermediate level
aspirating systems [Figure 21].
Benefits of Aspirating Smoke Detection
There are many hidden benefits of integrating an aspirating
smoke detection system into the fire detection system design for a large volume
space. It’s often a challenge to handle diverse placement options in fire and
life safety designs, but aspirating smoke detection technology is flexible. It
can accommodate a variety of horizontal and vertical sampling point locations
and/or capillary tubes – providing effective coverage while minimizing
architectural and aesthetic impact. Aspiration smoke detection systems also
allow for more specific levels of warnings and alarms to allow building staff
to investigate before emergency operations (such as evacuation) are
implemented.
Aspirating smoke detection systems can also provide
maintenance flexibility and cost savings for large spaces. Inspection and
testing is easy, because an air sampling pipe network can be in the upper
elevations of large volume spaces while the air sampling detector is installed
in a remote accessible location. By comparison, spot-type smoke detectors
located on high ceilings would require special procedures for inspection.
Furthermore, aspirating technology performance is more consistent and reliable
because it is not subject to building movement considerations of optical beam
smoke detection devices.
Smoke detection Aspirating systems generally include a
sensor of considerably increased level of sensitivity compared with a standard
point or line optical beam detectors. Such “high sensitivity” aspirating smoke
detection systems, are designated Class A systems in BS EN 54-20 and are often
used to protect critical electronic equipment rooms, in which even a very small
fire can result in unacceptable damage. Guidance on fire protection of such
facilities is given in BS 6266.
Typically, a Class B (enhanced sensitivity) or Class C
(normal sensitivity) aspirating smoke detection system is used in such
applications, but it is important to seek advice from suppliers with sufficient
experience and knowledge of aspirating smoke detection systems and BS EN 54-20.
For aspirating systems, specialist application guidance
needs to be sought from the manufacturer.