Indian
Standard
SELECTION, INSTALLATION AND MAINTENANCE OF AUTOMATIC FIRE DETECTION AND ALARM SYSTEM-CODE OF PRACTICE (IS 2189 : 2008)
SELECTION, INSTALLATION AND MAINTENANCE OF AUTOMATIC FIRE DETECTION AND ALARM SYSTEM-CODE OF PRACTICE (IS 2189 : 2008)
1 SCOPE
1.1
This
standard covers the planning, design, selection, installation and maintenance
of tire detection and alarm systems. It is applicable to simple systems with a
few manual call points as well as to complex installations comprising
addressable control and indicating panel, non-addressable detectors, manual
call points, control and indication panels. It covers systems capable of
providing signals to initiate, in the event of a fire, the operation of
ancillary services, such as fire extinguishing systems and other necessary
precautions but it does not cover the ancillary services. It covers tire
detection and alarm system installed in buildings of different types including
those installed in industries.
1.2
This
standard covers minimum level of protection. Nothing in this standard prevents
to install systems designed for higher degree of protection, for special risks,
etc.
2 REFERENCES
The
standards listed below contain provisions which, through reference in this
text, constitute provisions of this standard. At the time of publication, the
editions indicated were valid. All standards are subject to revision and
parties to agreements based on this standard are encouraged to investigate the
possibility of applying the most recent editions of the standards indicated
below:
IS No.
|
Title
|
2175:1988
|
Specification for heat
sensitive fire detectors for use in automatic fire alarm system (second
revision)
|
8757:1999
|
Glossary of terms
associated with tire safety (first revision)
|
11360:1985
|
Specification for smoke
detectors for use in automatic electrical tire alarm system
|
12456:1988
|
Code of practice for tire
protection of electronic data processing installations
|
3 TERMINOLOGY
3.0
For the
purpose of this standard, the following definitions and definitions given in IS
8757 shall apply.
3.1
Acknowledge
- To confirm that a message or signal has been received, such as by the
pressing of a button or the selection of a software command.
3.2
Activation
Device (Trigger Device) - Device capable of being operated automatically or
manually to initiate an alarm that is, detector, a manual (tire alarm) call
point or a pressure switch.
3.3
Addressable
Device - A fire alarm system component with discrete identification that can
have its status individually identified or that is used to individually control
other functions.
3.4
Addressable
System - System in which signals from detectors, manual call points, or any
other devices are individually identified at the control and indicating
equipment.
3.5
Air
Sampling-Type Detector - A detector that consists of a piping or tubing
distribution network that runs from the detector to the area(s) to be
protected. An aspiration fan in the detector housing draws air from the
protected area back to the detector through air sampling ports, piping, or
tubing. At the detector, the air is analyzed for tire products.
3.6
Alarm
Zone - Geographical sub-division of the protected premises, in which the tire
alarm warning can be given separately, and independently, of a fire alarm
warning in any other alarm zone.
3.7
Alert
Tone - An attention getting signal to alert occupants of the pending
transmission of a voice message.
3.8
Analog
Initiating Device (Sensor) - An initiating device that transmits a signal
indicating varying degrees of conditions as contrasted with a conventional
initiating device which can only indicate an on-off condition.
3.9
Annunciator
- A unit containing one or more indicator lamps, alphanumeric displays,
graphical displays or other equivalent means in which each indication provides
status information about a circuit, condition or location.
3.10
Approved
- Acceptable to the authority having jurisdiction.
3.11
Audibility
- Property of a sound which allows it to be heard among other sounds in the
background.
3.12
Authority
having Jurisdiction - The organization, office, or individual responsible for
approving equipment, materials, an installation or a procedure.
3.13
Automatic
Fire Detection and Alarm System - Fire alarm system comprising components and
sub-system required for automatically detecting a fire, initiating an automatic
alarm for fire and initiating other action as required,
3.14
Automatic
Fire Signal-Alarm of fire originated by an automatic device, given audibly
and/or visibly.
NOTE—The system may also
include manual fire alarm call points.
3.15
Ceiling-
The upper surface of a space, regardless of height. Areas with a suspended
ceiling have two ceilings, one visible from the floor and one above the
suspended ceiling.
3.16
Ceiling
Height—The height from the continuous floor of a room to the continuous ceiling
of a room or space.
3.17
Circuit -
Assembly of fire alarm components supplied from the same control equipment and
protected against overcurrent by the same protective device(s) or current
limitation arrangements.
3.18
Circulation
Area - Area (including a stairway) used mainly as a means of access between a
room and an exit from the building or compartment.
3.19
Combination/Multifunction
Detector- A device that either responds to more than one of the fire phenomena
or employs more than one operating principle to sense one of these phenomena.
Typical examples are a combination of a heat detector with a smoke detector or
a combination of rate-of-rise and fixed-temperature heat detector.
3.20
Commissioning
- Process by which it is determined that the installed system meets the defined
requirements.
3.21
Control
Centre - Permanently staffed room within or near the premises at risk for the
receipt of emergency calls and equipped with means for indicating the situation
in each of the protected premises, and the communications needed for
transmission of calls for assistance to emergency services.
3.22
Control
Unit - A system component that monitors inputs and controls outputs through
various types of circuits.
3.23
Detection
Zone - Sub-division of the protected premises such that the occurrence of fire
within it will be indicated by a fire alarm system separately from an
indication of fire in any other sub-division.
3.24
Detector
- A device suitable for connection to a circuit that has a sensor that responds
to a physical stimulus such as heat or smoke or flame.
3.25
Display -
The visual representation of output data, other than printed copy.
3.26
Electrical
Conductivity Heat Detector - A line-type or spot-type sensing element in which
resistance varies as a function of temperature.
3.27
Ember - A
particle of solid material that emits radiant energy due to either its
temperature or the process of combustion on its surface.
3.28
Emergency
Voice/Alarm Communications -Dedicated manual or automatic facilities for originating
and distributing voice instructions, as well as alert and evacuation signals
pertaining to a fire emergency, to the occupants of a building.
3.29
Evacuation—The
withdrawal of occupants from a building.
3.30
Evacuation
Signal-Distinctive signal intended to be recognized by the occupants as
requiring evacuation of the building.
3.31
Exit
Plan- Apian for the emergency evacuation of the premises.
3.32
False
Alarm - Alarm of fire that is, false, because the fire reported does not and
did not exist. This false alarm may arise by malicious, mistaken or accidental
intent.
3.33
Fault
Signal - A distinctive audible and visual signal indicating occurrence of a
fault within the system (for example, break in electric circuit, short circuit
or fault in power supply).
3.34
Fire
Alarm Control and Indicating Equipment - Equipment through which fire detectors
may be supplied with power and which:
- is used to accept a detection
signal and actuate a fire alarm signal;
- is able to pass on the fire
detection signal, through the fire alarm routing equipment, to the fire
fighting organization or to automatic extinguishers;
- is used to monitor automatically
the correct functioning of the system; and
- is used to indicate or display the
location of fire/alarm activation device.
3.35
Fire
Alarm Signal - A signal initiated by a fire alarm-initiating device, such as a
manual fire alarm box, automatic fire detector, water flow switch, or other
device in which activation is indicative of the presence of a fire or fire
signature.
3.36
Fire
Alarm System - A combination of components for giving an audible and visible
and/or other perceptible alarm of fire. The system may also initiate other
ancillary action.
3.37
Fire
Rating - The classification indicating in time (hours) the ability of a
structure or component to withstand a standardized fire test. This
classification does not necessarily reflect performance of rated components in
an actual fire.
3.38
Fire
Safety Functions - Building and fire control functions that are intended to
increase the level of life safety for occupants or to control the spread of the
harmful effects of fire.
3.39
Fixed
Temperature Detector - A device that responds when its operating element
becomes heated to a predetermined level.
3.40
Flame - A
body or stream of gaseous material involved in the combustion process and
emitting radiant energy at specific wavelength bands determined by the
combustion chemistry of the fuel. In most cases, some portion of the emitted
radiant energy is visible to the human eye.
3.41
Flame
Detector - A radiant energy-sensing fire detector that detects the radiant
energy emitted by the flame.
3.42
Flame
Detector Sensitivity - The distance along the optical axis of the detector at
which the detector can detect a fire of specified size and fuel within a given
time frame.
3.43
Floor -
Area contained on each storey of the building.
3.44
Heat
Detector - A fire detector that detects either abnormally high temperature or
rate of temperature rise, or both.
3.45
Ionization
Smoke Detection - The principle of using a small amount of radioactive material
to ionize the air between two differentially charged electrodes to sense the
presence of smoke particles. Smoke particles entering the ionization volume
decrease the conductance of the air by reducing ion mobility. The reduced
conductance signal is processed and used to convey an alarm condition when it
meets preset criteria.
NOTE—It is suggested that
the use of such detectors be discouraged/avoided, as they have a radioactive
source. Multifunction detectors may be used instead.
3.46
Line
Detector- Detector which responds to the phenomenon sensed in the vicinity of a
continuous line.
3.47
Maintenance
- Repair service, including periodic inspections and tests, required to keep
the fire alarm system and its component parts in an operative condition at all
times, and the replacement of the system or its components when they become
undependable or inoperable for any reason.
3.48
Manual
Call Point - A manually operated device used to initiate an alarm signal. It
can be manual alarm system or part of automatic alarm system.
3.49
Mimic
Panel - A panel in which the floor/area plans of the premises are projected to
reduced scale to enable easy identification of the sector/zone.
3.50
Multi-Sensor
Fire Detector- Fire detector that monitors more than one physical and/or
chemical phenomenon associated with fire. Typical examples are a combination of
a heat and smoke detector or combination of heat and gas detectors.
3.51
Photoelectric
Light Obscuration Smoke Detection - The principle of using a light source and a
photosensitive sensor onto which the principal portion of the source emissions
is focused. When smoke particles enter the light path, some of
the light is scattered and some is absorbed, thereby reducing the light
reaching the receiving sensor. The light reduction signal is processed and used
to convey an alarm condition when it meets preset criteria.
3.52
Photoelectric
Light-Scattering Smoke Detection - The principle of using a light source and a
photosensitive sensor arranged so that the rays from the light source do not
normally fall onto the photosensitive sensor. When smoke particles enter the
light path, some of the light is scattered by reflection and refraction onto
the sensor. The light signal is processed and used to convey an alarm condition
when it meets preset criteria.
3.53
Point
Detector - Detector which responds to the phenomenon sensed in the vicinity of
a fixed point.
3.54
Power
Supply - A source of electrical operating power, including the circuits and
terminals connecting it to the dependent system components.
3.55
Projected
Beam-Type Detector - A type of photoelectric light obscuration smoke detector
wherein the beam spans the protected area.
3.56
Protected
Premises - The physical location protected by a fire alarm system.
3.57
Radio
Alarm System (RAS) - A system in which signals are transmitted from a radio
alarm transmitter (RAT) located at the protected premises through a radio
channel to two or more radio alarm repeater station receivers (RARSR) and that
are annunciated by a radio alarm supervising station receiver (RASSR) located
at the central station.
3.58
Rate-of-Rise
Detector- A device that responds when the temperature rises at a rate exceeding
a predetermined value.
3.59
Search
Distance - Distance which has to be travelled by a searcher within a zone in
order to determine visually the position of fire.
3.60
Sector -
A sub-division of the protected premises larger than a zone. A larger floor may
be demarcated into sectors, that is, addressed part of the
floor. A sector will normally contain many zones.
3.61
Shapes of
Ceilings - The shapes of ceilings can be classified as sloping or smooth.
3.62
Short
Circuit Isolators - Devices which may be connected into a transmission path of
a fire detection and fire alarm system, to limit the consequences of low
parallel resistance faults between the lines of this transmission path.
3.63
Sloping
Ceiling - A ceiling that has a slope.
3.64
Smoke Detector
- A device that detects visible or invisible particles of combustion.
3.65
Smooth
Ceiling - A ceiling surface uninterrupted by continuous projections, such as
solid joists, beams, or ducts, extending more than 100 mm below the ceiling
surface.
3.66
Spacing -
A horizontally measured dimension related to the allowable coverage of fire
detectors.
3.67
Spark - A
moving ember.
3.68
Spark/Ember
Detector - A radiant energy-sensing fire detector that is designed to detect
sparks or embers, or both. These devices are normally intended to operate in
dark environments and in the infra-red part of the spectrum.
3.69
Spark/Ember
Detector Sensitivity - The number of watts (or the fraction of a watt) of
radiant power from a point source radiator, applied as a unit step signal at
the wavelength of maximum detector sensitivity, necessary to produce an alarm
signal from the detector within the specified response time.
3.70
Standby
Supply - Power supply, commonly from a rechargeable battery, which is
automatically connected to the fire alarm system when the normal power supply
fails.
3.71
Trouble
Signal - A signal initiated by the fire alarm system or device indicative of a
fault in a monitored circuit or component.
3.72
Zone -
Area or space that has a group of automatic and/or non-automatic fire detection
devices for which there is a separate common display in the control and
indicating equipment.
4 GENERAL REQUIREMENTS
4.1
Automatic
fire detection and alarm system consists of fire detectors and manual call
points connected by appropriate cables to sector/zonal panels which in turn are
connected to control and indicating equipment (C and I). The equipment and
cables of automatic fire detection and alarm system should be independent of
any other system or cables, and should not be shared with any other system.
NOTE—Where analog
addressable fire alarm system is used, which consists of addressable devices
and suitable control panel, zoning and number of detectors shall be as per
4.2.4.
4.1.1
If the
requirement of detectors in any area is less than 20, division into
zones/sectors may not be necessary. Similarly, sectorization may not be
necessary if the number of zones is not very large and in case of bigger
premises, the premises may be divided into wings and each wing may have
sectors/zones.
4.1.2
Size of
the conventional panels is normally referred by number of zones. Each zone can
be connected with the conventional detectors not exceeding 20.
4.2 Detection Zones
4.2.1 General
- In most of the buildings an alarm
of fire may initiate a number of different activities, for example,
provision of assistance, commencement of fire fighting operations and
emergency evacuation procedures, summoning of fire brigade, etc. It is
essential that these activities are well co-ordinated. In the pre-planning
of emergency procedures for a building it is therefore important, for ease
of communication and synchronization of effort, to fix a convenient number
of easily identifiable sectors/zones, which the building can be divided.
- In order to direct those
responding to a fire alarm signal to the area of fire, all buildings with
the exception of smaller ones need to be divided into detection zones. The
zones need to be small enough for a fire to be located quickly. Even if
the system is addressable, zoning indications needs to be provided as this
often provides a quicker indication of the location of a fire than typical
addressable text displays. Zone indicators also provide a simple ‘at a
glance’ overview of the extent of fire or smoke spread. Also this would
enable fire fighters who are not familiar with the building to proceed to
the location of fire.
4.2.2
Requirements
for detection zones that contain non-addressable automatic detection system are
given below:
- The floor area of a single zone
shall not exceed 2000 m2.
- If the total area of a building is
less than 300 m-, a zone can cover more than one floor.
- If the total area of a building is
more than 300 m’, each zone shall be restricted to a single floor.
- Voids, if any, above or below the
floor area of a room can be included in the same zone as of the room
provided that the voids and the room constitute a single
compartment.
- The search distance, that is, the
distance that has to be travelled by anyone responding to a fire alarm
signal after entry to the zone in order for the location of the fire to be
determined visually, shall not exceed 30 m.
- Automatic fire detectors within
any enclosed stairwell, lift well or other enclosed shaft-like structures
shall be considered as a separate zone.
- If manual call points are located
on the landings of an enclosed staircase, such points at each level shall
be incorporated within the zone that serves the adjacent accommodation on
that level.
- The detectors and manual call
points within sectors/zones shall be wired to the control and indicating
equipment.
- The entire electrical installation
pertaining to the entire fire alarm system as described above shall be
independent of other systems.
- When a signal of fire is given it
is necessary that there shall be no confusion about the zone from which it
is received.
- To facilitate response by persons
providing assistance, the zone shall be small enough for a fire located
quickly.
- It is advisable to provide
adequate fire separation between the zones.
- In larger premises, the fire alarm
system shall be so designed and arranged that it is fully compatible with
the emergency procedures and provides at some central or convenient point,
or points, an indication of the zone from which an alarm has originated.
- In the case of two stage alarms,
clear and unambiguous signals shall indicate the emergency procedure to be
adopted throughout each zone.
- If the requirement of detectors or
call points is less than 20 in any area, division of the area into zones
is not necessary. Similarly, sectorization is not necessary if the number
of zones is not very large.
- For larger systems covering more
than one building it may be necessary to create sectors in addition to
zones in order to restrict the number of zones from which alarms originate
simultaneously or in succession.
- It is not always possible to
provide definite guidelines regarding the requirements for the division of
sectors, etc, as stated above due to the fact that the configurations are
not same for all risks. The division into zones and/or sectors shall be
decided based on careful consideration on the type of risk and
accessibility of zones in respect of main circulation routes and the main
control and indicating equipment.
- In general, the signals used in
different zones in the same premises shall be the same unless the
background noise in one or more zones is such as to require different
sounders.
- The zoning arrangement for systems
in multiple occupations shall take into account the fact that all the
premises may not be occupied at the same time. No zone shall include areas
in more than one occupancy.
- Remote indicator lamps outside
doors of rooms, cabins, etc, within a zone may be useful, if doors are
likely to be locked. Making an area easier to search, the use of remote
indicator lamps reduce the need for a large number of smaller zones.
- Where a special risk is present
within a large protected area, for example, a spray painting both in
engineering workshop and it is considered important to obtain rapid
identification of fire in that risk, such special risk shall be deemed as
a separate zone.
- Where a zone extends beyond a
single compartment, the zone boundaries shall be the boundaries of the
fire compartments.
NOTES
- It is permissible to have two
complete fire compartments in one zone, or two complete zones in one fire
compartment.
- It is not permissible to have a
zone, which extends into parts of two compartments, or a compartment,
which extends into parts of two zones.
- If the
arrangement of an area is complex and time is likely to be wasted in
search for the fire, notwithstanding any limits shown above, the area
shall be further sub-divided into zones that are easier to search.
4.2.3 Size and Number of
Zones (Protected with Manual Call Points)
- In systems containing only manual
call points, location of a fire is usually known to the person operating
the call point. As it is often difficult to get information in time to the
safety personnel, the restriction on the size and number of zones shall
also apply to the systems protected with manual call points only.
- To prevent misleading indication
of the position of the fire, it is advisable that manual call points be
indicated in the control equipment separately from the detectors in zones,
which are protected, by both detectors and manual call points. It is
strongly recommended that the circuits for the detectors and the call
points shall be different in case of conventional detection systems.
4.2.4
Size of
the Analog Addressable Panel is normally referred by number of
signalling Line Circuit (Loop). Loop shall be of Class A wiring. Class A
wiring, win be return loop. Tapping may be used from the loop as Class Î’
wiring.
NOTE—Refer Fig. 1 for
wiring details.
4.2.4.1
Length of
the loop shall not exceed more than 3 000 m where size of wire shall not be
less than 1.5 mm-or manufacturer recommended length and size may be considered
4.2.4.2
Number of
addressable detectors and devices per loop shall be as per manufacturer’s
recommendation. It is recommended that number of detectors per loop may not be
exceeding 90 percent of the full capacity. The number of detector and devices
per loop varies from 128 per loop, 240 per loop, 200 per loop, 99 Smoke Detectors, 99 Devices and 159
Detectors and 159 Devices. Based on the manufacturer design some devices need
external power supply and some devices supported by loop power.
4.2.4.3
Each loop
should not be divided into more than 8 fire zones. Minimum two isolators are
required per zone. It is recommended that a pair offault isolator modules be
employed for every 20-30 detectors/manual call points. In case of Loop circuit not mandatory to make zones.
4.2.4.4
In
partially addressable system zone addressable module are used in the loop to
connect non-addressable fire detection devices. Wherever non-addressable
detectors are connected provisions of 4.1.1 to 4.2.3 are to be followed.
4.3
The
sounders for fire alarm should be electronic hooters/horns/electric bell having
a frequency range of 500 to 1 000 Hz. The sound of the fire alarm should be
continuous although the frequency and amplitude may vary. If a two tone alarm
is used, at least one of the major frequencies should be within the frequency
range of500 to I 000 Hz. The distribution of fire alarm sounders should be such
that the alarm is heard at all sites which can be occupied within the protected
area.
A minimum
sound level of either 65 dB (A) or 5 dB (A) above any other noise likely to
persist for a period longer than 30 s, whichever is greater should be produced
by the sounders at any point which can be occupied in a building. Sounders should
be suitably distributed throughout the building in regard to attenuation of
sound caused by walls, floors ceilings and partitions. If the fire routine for
the premises requires the audible alarm to arouse sleeping persons, the minimum
sound level should be 75 dB (A) at the bed head with all doors shut. A large
number of quieter sounders rather than a few very loud sounders may be
preferable to prevent noise levels in some areas from becoming too loud. In
siting sounders in corridors to serve the surrounding rooms, account should be
taken of the attenuation of the sounder frequency by any dividing element. Most
single doors will give attenuation greater than 20 dB. Thus it is unlikely that
sounder noise levels in a room will be satisfactory if more than one dividing
wall or door separates it from: the nearest sounder. At least one sounder for
each fire compartment will be necessary. Sound levels exceeding 120 dB (A) in
areas which are occupied may produce hearing damage.
4.4
Besides,
the control centre, which may be located anywhere on the ground floor or even
the basement, wherever necessary repeater or annunciated panel should be
provided near the main entrance so that the maintenance staff notices the fault
condition or isolation, if any, for rectification.
4.5
A control
centre should be provided preferably on the ground floor where mimic panels,
control and indicating equipment and other equipment associated with it should
be installed.
5 AUTOMATIC FIRE DETECTORS
5.1
The types
of detectors covered in the standard are given in 5.1.1 and 5.1.2.
5.1.1 Heat Detectors
See IS
2175. Also find in this blog.
5.1.1.1 Fixed temperature
The fixed
temperature heat detectors are designed to operate when the temperature of the
detector exceeds a predetermined value.
5.1.1.2 Rate-of-rise temperature-cum-fixed
temperature detector
The
detectors are designed to operate within a given time:
- when the rate of temperature rise at the detector exceeds a predetermined value regardless of the actual temperature; and
- when temperature at the detector exceeds a predetermined value.
5.1.1.3 Probe type high
temperature hi-metal heat detector
Bi-metal
heat detectors are resettable and highly suitable to use above 80°C where
electronic components cannot be used. The following are type of application for
which probe type high temperature heat detectors are suitable.
Generator
enclosure, turbine enclosure, oven and furnace area, kitchen wood and other
places as per the requirement where automatic fire extinguishing/suppression
systems are used.
5.1.1.4 Linear heat sensing
cables
Linear
heat sensing cables can be broadly divided into two categories. Digital or
analogue, depending upon the principle by which the sensing cable registers a
change in temperature.
Digital
sensor consists of two core cable in which the conductors are separated by a
heat sensitive insulator. When a specified temperature is reached, the cable
insulation breaks down and an alarm is indicated. In the case of analogue
sensor, cores are separated by a negative temperature co-efficient polymer
whose resistance will reduce in proportion to the temperature increase.
These
cables are used for detecting fire and overheating in certain specific
occupancies such as:
- cables tunnels, trays and vaults;
- material conveyors;
- bulk storage multi-racked areas;
- rim seals of floating rooftanks
storing hazardous chemicals; and
- a few other special occupancies.
5.1.1.5 Heat detectors
application
These are
suitable for use in situation where sufficient heat is likely to be generated
and damage caused by heat generated by the fire constitutes main hazard. This
is to be minimized through early detection. In many buildings, especially
non-air-conditioned buildings, these conditions prevail where heat detectors
can be advantageously used. Heat detectors are however, not suitable for
protection of places where larger losses can be caused by small fires and where
safety of life is involved.
5.1.2 Smoke Detectors
See IS
11360.
5.1.2.1 Ionization smoke
detectors
Detectors
employing ionization chamber(s) as sensing means for detecting aerosols
given-off by fires.
5.1.2.2 Optical
(photoelectric) smoke detectors
A
detector whose operation is based on light attenuation by smoke and/or light
scattering by smoke particles.
5.1.3 Air Sampling Type Detector
Laser
type smoke detectors are used in this type of detection system. A detector that
consists of a piping or tubing distribution network that runs from the detector
to the areas to be protected. An aspiration fan in the detector housing draws
air from the protected area back to the detector through air sampling ports,
piping or tubing. At the detector, the air is analyzed for fire products.
Typical application of the systems is where a trace of smoke needs to be
detected, where high airflow can make traditional smoke detector inadequate.
5.1.3.1 Smoke detectors
application
Ionization
smoke detectors respond quickly to smoke containing small particles normally
produced in clean burning fires, but may respond slowly to optically dense
smoke which may be produced by smouldering materials. Certain materials like
PVC, when overheated, produced mainly large particles to which ionization
detectors are less sensitive. Optical smoke detectors respond quickly to smoke,
that is optically dense. Both types of detectors have a sufficiently wide range
of responses to be of general use. While selecting the detector, 5.2 to be
taken into account.
5.1.4 Spark/Ember Detector
A
spark/ember-sensing detector usually uses a solid state photodiode or
phototransistor to sense the radiant energy emitted by embers. Typically
between 0.5 μ and 2.0 μ in normally dark environments. These detectors can be
made extremely sensitive (microwatts), and their response times can be made
very short (microseconds). Spark/ember detectors are installed primarily to
detect sparks and embers that could, if allowed to continue to bum, precipitate
a much larger fire or explosion. Spark/ember detectors are typically mounted on
some form of duct or conveyor, monitoring the fuel as it passes by. Usually, it
is necessary to enclose the portion of the conveyor where the detectors are
located, as these devices generally require a dark environment. Extraneous
sources of radiant emissions that have been identified as interfering with the
stability of spark/ember detectors include the following:
- Ambient light;
- Electromagnetic interference (EMI,
RFI); and
- Electrostatic discharge in the
fuel stream.
5.1.5 UV Flame Detector
UV Flame
detector makes use of ultraviolet sensitive photocathode for detecting flame.
It has a narrow spectral sensitivity of 185 to 260 urn which is insensitive to
visible light.
5.1.5.1 1R Flame detector
Single or
multiple wavelength infra-red flame detector sense wavelength in the infra-red
spectrum. Almost all the materials that participate in the flaming combustion
emit ultraviolet radiation to some degree during flaming combustion, whereas
only carbon-containing fuels emit significant radiation at the 4.35 micron
(carbon dioxide) band used by many detector types to detect a flame.
The
following are types of application for which flame detectors are suitable:
- High-ceiling, open-spaced
buildings, such as warehouses and aircraft hangers;
- Outdoor or semi-outdoor areas
where winds or draughts can prevent smoke from reaching a heat or smoke
detector;
- Areas where rapidly developing
flaming fires can occur, such as aircraft hangers, petrochemical
production areas, storage and transfer areas, natural gas installations,
paint shops, or solvent areas;
- Areas needing high fire risk
machinery or installations, often coupled with an automatic gas
extinguishing system; and
- Environments those are unsuitable
for other types of detectors.
Some
extraneous sources of radiant emissions that have been identified as
interfering with the stability of flame detectors include the following:
- Sunlight;
- Lightning;
- X-rays;
- Gamma rays;
- Cosmic rays;
- Ultraviolet radiation from arc
welding;
- Electromagnetic interference (EMI,
RFI);
- Hot objects; and
- Artificial lightning.
5.2 Choice of Fire Detector
Fire
detectors are designed to detect one or more of three characteristics of a fire
that is smoke, heat or radiation (flame). No one type of detector is the most
suitable for all applications and final choice is dependent on the individual
circumstances. It is often useful to employ a combination of different types of
detectors. Most fire detectors are affected not only by the level of the
detected phenomena but also by the behaviour of the phenomena
with time. In some cases it is the rate of change of
phenomena; 10 others it is the effect, for example, delays in smoke entry or
thermal lags.
Every
fire alarm system is a compromise. It is possible to increase the sensitivity
of detectors but that would probably increase the frequency of false alarms.
It is
possible to reduce the losses by reducing the spacing between the detectors or
using several types of detectors in the same area but these would increase the
cost of the system.
It is
possible to increase the frequency of testing but this might lead to increased
disturbances on the premises.
Since
each type of detector has its own advantages and disadvantages, and no one type
of detector is most suitable for all applications, the choice of a detector to
be used for a particular application is always a compromise. Final choice will
depend primarily on: (a) the speed of response required; (b) the need to minimize
false alarms; and (c) the nature of the fire hazard. However, other factors
such as cost, suitability for the environment and maintenance requirements
shall also need to be considered.
In any
automatic detection system a detector has to discriminate between a fire and
the normal environment existing within the building. The system chosen shall
have detectors that are suited to the conditions and that provide the earliest
reliable warning.
Each type
of detector responds at a different rate to different kinds of fire. With a
slowly smoldering fire such as the initial stages of a fire involving
cardboard, a smoke detector would probably operate first. A fire that evolves
heat rapidly and with very little smoke could operate a heat detector before a
smoke detector could operate first.
In
general, smoke detectors would give appreciably faster responses than heat
detectors but may be liable to give false alarms.
A
combination of various detectors is necessary. The likely fire behaviour of the
contents of each part of the buildings, the processes taking place or planned
and the design of the building shall be considered. The susceptibility of the
contents to heat, smoke and water damage shall also be considered.
NOTE—Choice of detectors
based on all the above considerations for any particular application has been
shown in Annex A. However, this shall be purely considered as a guideline for
selection.
5.2.1 Life Safety Installation
Whenever
optical density of smoke exceeds 0.1 dB/m (10 m visibility), temperature rises
beyond 66°C and concentration of carbon monoxide 10 atmosphere exceeds 0.04
percent, and human survival is endangered. An alarm should be initiated before
these limits are reached so that the occupants are able to escape to safety.
Time overriding priority is to be given for detection of smoke because of the
following factors:
- Main threat to life in a fire
emergency emanates from smoke and toxic fumes;
- Smoke and lethal gases travel
rapidly to areas away from fire due to strong convection currents threaten
the life of the occupants even at far away places; and
- Detectable quantity of smoke from
a hostile fire precede detectable heat level and the development of lethal
atmosphere.
In a life
safety installation, it is, therefore, essential to:
- pay primary attention to early
detection of smoke and to protect escape routes including those areas from
which the routes might be hazarded by smoke detectors;
- ensure operation of detectors on
escape route before optical density exceeds 0.05 dB/m that is, visibility
falls below 20 m; and
- take into account any scheme of
pressurization/smoke control while providing detectors there.
5.2.1.1
Heat
detectors are not suitable for detecting fire in slow burning/air-conditioned
premises where temperatures required to operate them may only be reached after
the smoke density in the escape route/circulation areas has reached to the
critical level.
5.2.1.2
Heat
detectors are suitable in compartments where heat producing equipment (for
example, kitchen and pantry, etc) are used in closets or other unsupervised
spaces compact areas with low value contents.
5.2.2 Property Safety Installation
People
are not always present, mobile or alert in all parts of premises, housing
property even during normal occupancy hours. Premises may remain unattended or
unsupervised for long and short periods. When fire starts in such areas it gets
time to grow to a stage where it cannot be easily extinguished. Installation of
fire detectors enables early detection and easy extinction by reducing delay between
ignition and start of fire fighting measures. As rapid and extensive loss of
property is caused by flaming combustion, detectors should be efficient in
detecting flaming fire to keep losses to a minimum. It is
important to minimize incidence of false alarms particularly when detectors are
hooked up to actuate means of automatic extinction. Automatic extinction should
generally be initiated only on confirmation of two detecting signals to avoid
possibility of false actuation.
5.2.2.1
Computer/EDP
centre/other electronic equipment which have a very high value should be
protected by smoke detectors.
5.2.2.2
Archives,
high value libraries, and museums with high value combustibles should be
protected by combination of heat, flame, smoke detectors. The heat detectors
should be used on the racks and cupboards and smoke detectors in open space on
the ceiling. Flame detectors maybe used where height of the ceiling is more
than 9 m.
5.2.2.3
Flammable
liquid in small quantities stored in confined spaces where ambient temperature
is high or where chances of rapid heat build-up exist (such as garages, repair
shops, store areas, battery rooms, etc) heat or flame detectors should be
provided.
6 SITING OF FIRE DETECTORS
6.1
At the
time of installation and prior to commissioning, every fire detector should be
allotted an identification number, preceded by alphabetic initials showing the
type of detectors, for example, Z 1/SOI/20 meaning Smoke Detector, Ionization,
Zone 1, 20th Detector. Z2/SDOT/3 meaning Smoke Detector Optical, Zone 2, 3rd
Detector. HFT/4 (Fixed Temperature Heat Detector, 4th Detector) HFR Rate of
Rise Heat Detector, etc. A record of this should be maintained in the control
centre.
6.2
Heat
detectors should be so installed that the sensing element is not less than 25
mm and not more than 150 mm below the ceiling/roof level. For smoke detectors,
the sensing element should not be less than 25 mm and not more than 600 mm
below the ceiling/roof level except as necessary by site test. Where
possibility of stratification exists, the level of stratification should be
determined by measuring the vertical gradient of smoke density and additional
detector provided below the stratifying level if considered necessary by the site
test.
6.3
Siting
and Spacing Requirements of Detectors Covering General Cases
6.3.1 General
- Heat and smoke detectors depend on
convection to transport hot gases and smoke from the fire to the
detectors. Spacing and siting of detectors need to be based on the need to
restrict the time taken for this movement and to ensure that the products
of combustion reach the detectors in adequate concentration. In a
building, the hottest gas and the greatest concentration of smoke will
generally form at the highest parts of the enclosed areas, and it is here,
therefore, that heat and smoke detectors need to be sited.
- There are other constraining
factors in siting the detectors like the height of the ceiling (more the
height means more cooling of hot gases, thus diluting the performance of
the detectors), effects of stratification (where smoke does not rise to
the ceiling at all), type of roof (with beams extending deep below, etc),
air movement (within the protected area below the detectors), supply air
inlets (in the vicinity of detectors), HVAC systems (with high air change
rates), obstructions (in the path of rise of hot gases and smoke like
ducts, machinery parts, false ceilings, light fixtures, etc). Spacing and
siting of detectors shall address all these issues for optimum protection.
6.3.2
Siting
and spacing of detectors (common to all types of smoke and heat detectors):
- Under flat ceilings, the
horizontal distance between any point in a protected area and the detector
nearest to that point shall not exceed (1) 7.5 m in case of smoke
detector, and (2) 5.3 m in case of heat detector.
- In case of a sloping roof or
pitched ceiling (where the distance between the top of apex and bottom of
the roofexceeds 600 mm), spacing of detectors at or in the vicinity of
apex may be spaced between 7.5 m and 8.5 m for smoke detectors.
- Detectors shall not be mounted
within 500 mm of any walls, partitions or obstructions to flow of smoke or
hot gases, such as structural beams and ductwork, where the obstructions
are greater than 250 mm in depth.
- Where structural beams or ductwork
for light fittings or any other ceiling attachments, not greater than 250
mm depth, create obstacles to the flow of smoke, detectors shall not be
mounted closer to the obstruction than twice the depth of the obstruction.
- Where partitions or storage racks
that reach within 300 mm of the ceiling, they shall be construed as walls
that extend to the ceiling for the purpose of siting the detectors.
- Similarly, ceiling obstructions,
such as structural beams, deeper than 10 percent of the overall ceiling
height shall be construed as walls for the purpose of siting the
detectors, that is, each bay formed by such beams shall be treated
as separate enclosure for provision/spacing of detectors.
- Detectors shall not be mounted
within I m of any air inlet (supply air inlets of H VAC system) or a
forced ventilation system.
- Detector siting shall be such that
a clear space of 500 mm is maintained below each detector.
- Where detectors are constrained to
be fixed to the wall, they shall be sited in such a way that the top of
the detection element is between 150 mm and 300 mm below the ceiling and
the bottom of the detection element is above the level of door opening.
Additional detector shall be placed on the ceiling at a position 1.5 m
from any opening which might act like a flue.
- A detector shall be placed on the
protected side of the premises on the ceiling 1.5 m from any door, window
or any opening in the wall partitions separating the protected premises
from the other premises.
- All stairwells, lift shafts, other
utility shafts, etc, shall have a detector at the top. Lift machine rooms
shall be provided with a detector.
- All unenclosed staircase shall
have one detector at each main landing within the staircase.
- The detector shall also be
provided in cable tunnels, ducts, false floors, AC and AHU room, long AC
return ducts and distribution boards.
- No detector shall be subjected to
any interior decoration treatment, that is, painting, alteration of
exterior cover, etc, to conform with the environment.
- Every enclosure (that is, room or
cabin) shall have a detector at ceiling level and also under false
ceiling, if provided.
- Where there is more than one such
enclosure per floor, a response indicator shall be installed at the
entrance to such enclosures to indicate where the detector has actuated.
This arrangement shall also be followed in case of all concealed detectors
in false floors, plenums, shafts, tunnels, etc.
- Voids as in false ceiling/flooring
more than 800 mm shall be protected with detectors with spacing like in
normal installation. However, voids as in false ceiling/flooring less than
800 mm height need not necessarily have independent coverage unless the
void is such that the spread of fire products between the rooms or
compartments take place through it. Bathroom, lavatories, WC, etc,
however, need not be protected.
- For irregular shaped areas, the
spacing between the detectors may be greater than the determined spacing
provided the maximum spacing from the detector to the farthest point of a
side wall or comer within its zone of protection is not greater than 0.7
times the determined spacing.
Table 1
gives spacing parameter(s) at different ceiling heights for open areas under
smooth and flat ceiling with no-forced ventilation/air-flows.
NOTE—Refer Fig. 2 for the
arrangement details of the detectors.
6.3.3 Compensation to the Spacing of Detectors
- Height consideration
Spacing of 7.5 m for smoke
detectors is valid up to a height of 7 m only and that of 5.3 m for heat
detectors is valid only up to a height of 5 m. Beyond these heights, spacing
between the detectors shall be adjusted as follows:
- Smoke detectors for heights
between 7 m and 10 m - 5 m spacing
Beyond 10m height - Only
beam detectors or aspirating type detection systems
- Heat detectors for heights
between 5 m and 7 m - 3.5 m spacing
Beyond7m height- Not
allowed to install heat detectors
- High air movement consideration
- Spacing between detectors shall
be suitably reduced in areas where high air movement or where high air
changes prevail. Modified values of spacing are given in the Table 2.
- Detectors shall not be located in
the vicinity of supply air diffusers. Minimum distance between the
detector and the air inlets/diffusers shall be at least 1.5 m.
- Detectors shall be so mounted as
to favour the air flow towards return air openings.
- The above provisions shall not
disturb the normal population (count) of detectors, which is provided
assuming that air-handling systems are off.
- After designing the detector
spacing, it shall be cross-checked to ensure that there is at least one
smoke detector for every 100 m2 or one heat detector for
every 50 m’ of the compartment area.
6.3.4 Additional Requirements for Optical Beam Detectors
Table 1 Spacing(s) at Different Ceiling Heights
(Clause 6.3.2) |
||||||||||
Type of Detector
|
Spacing for Ceiling Height(s), m
|
Remarks
|
||||||||
10.0
|
||||||||||
(1)
|
(9)
|
(10)
|
||||||||
Smoke
detectors conforming to IS 11360 (both ionization and optical type)
|
5.0
|
The
spacing in corridors should not be greater than 3S/2
|
||||||||
Heat
detectors conforming to IS 2175
|
Grade
1 (time instant 205)
|
7
|
No
chance
|
6
|
5
|
5
|
4
|
3
|
Nil
|
|
Grade
2 (time instant 40 s)
|
6
|
5.5
|
5
|
4
|
3.5
|
3
|
Nil
|
Nil
|
Spacing
from the boundary wall should bekeptSI2
|
|
Grade
3 (time instant 60 s)
|
5
|
4.5
|
4
|
3
|
3.5
|
Nil
|
Nil
|
Nil
|
||
NOTES
1.
The
spacings have been adapted from charts of Fire Detection Institute of
America, adopting the parameters mentioned in 6.3 (nearest/rounded off
values).
2.
It is
presumed that ‘No chance’ means ‘No change’.
|
Table 2 Modified Spacing for High Air Movement Areas
[Clause 6.3.3(b)(1)] |
||
Air Changes/h Inside Block
|
Multiplying Factor for Modified
|
|
Spacing
|
(Area Coverage)
|
|
(1)
|
(2)
|
(3)
|
Less
than 7.5
|
1.00
|
(1.00)
|
8.5
|
0.95
|
(0.91)
|
10.0
|
0.91
|
(0.83)
|
12.0
|
0.83
|
(0.70)
|
15.0
|
0.74
|
(0.55)
|
20.0
|
0.64
|
(0.40)
|
30.0
|
0.50
|
(0.25)
|
60.0
|
038
|
(0.15)
|
A. Optical
beam-type detectors shall be sited in such a way that no point in the protected
B. In
case of a sloping roof or pitched ceiling (where the distance between the top
of apex and bottom of the roof exceeds 600 mm), distance stated in (a) above
may be increased to 8.5 m.
C. Where
optical beam type smoke detectors are used at more than 600 mm from ceiling
level in order to provide supplementary detection of rising smoke within a high
space (like Atrium etc), the width of the area protected on each side of
optical beam shall be regarded as 12.5 percent of the height of the above beam
from ground level.
D. Where
there is a probability of people walking through the beam or where the beam is
likely to be obstructed by forklifts, etc, detectors shall be mounted at a
suitable height.
E. Transmitters,
receivers and/or reflectors shall be mounted on a solid construction which
shall withstand vibrations, temperatures or any imposed load.
F. The
path length of the optical beam shall be within the limits specified by the
manufacturers.
G. Beam
detection area shall not exceed the detection zone in which it is installed.
H. The
effects of stratification shall be fully evaluated when locating the detectors.
I. If
mirrors are used with the projected beams (reflective beam detectors), they
shall be installed as per manufacturer’s recommendations.
J. Projected
beam detectors and their mirrors (reflective beam detectors) shall be mounted
on stable surfaces to prevent false or erratic operation due to vibrations and
movements in the vicinity.
K. The
beam shall be designed so that small angular movements of the light source or
receiver do not prevent operation due to smoke and do not cause nuisance
alarms.
L. The
light path of projected beam detectors (reflective beam detectors) shall be
kept clear of opaque obstacles at all times.
6.3.6 Siting of Flame Detectors
6.3.6.1 General
- The location and spacing of the
detectors shall be based on sound engineering evaluations taking into
account the following:
- Size of the fire requiring
detection,
- Fuel involved,
- Sensitivity of detectors,
- Distance between the fire and
detector,
- Radiant energy absorption of the
atmosphere,
- Presence of other sources of
emission,
- Purpose of detection system, and
- Response time required.
- Certain flame detectors respond to
the instantaneous level of radiation received while others depend upon the
level received over a period.
- In either case the response will
depend on the distance between the flame detector and the fire, since the
radiation level received is inversely proportional to the square of this
distance. Increased distance from the fire will, therefore, lead to an
increase in the size of the fire at detection.
- A clear line of sight to the area
being protected is of great importance but at the same time care shall be
exercised to avoid a direct line of sight to likely sources of non-fire
radiation to prevent false alarms.
6.3.6.2 Spacing guideline
- Sufficient number of detectors
shall be used and they shall be positioned such that no point requiring detection
in the hazard area is obstructed or outside the field of view of at least
one detector;
- In applications where, the fire to
be detected could occur in an area not on the optical axis of the
detector, the distance shall be reduced or alternatively more detectors
added to compensate for the angular displacement of the fire;
- The spacing of the detectors shall
vary from fuel to fuel. It is, therefore, necessary to fix the distances
as per the recommendations of the manufacturers;
- The location of the detectors
shall also be such that structural members or any other opaque objects or
materials do not impede their line of sight; and
- When installed outdoors, detectors
shall be shielded to prevent diminishing sensitivity due to rain, snow,
ice, etc, and allow a clear vision of the hazard area.
6.3.7 Siting of Spark/Ember Detectors
- The location and spacing of the
detectors shall be based on sound engineering evaluations taking into
account the following:
- Size of the spark or ember that
is to be detected,
- Fuel involved,
- Sensitivity of detectors,
- Distance between the fire and the
detector,
- Radiant energy absorption of the
atmosphere,
- Presence of other sources of
emission,
- Purpose of detection system, and
- Response time required.
- The system design shall specify
the size of spark or ember of the given fuel that the system is to detect.
- Spark detectors shall be
positioned so that all the points within the cross-section of the
conveyance duct, conveyor or chute, where the detectors are located, are
within the field of view of at least one detector.
- In any case the response will
depend on the distance between the detector and the fire, since the
radiation level received is inversely proportional to the square of this
distance. Increased distance from the fire will, therefore, lead to an
increase in the size of the fire at detection.
6.3.8 Siting of Manual Call Points
Manual
call points shall be so located that, to give an alarm, no person in the
premises has to travel distance of more than 30 m to reach them. When manual call
points are also installed external to the building, the travel distance shall
be 45 m.
Where
necessary, the travel distance may require to be reduced to less than 30 m, for
example, where there is difficulty in free access within the risk or in potentially
dangerous risks.
Call
points shall be fixed at a height of 1.4 m above the surrounding floor level,
at easily accessible, well-illuminated and conspicuous positions, which are
free of obstructions.
Where the
call points are not visible from the front as in the case of a long corridor,
they shall be surface mounted or semi-recessed in order to present a side
profile area of not less than 750 mm’.
Manual
call points shall be housed in dust pre of and moisture proof enclosure
properly sealed with rubber lining.
Manual
call point shall be located preferably near entry to staircases at various
levels.
The glass
surface shall be minimum 30 em’ in area and glass thickness shall not exceed 2
mm. Once the glass is broken the alarm shall sound on the floor as well as on
the Control and Indicating equipments and light shall glow to indicate its
operation. The alarm shall be maintained by the control and indicating
equipment even if someone presses the button subsequently.
6.3.9 ComputeriEDPIOther Electronic Equipment Installed in
Air-Conditioned Areas
Fire
alarm system and detection network shall, in addition to the requirements of
this standard, comply with various provisions listed under 8 of IS 12456. Where
the requirements differ, those specified in IS 12456 shall prevail.
6.3.10 Detectors (Smoke) in Ventilation Ducts
- Smoke detectors or probes shall be
installed in straight stretches of ductwork, at a distance from the
nearest bend, corner or junction of at least three times the width of the
duct; and
- The suitability of the smoke
detector for duct type application shall be evaluated within the
parameters defined by the manufacturers.
The
sampling inlet probe and the holes in the probe shall be arranged, according to
the manufacturers specifications, to cover as much of the duct as possible.
This provision normally calls for the probe to cover the wider dimension of the
duct and the length of the probe shall be at least two-thirds of that
dimension.
7 INSPECTION, TESTING AND MAINTENANCE
7.1 General
Even a
well designed and properly installed automatic fire alarm system will not be
able to render reliable and trouble-free service unless high standard of
maintenance and supervision are ensured during the entire service period of the
system. Regular inspections and scheduled preventive maintenance are critical
and should include all the components of the system.
7.2 Initial Installation
Inspection Tests
7.2.1
After
installation, a visual inspection of all the detectors should be made to make
sure that they are properly sited. Each detector should be inspected to ensure
that it is properly mounted and connected.
7.2.2
Restorable
heat detectors and restorable elements of combination detectors should be
tested by a heat source, such as a hair dryer, or a shielded heat lamp until it
responds, making sure that the sensing element is not damaged. After each heat
test, the detector should be reset. Precautions should be taken to avoid damage
of the non-restorable fixed temperature element of a combination rate of
rise/fixed temperature detector.
7.2.3
Non-resettable
fixed temperature heat detectors which are not to be heat-tested should be
tested mechanically or electrically for fire alarm function.
7.2.4
Heat
detectors with replaceable fusible alloy element should be tested first by
removing the element to see whether contact operate properly and then
reinserting them in proper position.
7.2.5
In
periodic testing, heat detectors should be visually examined for damage or
other conditions (such as heavy coats of paints, etc) likely to interface with
the correct operation.
7.2.6
Each
smoke detector should be tested to initiate an alarm at its installed location
with smoke or other approved aerosol which demonstrates that the smoke can
enter the chamber and initiate an alarm.
7.2.7
In order
to ensure that each smoke detector is within its sensitivity range, it should
be tested using either:
- a calibrated test method, or
- a manufacturer’s/supplier’s
approved calibrated sensitivity test instrument, or
- approved control equipment
arranged for the purpose, or
- other approved calibrated
sensitivity test method.
7.2.7.1
Detectors
found to have sensitivity outside the approved range should be replaced.
NOTE—Detector sensitivity
cannot be tested or measured using any spray/smoke producing device that
administers an unmeasured concentration of aerosol/smoke into the detector.
7.3 ServicinglPeriodical
Maintenance
7.3.1
To ensure
that regular and reliable servicing/maintenance of the systems and its
components is carried out; any of the following methods should be adopted:
- Through an agreement/contract with
the competent contractor who should attend to the maintenance/repair, when
necessary, promptly, and
- Where no such service contract can
be entered into for any reason, at least one qualified employee of the
user with suitable experience of electrical equipment should undergo
special training to deal with all aspects of basic servicing and
maintenance, including routine sensitivity tests/checks of the detectors,
as and when required.
7.3.2
For
institutional occupancies, such as hospitals, hotels, old people’s homes, etc,
the provision should include a requirement that an engineer should be on call
at all times and that request over the telephone for emergency service should
be executed promptly, within 24 h. Serving arrangement should be made
immediately on completion of the installation whether the premises are occupied
or not. If the premises are not occupied, special precautions should be taken,
if necessary, to protect the system against damage by dampness or other causes.
7.4 Maintenance Schedule
7.4.1
It is the
responsibility of the user of the equipment to ensure that proper instructions
are obtained from the manufacturer/supplier or installer regarding the routine
attention and test procedures.
7.4.2
The
routine to be adopted in individual premises may vary with the use of the
premises; equipment installed in corrosive or dirty environmental conditions
will need to be checked more thoroughly and at more frequent intervals than
that in clear and dry situations. Care should be taken that all equipments are
properly reinstated after testing. The occupants of the premises should be
notified of any test of the system that may result in the sounders being
operated.
7.4.3 Daily Attention by User
A check
should be made every day to ascertain that:
- the panel indicates normal
operation; ifnot, that any fault indicated is recorded in the log book and
is receiving urgent attention; and
- any fault warning recorded the
previous day has received attention.
7.4.4 Weekly Attention by the User
The
following tests should be made every week to ensure that the system is capable
of operating under alarm conditions:
- Once a week, at least one trigger
device or end of line switch on one zone circuit should be operated to
test the ability of the control and indicating equipment to receive a
signal and to sound the alarm and operate other warning devices. If there
is more than one zone on a system having unmonitored wiring, each
unmonitored zone should be tested each week, but without sounding the
alarm more than once. For systems having monitored wiring and up to 13
zones, each zone should be tested in turn but if there are more than
13zones, more than one zone may need to be tested in any week so that the
interval between tests on one zone does not exceed 13 weeks. It is
preferable that each time a particular zone is tested; a different trigger
device is used. An entry should be made in the log book quoting the
particular trigger device that has been used to initiate the test. If the
operation of the alarm sounders and/or the transmission of the alarm
signal has been prevented by disconnection, then a further test should be
carried out to prove the final reinstatement to the sounders, and if
permissible, the alarm transmission circuits.
- A visual examination of the
battery and connection should be made to ensure that they are in good
condition. Action should be taken to remedy any defect, including low
electrolyte level.
Any
defect noticed should be recorded in the log book and reported to the
responsible person, and action should be taken to correct it.
7.4.5 Quarterly Inspection and Test by the User
The
following check-list and test sequence should be carried out:
- Entries in the log book since the
previous inspection should be checked and any necessary action taken.
- Batteries and their connections
should be examined and tested to ensure that they are in good serviceable
condition.
- Where applicable, secondary
batteries should be examined to ensure that the specific gravity of
electrolyte in each cell is correct. Necessary remedial action should be
taken and an appropriate entry made in the log book. Care should be taken
to ensure that hydrometers, vessels, etc, used in the servicing of
alkaline secondary cells are not contaminated by acid and vice
versa. Contamination of electrolyte can ruin a cell.
- Primary batteries, including
reserves, should be tested to verify that they are satisfactory for a
further period.
- The alarm function of control and
indicating equipment should be checked by the operation of a trigger
device in each zone as described. The operation of alarm sounders and any
link to a remote manned centre should be tested. An ancillary function of
the control panel should also be tested where practicable. All fault
indicators and their circuits should be checked preferably by simulation
offault conditions. The Control and Indicating equipment should be
visually inspected for signs of moisture ingress and other deterioration.
- A visual inspection should be made
that structural or occupancy changes have not affected the requirements
for the sting of trigger devices (manual call points, smoke detectors and
heat detectors). The visual inspection should also confirm that a clear
space of at least 750 mm radius is preserved in all directions below every
detector, that the detectors are preferably sited and that all manual call
points remain unobstructed and conspicuous.
Any
defect should be recorded in the log book and reported to the responsible
person, and action should be taken to correct it.
7.4.6 Annual Inspection Tests
The
following checks and test sequence should be carried out:
- The instruction and test routines
detailed in 7.4.5(a) to (t).
- Operation of at least 20 percent
of the detectors in an installation should be checked each year and the
selection should be done in such a way that all the detectors in an
installation shall have been checked once in every 5 years - replacement
by a new one.
- Each detector should be checked
for correct operation using specified test equipment and method, except
non-resettable detectors. The checks to be carried out are specified in
7.2.2 to 7.2.5 in respect of heat detectors and, 7.2.6 and 7.2.7 in
respect of smoke detectors.
- Visual inspection should be made
to confirm that all cable fittings and equipment are secure, undamaged and
adequately protected.
- At least once in every three years
at the annual inspection, the electrical installation should be tested.
Any defect should be recorded in log book and suitable remedial action
should be taken.
- On completion of the annual
inspection, the entry should be made in register in respect of defects
found. After the defects are rectified, the entries should then again be
made.
7.5 General Points About
Detectors
It is
essential (particularly for installations involving life hazard) to ensure
specified range of sensitivity of the detectors being installed and that the
correct degree of sensitivity is maintained. Users should satisfy themselves on
this point. Sensitivity range should be checked on equipment as already
specifted. It is essential to apply frequent sensitivity checks and routine
tests as prescribed in the Code so that the correct sensitivity levels/degree
is maintained during the entire service span of the installation (see 7.2.7).
7.6 Cleaning and
Maintenance
Detectors
require periodic cleaning to remove dust or dirt that has accumulated. The
frequency of cleaning depends upon the type of detector and local ambient
conditions. In any case, the interval should not exceed a period of 3 months.
For each detector, the cleaning, checking, operating and sensitivity adjustment
should be attempted only after consulting manufacturer’s instructions. These
instructions should detail methods such as creating vacuum to remove loose dust
and insects, and cleaning heavy greasy deposits, following partial disassembly
or the cleaning or the washing of detectors to remove contamination, the
sensitivity test requirements in accordance with the relevant clauses should be
performed.
7.7 Tests Following an
Alarm or Fire
All
detectors suspected of exposure to a fire condition should be tested in
accordance with the provisions contained in this Code pertaining to annual
inspection tests. In addition, a visual check of the battery charger should be
earned out to ensure perfect serviceability. However, a check should be made to
the extent of damage, if any, to the cables and other components and also the
operation of the systems as a whole.
7.8 System Disconnection
During Testing
Care
should be taken to minimize the disruption of the normal use of the building by
alarm sounding during detector testing. If detectors are removed for testing or
servicing, replacement detectors should be provided.
7.9 Spares
It may
not be necessary to keep spares in premises other than covers for manual call
point and fuses and other essential spares which should be worked out based on
installation.
ANNEX A
MERITS AND RELATIVE DEMERITS OF VARIOUS TYPES OF DETECTORS
MERITS AND RELATIVE DEMERITS OF VARIOUS TYPES OF DETECTORS
(Clause 5.2)
Type of Detector (1)
|
Suitability and Merits (2)
|
Unsuitability and Demerits (3)
|
Smoke detectors (general)
|
Slow burning fires,
smoldering fires, for most of the areas where principal tire hazard is not
from the presence of flammable liquids. Fires involving wood, paper, textile,
etc, in earlier stages
|
Not sensitive for clean
burning fires which does not produce smoke particles; areas in which the
principal fire hazard is the presence of tlammable liquids or gases that
produce little smoke during a fire
|
Ionization smoke detector
|
General purpose smoke
detector-better for smoke containing small particles, such as rapidly burning
fast flaming fires
|
Less sensitive to the
larger particles found’in optically dense smoke of similar mass, such as can
result from smoldering fires including those involving polyurethane foam, or
overheated PVC. Areas subject to smoke, steam, dust or dirt during normal
use. Usage of these detectors are on way to phase out due to radiation
problems
|
Optical smoke detector
|
General purpose smoke
detector -better for smoldering fires
|
Areas subject to smoke,
steam, dust or dirt during normal use
|
Light scattering type
(smoke detector)
|
Sensitive to light
coloured smoke
|
Less sensitive to very
dark smoke which absorbs light rather than scattering it
|
Light obscuration type
(smoke) detector
|
Sensitive to very dark
smoke which absorbs light rather than scattering it
|
Areas subject to smoke,
steam, dust or dirt during normal use
|
Photo-thermal
multi-criteria detector
|
General purpose detector
- good for smoldering and fast flaming fires, optically dense smoke
|
Areas subject to smoke,
steam, dust or dirt during normal use, less sensitive to small particles
found in clean burning fires that produce little visible smoke
|
Optical beam smoke
detector
|
Large and high rooms,
open plan spaces with relatively high ceilings (for example warehouses),
fires not involving production of smoke (with built in thermal turbulence
detection). Suited for applications where anticipated fire would produce
black smoke. Sensitive to cumulative obscuration presented by a smoke field
|
Areas subject to smoke,
steam, dust or dirt during normal use. Less sensitive to colour of smoke.
Cannot detect clean colourless smoke
|
Aspirating (air-sampling)
type smoke detector
|
They are suitable for use
where usage of other types of smoke detectors present difficulties, such as
aesthetics, height and temperature of the enclosure. Sampling points can be
located almost anywhere unlike detectors which cannot be installed on walls,
storage racks, machinery space, floor voids, etc. Each sampling point is a
detector itself. Suitable for cold storage. Higher sensitivity levels, ease
of installation and most suitable for protection of high value and critical
equipment
|
Air-sampling
detectors are not suitable if the air movement due to HVAC requirements is
outside the range specified by the manufacturers
|
Heat detectors (general)
|
Clean
burning fires, such as those involving certain flammable liquids. Areas
subject to smoke, steam, dust or dirt during normal use, fires that evolve
heat and flame rapidly, suitable for rooms where heat producing equipment
like kitchen, pantry, boilers, DC sets, etc, are installed/used
|
Unlikely
to respond to smoldering and slow burning fires, unsuitable for high value
areas where a small fire can cause major damage. Areas in which presence of
smoke can pose a potential threat to the occupants
|
Rate-of-rise
heat detector
|
Areas
subject to smoke, steam, dust or dirt during normal use
|
Areas
subject to rapid changes of temperature or temperatures over 43 DC
|
Fixed
temperature heat detector
|
Areas
subject to smoke, steam, dust or dirt and rapid changes of temperature during
normal use
|
|
Multi-sensor
fire detector
|
Combines
the characters of two types of detectors, each of which responds to different
physical and/or chemical characteristics of fire. The purpose of combining
sensors in this way is to enhance the performance of the system in detection
of fire or its resistance to at least certain categories of false alarms or
both. There is significant potential for reduction of many types of false
alarm. It is also possible to disable an individual sensor depending on the
circumstances at the place of installation
|
|
Flame detectors (general)
|
High
ceiling, open spaced buildings like warehouses/aircraft hangers,
outdoor/semi-outdoor areas, areas where rapidly developing flames occur like
petrochemical/refinery/gas installations/paint shops, etc
|
Not
sensitive to smoldering/slow burning fires and hence cannot be called general
purpose detectors. Not suitable for the type of fires where, flaming can
occur only after substantial release of smoke
|
Infra
red flame detector
|
Same as
above, these detectors penetrate through smoke well. High speed, moderate
sensitivity. Suitable for indoor/outdoor applications
|
Affected
by temperature range in the vicinity, subject to false alarms caused by
blackbody radiation like heaters, incandescent lamps, halogen lamps,
flickering sunlight, etc and hence usage in such areas to be avoided.
Sensitive toIR radiation from sources like any hot surface,
ovens, furnaces, lamps, etc. also and due care shall be taken while
installation
|
Ultraviolet
flame detector
|
Highest
speed, highest sensitivity. Suitable for indoor applications
|
Not
sensitive for high ceiling, etc, as the radiation from fire is attenuated by
smoke. Random UV radiation from sources, such as lightning, arc welding, etc,
can cause false alarms and hence usage in such areas to be avoided. Blinded
by thick smoke and oil vapours on optics
|
IRfIR
flame detector
|
High
speed, moderate sensitivity, low false alarm rate, most suitable for chemical
and hydrocarbon flames in particular as signal received is processed at two
sensors. Suitable for indoor/outdoor applications
|
Somewhat
affected by temperature range in the vicinity, suffer from atmospheric
attenuations, especially on long range detection applications
|
UVfIR
detector
|
Highest
speed, highest sensitivity and low false alarm rate
|
Blinded
by thick smoke and oil vapours on optics. Suitable for indoor/outdoor
applications
|
IRfIR/IR
(IR3) detector
|
Highest
speed, highest sensitivity, lowest false alarm rate. Most suitable for
chemical and hydrocarbon flames in particular as signal received is processed
at three sensors
|
No
significant disadvantages. Suitable for indoor/outdoor applications
|
Spark
detector
|
Spark
detectors are suitable for detection of sparks some types of duct or
conveyor, monitoring the fuel, etc, as it passes by. Usually, it is necessary
to enclose the portion of the conveyor where the detectors are located, as
these devices generally require a dark environment
|
Extraneous
sources of radiant emissions that have been identified as interfering with
the stability of spark detectors include: (a) ambient light (b)
electromagnetic interference (EMI, RFI), and (c) electrostatic discharge in
the fuel stream
|
Ember
detector
|
Same as
above except that ember detectors can also detect fires in lit environment
like coal conveyors, etc
|
Detector
window clarity shall always be ensured
|
Linear
heat sensing cables
|
Cables
tunnels, trays and vaults, material conveyors, bulk storage multi-racked
areas, rim seals of floating roof tanks storing hazardous chemicals, and a
few other special occupancies
|
Not
suitable at all applications other than what is specified
|
Bureau of Indian Standards
BIS is a
statutory institution established under the Bureau of Indian Standards
Act, 1986 to promote harmonious development of the activities of
standardization, marking and quality certification of goods and attending to
connected matters in the country.