Smoke Detector & Heat Detector
Mounting Heights BS5839
There
are essentially two types of initiating devices used in a typical fire alarm
system: automatic and manual.
Typical
automatic devices include spot-type smoke detectors, rate-of-rise heat sensors,
fixed-temperature sensors, photoelectric smoke detectors, sprinkler heads and
duct-type smoke detectors.
Manual
activation is commonly accomplished using a manual fire pull, and automatic
detection happens without human intervention. NFPA 72, also called the National
Fire Alarm Code (NFAC), is the primary document used when an engineer designs,
and an EC or fire alarm technician installs, a fire alarm system.
BS5839
makes reference to recommendations of maximum mounting heights for different
types of detectors. This is to ensure that the detector is still
effective when mounted at high levels. The recommendations of BS5839
split the mounting heights up into two categories. These categories are
standard BS5839 systems and systems with a 5 minute fire service response time.
Below
is a series of recommended mounting heights for fire alarm system equipment including
different types of smoke detector (including Optical Beam Detectors) and Heat
Detectors.
The
table below also shows heights which detectors are permitted to be mounted at
if 10% or less of the ceiling is the height shown.
Mounting Heights
Detector Type
|
Maximum Ceiling Height (m) Cat L/P
|
5 Minute Response (m) Cat P
|
Rate
of Rise Heat Detector
|
9
Meters (10.5 meters for 10% of Ceiling)
|
13.5
Meters (15 meters for 10% of Ceiling)
|
Fixed
Temperature Heat Detectors
|
7.5
Meters (10.5 meters for 10% of Ceiling)
|
12
Meters (15 meters for 10% of Ceiling)
|
Smoke
Detectors
|
10.5
Meters (12.5 meters for 10% of Ceiling)
|
15
Meters (18 meters for 10% of Ceiling)
|
CO
Point Detectors
|
10.5
Meters (12.5 meters for 10% of Ceiling)
|
15
Meters (18 meters for 10% of Ceiling)
|
Optical
Beam Detectors
|
25
Meters (25 meters for 10% of Ceiling)
|
40
Meters (40 meters for 10% of Ceiling)
|
Automatic
smoke detector placement is another important aspect of a fire alarm
installation. Unless every smoke detector is placed properly, false alarm, or
even no alarms, can occur. Either way, the client suffers, and the low-voltage
contractor looks bad in the process.
The
most common type of smoke detector used in residential and commercial settings
is the spot-type detector. According to Section 5.7.3.2, NFPA 72, 2007 Edition,
spot-type smoke detectors can be mounted either on the side wall or ceiling.
When using the side wall, mount the device no closer than 4 inches from the
ceiling.
The
maximum distance is 12 inches. The distance from detector to side wall when
mounting the same smoke detector on a ceiling is the same 4 inches.
Ceiling-mounted units also must be placed no closer than 4 inches from a side
wall.
Spacing
between smoke detectors is likewise important. On a smooth ceiling, the common
distance between each smoke detector is 30 feet. According to Section
5.7.3.2.3.5, all points on a smooth ceiling should have a smoke detector within
0.7 times the selected spacing or 21 feet.
Not
all ceilings are smooth; thus, the spacing between smoke detectors will vary.
To ensure optimum performance and compliance, refer to Chapter 5 of NFPA 72,
2007 Edition, for a specific situation. Read also Codes & Standards, page
140.
Space
and placement both matter when planning your fire alarm package. Thorough
preparation often leads to a successful installation.
As per IS: 2189:2008 under clause 6.3.2 Siting and spacing of detectors (common to all types of smoke and heat detectors):
As per IS: 2189:2008 under clause 6.3.2 Siting and spacing of detectors (common to all types of smoke and heat detectors):
- Under flat ceilings, the
horizontal distance between any point in a protected area and the detector
nearest to that point shall not exceed 7.5 m in case of smoke
detector, and 5.3 m in case of heat detector.
- In case of a sloping roof or
pitched ceiling (where the distance between the top of apex and bottom of
the roof exceeds 600 mm), spacing of detectors at or in the vicinity of
apex may be spaced between 7.5 m and 8.5 m for smoke detectors.
- Detectors shall not be mounted
within 500 mm of any walls, partitions or obstructions to flow of smoke or
hot gases, such as structural beams and duct work, where the obstructions
are greater than 250 mm in depth.
- Where structural beams or duct work
for light fittings or any other ceiling attachments, not greater than 250
mm depth, create obstacles to the flow of smoke, detectors shall not be
mounted closer to the obstruction than twice the depth of the obstruction.
- Where partitions or storage racks
that reach within 300 mm of the ceiling, they shall be construed as walls
that extend to the ceiling for the purpose of siting the detectors.
- Similarly, ceiling obstructions,
such as structural beams, deeper than 10 percent of the overall ceiling
height shall be construed as walls for the purpose of siting the
detectors, that is, each bay formed by such beams shall be treated
as separate enclosure for provision/spacing of detectors.
- Detectors shall not be mounted
within 1m of any air inlet (supply air inlets of H VAC system)
or a forced ventilation system.
- Detector siting shall be such that
a clear space of 500 mm is maintained below each detector.
- Where detectors are constrained to
be fixed to the wall, they shall be sited in such a way that the top of
the detection element is between 150 mm and 300 mm below the ceiling and
the bottom of the detection element is above the level of door opening.
Additional detector shall be placed on the ceiling at a position 1.5 m
from any opening which might act like a flue.
- A detector shall be placed on the
protected side of the premises on the ceiling 1.5 m from any door, window
or any opening in the wall partitions separating the protected premises
from the other premises.
- All stairwells, lift shafts, other
utility shafts, etc, shall have a detector at the top. Lift machine rooms
shall be provided with a detector.
- All unenclosed staircase shall
have one detector at each main landing within the staircase.
- The detector shall also be
provided in cable tunnels, ducts, false floors, AC and AHU room, long AC
return ducts and distribution boards.
- No detector shall be subjected to
any interior decoration treatment, that is, painting, alteration of
exterior cover, etc, to conform with the environment.
- Every enclosure (that is, room or
cabin) shall have a detector at ceiling level and also under false
ceiling, if provided.
- Where there is more than one such
enclosure per floor, a response indicator shall be installed at the
entrance to such enclosures to indicate where the detector has actuated.
This arrangement shall also be followed in case of all concealed detectors
in false floors, plenums, shafts, tunnels, etc.
- Voids as in false ceiling/flooring
more than 800 mm shall be protected with detectors with spacing like in
normal installation. However, voids as in false ceiling/flooring less than
800 mm height need not necessarily have independent coverage unless the
void is such that the spread of fire products between the rooms or
compartments take place through it. Bathroom, lavatories, WC, etc,
however, need not be protected.
- For irregular shaped areas, the
spacing between the detectors may be greater than the determined spacing
provided the maximum spacing from the detector to the farthest point of a
side wall or comer within its zone of protection is not greater than 0.7
times the determined spacing.
As per IS: 2189:2008 under clause 6.3.3 Compensation to the Spacing of Detectors
- Height consideration
Spacing of 7.5 m for smoke
detectors is valid up to a height of 7 m only and that of 5.3 m for heat
detectors is valid only up to a height of 5 m. beyond these heights, spacing
between the detectors shall be adjusted as follows:
- Smoke detectors for heights
between 7 m and 10 m - 5 m spacing
Beyond 10m height - Only
beam detectors or aspirating type detection systems
- Heat detectors for heights
between 5 m and 7 m - 3.5 m spacing
Beyond7m height- Not
allowed to install heat detectors
- High air movement consideration
- Spacing between detectors shall
be suitably reduced in areas where high air movement or where high air
changes prevail.
- Detectors shall not be located in
the vicinity of supply air diffusers. Minimum distance between the
detector and the air inlets/diffusers shall be at least 1.5 m.
- Detectors shall be so mounted as
to favour the air flow towards return air openings.
- The above provisions shall not
disturb the normal population (count) of detectors, which is provided
assuming that air-handling systems are off.
- After designing the detector
spacing, it shall be cross-checked to ensure that there is at least one
smoke detector for every 100 m2 or one heat detector for
every 50 m’ of the compartment area.