How Should A Fire Alarm System Be Tested
We
are often asked by customers "How Often Should A Fire Alarm System Be
Tested?". The British Standard associated with fire alarm systems gives
some recommendations as to when and how often a fire alarm system should be
tested.
BS5839
recognises that although modern fire alarm systems incorporate a high degree of
monitoring, so that faults are indicated at the control panel position, it is
still necessary for a responsible person nominated by the user to ensure that
fault indications at the panel are identified for appropriate action. It
is also impertitive for a regular test to be carried out to ensure that there
has not been any major failure of the entire system, or significant part of the
system.
How Often Should The User Test Their Fire
Alarm System?
BS5839
recommends that the user / responsible person for the fire system tests their
fire alarm system on a weekly basis. The recommendations of the standard
are as follows:-
- Every week, a manual call point
should be operated during normal working hours. It should be
confirmed that the control equipment (fire alarm panel) is capable of
processing a fire alarm signal and providing an output to fire alarm
sounders installed on the system, and if applicable to ensure that the
fire alarm signal is correctly received at any fire alarm receiving centre
to which fire alarm signals are transmitted. It is not necessary to
confirm that all fire alarm sounder circuits
operate correctly at this time of the test.
- The British Standard recommends
that the weekly test carried out by the user should be carried out at
approximately the same time each week. Instructions to occupants
should then be that they should report any instances of poor audibility of
the fire alarm sounders. In systems with staged alarms that
incorporate an 'Alert' and 'Evacuate' alarm signal, the two signals should
be operated, where praticable, sequentially in order they would occur at
the time of a real fire event (i.e. 'Alert'
and then 'Evacuate').
- In premises in which some
employees only work during hours other than at which the fire alarm system
is normally tested, an additional test(s) should be carried out at least
once a month to ensure familiarity of these employees with the fire alarm
system singal(s).
- A different manual call point
on the system should be used at the time of every weekly test, so that all
manual call points within the building are tested in rotation over a
prolonged period. There is no maximum limit for this period (e.g. in
a system with 150 manual call points, the user will test each call point
every 150 weeks). The result of the weekly test and identity of the manual
call point should be recorded in the system log book.
- The duration for which any fire
alarm signal is given at the time of the weekly test by the user should
not normally exceed one minute, so that, in the event of a fire at the
time of the weekly test, occupants will be warned by the prolonged
operation of the fire alarm devices.
- Voice alarm systems should be tested weekly in accordance with the recommendations of BS5839-8.
Recommendations For Monthly Attention By The
User Of The Fire Alarm System
Each
month BS5839 makes the following recommendations upon the monthly attention on
a fire alarm systems each month if applicable.
- If an automatically started emergency
generator is used as part of the standby power supply of a fire alarm
system, it should be started up once each month by simulation of failure
of the normal power supply and operated on-load for at least one
hour. The test should be carried out in accordance with the
instructions of the generator manufacturer, including instructions on the
load that should be operated. At the end of the test, the fuel tanks
should be left filled, and the oil and coolant levels should be checked
and topped up if necessary.
- If vented batteries are used as
a standby power supply, a visual inspection of the batteries and their
connections should be made to ensure that they are in good
condiction. Action should be taken to rectify any defect, including
low electrolyte level.
Note: Care should be taken to ensure that any person
undertaking these monthly tasks is competent to do so safely and has the
relevant technical knowledge and training.